Appendix B
Troubleshooting
The PowerView reports various messages on the display, including alarm status and changes in system configura- tion. This section lists all PowerView display messages, what each means, and an appropriate corrective action.
Note: More than one of these messages may occur at one time. If this happens, be sure to review all of the messages for a better understanding of the system condition.
| PowerView | Meaning | Corrective Action |
| Message | ||
|
|
| |
|
|
|
|
| #Pwr modules changed | At least one power module has been | No corrective action necessary. Proceed |
| since last ON. | added, or removed from the | with the startup. |
|
| SymmetraTM since the last time the |
|
|
| Pwr ON command was issued. |
|
|
|
|
|
| #Batteries changed since | At least one battery module has been | No corrective action necessary. Proceed |
| last ON. | added, or removed from the | with the startup. |
|
| SymmetraTM since the last time the |
|
|
| Pwr ON command was issued. |
|
|
|
|
|
| No Redundant | There is no RIM installed. | Proceed with the startup, or abort the |
| Intelligence Module. |
| startup, and install a RIM. |
|
|
| Note: Without a functioning RIM, there |
|
|
| is no redundancy in the event of a MIM |
|
|
| failure. |
|
|
|
|
| Batt capacity less than | The battery capacity of the | Option #1: Abort the startup, and allow |
| Return Batt Cap | SymmetraTM is less than the user | batteries to recharge. |
|
| specified minimum battery capacity | Option #2: Continue startup, with less |
|
| required to turn on the load. | than minimum battery capacity. |
|
|
|
|
| Input Freq outside | The input frequency to the | Option #1: Improve the frequency of the |
| configured range | SymmetraTM is outside the configured | incoming voltage. |
|
| range. The output frequency will | Option #2: Widen the range of the |
|
| not synchronize with the input | acceptable incoming frequency with the |
|
| frequency. Normal bypass is not | PowerView. |
|
| available. | Select.) |
|
|
| Option #3: Proceed with startup. Normal |
|
|
| bypass is not available. |
|
|
|
|
| AC adequate for UPS but | The SymmetraTM will function online | Option #1: Improve the incoming |
| not for bypass | with the input voltage, but in the | voltage. |
|
| event that bypass is required, the | Option #2: Proceed with startup. Normal |
|
| input voltage is not adequate to | bypass is not available. |
|
| power the load equipment. |
|
|
|
|
|
| Low/No AC input, | Input voltage is not adequate to start | Option #1: Abort startup until acceptable |
| startup on battery | the SymmetraTM. If startup proceeds, | input voltage is present. |
|
| SymmetraTM will function from | Option #2: Proceed with startup. Battery |
|
| battery. | will be discharged. |
|
|
|
|
Appendix B - Troubleshooting - Page 1 | |
|