American Power Conversion SYMSTRF3I user manual System Startup Procedure

Page 40

System Startup Procedure

Notice!

νRefer to Appendix A for information about the PowerView Interface.

νAt least one power module, one battery module, and the main intelligence module must be installed before the system will start.

νLoad equipment can be left connected during this start-up procedure, but it should be switched off until startup is complete.

νThe PowerView can be configured to display French, Italian, German or Spanish. (Appendix A, page 3.)

1.Apply input power to the system from the utility power source.

2.Switch the input circuit breaker(s) and the system enable switch on.

3.Wait approximately 15 seconds to allow the system intelligence module to boot up and complete a startup sequence.

4.Open the top-level menu screen on the PowerView display. (See Appendix A, page 4.)

Note: The PowerView may display some “configuration change” messages because the system was configured at the factory with a different number of power or battery modules than are now installed. Disregard these messages, and press the escape key to close them.

5.Verify that all power, battery and intelligence modules are detected by the system and are functioning prop- erly by reviewing all status screens on the PowerView. (From the Status menu, open status screens for battery, power, main intelligence, and redundant intelligence modules. See Appendix A, page 5.)

Note: If a problem is reported, ensure the system component in question is properly installed. If the problem persists, refer to the troubleshooting information in Appendix B.

6.Turn load on. (From the Control menu, click Turn Load On. See Appendix A, page 5.)

7.Replace all front grill covers. Make sure all wiring panels are firmly secured to the frame.

8.The SymmetraTM system is now ready to support the load equipment and be configured to meet specific power needs.

Page 4 - Start-Up Procedure

990-7167-001

 

Image 40
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Limited Warranty Life Support PolicyTable of Contents Page Safety Information Safety SymbolsOperation Symbols Radio Frequency InterferenceModels WelcomeFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SymmetraTM Components Description Specific To Model SYMSTRF3IBasic Operation Glossary of SymmetraTM Terms 8 Introduction Site Requirements Operating Space RequirementsRear Clearance Front ClearanceStructural Requirements ModelsEnvironmental Requirements Short-Term Battery Module Storage RequirementsHeat Output Electrical Requirements Input/Output VACElectrical Requirements EPO Switch EPO SpecificationsElectrical Wiring Overview SymmetraTM Component Shipping Weight Shipping Dimensions Receiving and UnpackingReceiving the SymmetraTM Inspect PackagingMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Electrical Installation Model SYMSTRF3IEPO Switch Wiring Required Electrical RequirementsElectrical Wiring Overview Input/Output Wiring Wire Size Input/Output Wiring ProcedureMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Bypass Balance Transformer Wiring Procedure Optional Wiring Symbol Description Minimum Wire GaugeWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Startup Procedure Securing The Frame Setting The Leveling FeetPower Module Installation Battery Module Installation System Startup Procedure Configuration and Advanced Operation ConfigurationDisplay Settings System Settings SetupAdvanced Operation PowerView Interface PowerView Components PowerView Component DescriptionLanguage Configuration Language Chip Replacement ProcedureStartup Screen Top-Level Menu ScreenControl StatusPowerView Commands SetupAccessories LoggingDisplay Function OptionsDiagnostics HelpWall Mounting the PowerView Troubleshooting PowerView Meaning Corrective Action Message Start-UpPowerView Meaning Corrective Action Message General PowerView Meaning Corrective Action Message Module AlarmFailure ThresholdPowerView Meaning Corrective Action Message Bypass FaultPowerView Meaning Corrective Action Message General6 Troubleshooting Appendix B Module Replacement Module Failure Alarm IndicatorsTechnical Support & Obtaining Replacement Module Returning Modules to APCBattery Module Replacement Replacement Battery Module VerificationPower Module Replacement Replacement Module VerificationMain Intelligence Module Replacement Replacement MIM VerificationRedundant Intelligence Module Replacement Replacement RIM Verification6 Module Replacement Appendix C Input Specifications SpecificationsOperation Physical Specifications Output SpecificationsCompliance Specifications Page Tel0800 180