American Power Conversion SYMSTRF3I user manual Control, Status

Page 47

Control

 

Function

 

 

 

 

 

 

 

 

Turn Load On/Off

 

The system control for delivery of output power to connected equipment.

 

 

 

 

 

 

 

 

Do Self Test

 

Initiates a system self test. Runs through all self-diagnostics. If a problem is

 

 

 

detected, an error message will be displayed.

 

 

 

 

 

 

 

 

 

 

 

 

 

Simulate Power Failure

 

Simulates a power failure/return. Used to test if the server recognizes this

 

 

 

event.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Requires the Symmetra to be connected to PowerChute software. Initiates a

 

 

 

 

 

signal for the server to shutdown. After the user-defined "Low-Battery

 

 

Graceful Reboot

 

Duration," the output power is switched off for the duration of the user-

 

 

 

 

 

defined "Return Delay." Then the output power is switched on again. See

 

 

 

 

 

Setup>Shutdown to set these time delays.

 

 

 

 

 

 

 

 

 

 

 

Requires the Symmetra to be connected to PowerChute software. Initiates a

 

 

Graceful Turn Off/On

 

signal for the server to shutdown. After the user-defined "Low-Battery

 

 

 

Duration," the output power is switched off. See Setup>Shutdown to set

 

 

 

 

 

 

 

 

 

 

these time delays.

 

 

 

 

 

 

 

 

Start Runtime Calibration

 

Calculates an accurate battery runtime measurement. Delivers load output

 

 

 

power from battery source. Discharges battery to 50% of their capacity.

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Into/Out Of Bypass

 

The system control of the bypass function. Power is delivered directly from

 

 

 

utility source to load equipment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status

Function

 

 

 

 

 

 

 

Voltage/Current Status Screen

Displays input voltage, output voltage, and output current information.

 

 

 

 

 

 

 

Percentage Load - No Redundancy

Compares the current load to the total capacity of all power modules.

 

 

 

 

 

 

 

 

 

Compares the current load to the total capacity of all power modules except

 

 

Percentage Load - With

the power modules that are set aside by the "Fault Tolerance" alarm threshold.

 

 

For example, if there are four power modules installed, and the fault tolerance

 

 

Redundancy

alarm threshold is set to "1," this percentage of load uses only 3 power

 

 

 

 

modules for the calculation. See Setup>Alarm Thresholds to set the

 

 

 

 

redundancy level.

 

 

 

 

 

 

 

Input and Output Frequencies

Displays the measured input and output frequencies

 

 

 

 

 

 

 

Battery Status Screen

Displays battery module source voltage, capacity, runtime, and status

 

 

information.

 

 

 

 

 

 

 

 

 

 

 

Power Module Status Screen

Displays power module source capacity, fault tolerance, and status information.

 

 

 

 

 

 

 

Alarm Thresholds Status Screen

Displays the user-defined alarm settings. See Setup>Alarms to set these alarm

 

 

thresholds.

 

 

 

 

 

 

 

 

 

 

 

 

Miscellaneous Status Screen

 

 

 

 

 

 

 

 

 

 

Self Tst

Displays summary result of self test.

 

 

 

 

 

 

 

 

Lst xfr

Displays a summary of the reason for the last system transfer.

 

 

 

 

 

 

 

 

Status

Displays the current operating mode (i.e., on line, on batt, bypass, etc.).

 

 

 

 

 

 

 

 

IM/RIM

Displays the status of Intelligence and Redundant Intelligence modules.

 

 

 

 

 

 

 

 

 

 

 

 

 

990-7169-001

Appendix A - The PowerView Interface - Page 5

 

Image 47
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Life Support Policy Limited WarrantyTable of Contents Page Safety Symbols Safety InformationRadio Frequency Interference Operation SymbolsFrame Model Description Illustration WelcomeModels System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SYMSTRF3I SymmetraTM Components Description Specific To ModelBasic Operation Glossary of SymmetraTM Terms 8 Introduction Front Clearance Site RequirementsOperating Space Requirements Rear ClearanceModels Structural RequirementsHeat Output Short-Term Battery Module Storage RequirementsEnvironmental Requirements VAC Electrical Requirements Input/OutputEPO Specifications Electrical Requirements EPO SwitchElectrical Wiring Overview Inspect Packaging SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Receiving the SymmetraTMMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Model SYMSTRF3I Electrical InstallationElectrical Requirements EPO Switch Wiring RequiredElectrical Wiring Overview Input/Output Wiring Minimum Input/Output Wiring ProcedureWire Size Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Wiring Symbol Description Minimum Wire Gauge Bypass Balance Transformer Wiring Procedure OptionalWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Securing The Frame Setting The Leveling Feet Startup ProcedurePower Module Installation Battery Module Installation System Startup Procedure System Settings Setup Configuration and Advanced OperationConfiguration Display SettingsAdvanced Operation PowerView Interface PowerView Component Description PowerView ComponentsLanguage Chip Replacement Procedure Language ConfigurationTop-Level Menu Screen Startup ScreenStatus ControlSetup PowerView CommandsLogging AccessoriesFunction Options DisplayHelp DiagnosticsWall Mounting the PowerView PowerView Meaning Corrective Action Message Start-Up TroubleshootingPowerView Meaning Corrective Action Message General Threshold PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassGeneral PowerView Meaning Corrective Action Message6 Troubleshooting Appendix B Module Failure Alarm Indicators Module ReplacementReturning Modules to APC Technical Support & Obtaining Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementReplacement Module Verification Power Module ReplacementReplacement RIM Verification Main Intelligence Module ReplacementReplacement MIM Verification Redundant Intelligence Module Replacement6 Module Replacement Appendix C Operation SpecificationsInput Specifications Compliance Specifications Output SpecificationsPhysical Specifications Page Tel0800 180