System Startup Procedure
Notice!
νRefer to Appendix A for information about the PowerView Interface.
νAt least one power module, one battery module, and the main intelligence module must be installed before the system will start.
νLoad equipment can be left connected during this
νThe PowerView can be configured to display French, Italian, German or Spanish. (Appendix A, page 3.)
1.Apply input power to the system from the utility power source.
2.Switch the input circuit breaker(s) and the system enable switch on.
3.Wait approximately 15 seconds to allow the system intelligence module to boot up and complete a startup sequence.
4.Open the
Note: The PowerView may display some “configuration change” messages because the system was configured at the factory with a different number of power or battery modules than are now installed. Disregard these messages, and press the escape key to close them.
5.Verify that all power, battery and intelligence modules are detected by the system and are functioning prop- erly by reviewing all status screens on the PowerView. (From the Status menu, open status screens for battery, power, main intelligence, and redundant intelligence modules. See Appendix A, page 5.)
Note: If a problem is reported, ensure the system component in question is properly installed. If the problem persists, refer to the troubleshooting information in Appendix B.
6.Turn load on. (From the Control menu, click Turn Load On. See Appendix A, page 5.)
7.Replace all front grill covers. Make sure all wiring panels are firmly secured to the frame.
8.The SymmetraTM system is now ready to support the load equipment and be configured to meet specific power needs.
Page 4 - | |
|