American Power Conversion SYMSTRF3I user manual Main Intelligence Module Replacement

Page 63

Main Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array.

The intelligence module resides under the redundant intelligence module in the upper right corner of the frame. Note: If a functioning RIM is installed, it will provide limited control of the SymmetraTM until the replacement MIM is installed. If a functioning RIM is not installed, either the SymmetraTM must be placed in manual bypass mode or the load equipment must be switched off. To place the SymmetraTM in manual bypass, switch the maintenance bypass switch to the “on” position.

Important: When the SymmetraTM is in bypass mode, the load equipment is unprotected from power failure.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the MIM out of the frame.

5.Slide the replacement MIM into the frame. If SymmetraTM was placed in manual bypass in step 1 above, return to normal operation by switching the maintenance bypass switch back to the “off” position.

Replacement MIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in below to ensure that the replacement MIM is functioning properly. (Status: On & OK).

Redundant Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array.

The redundant intelligence module resides above the intelligence module in the upper right corner of the frame. Note. A RIM can only be replaced if a functioning MIM is installed or the load equipment is switched off.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the RIM out of the frame.

5.Slide the replacement RIM into the frame.

Replacement RIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in below to ensure that the replacement RIM is functioning properly. (Status: On & OK).

990-7171-001

Appendix C - Module Replacement - Page 5

 

Image 63
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Life Support Policy Limited WarrantyTable of Contents Page Safety Symbols Safety InformationRadio Frequency Interference Operation SymbolsWelcome ModelsFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SYMSTRF3I SymmetraTM Components Description Specific To ModelBasic Operation Glossary of SymmetraTM Terms 8 Introduction Front Clearance Site RequirementsOperating Space Requirements Rear ClearanceModels Structural RequirementsShort-Term Battery Module Storage Requirements Environmental RequirementsHeat Output VAC Electrical Requirements Input/OutputEPO Specifications Electrical Requirements EPO SwitchElectrical Wiring Overview Inspect Packaging SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Receiving the SymmetraTMMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Model SYMSTRF3I Electrical InstallationElectrical Requirements EPO Switch Wiring RequiredElectrical Wiring Overview Input/Output Wiring Input/Output Wiring Procedure Wire SizeMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Wiring Symbol Description Minimum Wire Gauge Bypass Balance Transformer Wiring Procedure OptionalWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Securing The Frame Setting The Leveling Feet Startup ProcedurePower Module Installation Battery Module Installation System Startup Procedure System Settings Setup Configuration and Advanced OperationConfiguration Display SettingsAdvanced Operation PowerView Interface PowerView Component Description PowerView ComponentsLanguage Chip Replacement Procedure Language ConfigurationTop-Level Menu Screen Startup ScreenStatus ControlSetup PowerView CommandsLogging AccessoriesFunction Options DisplayHelp DiagnosticsWall Mounting the PowerView PowerView Meaning Corrective Action Message Start-Up TroubleshootingPowerView Meaning Corrective Action Message General Threshold PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassGeneral PowerView Meaning Corrective Action Message6 Troubleshooting Appendix B Module Failure Alarm Indicators Module ReplacementReturning Modules to APC Technical Support & Obtaining Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementReplacement Module Verification Power Module ReplacementReplacement RIM Verification Main Intelligence Module ReplacementReplacement MIM Verification Redundant Intelligence Module Replacement6 Module Replacement Appendix C Specifications Input SpecificationsOperation Output Specifications Physical SpecificationsCompliance Specifications Page Tel0800 180