| PowerView | Meaning | Corrective Action |
| Message | ||
|
|
| |
|
|
|
|
General | Fault, Internal Temp exceeded | The temperature of one or more | Replace the overheated modules. Refer |
Fault | normal limits | battery modules is too hot. | to Appendix C for module replacement |
|
| procedures. | |
|
|
| |
|
|
|
|
| Input circuit breaker tripped | The input circuit breaker on the | Option #1: If this occurs in conjunction |
| open | SymmetraTM has tripped. | with an overload condition, decrease the |
|
| Input voltage is disconnected to the | load and reset the breaker. |
|
| SymmetraTM. | Option #1: If no overload condition |
|
|
| exists, reset breaker. If it trips again, call |
|
|
| your contract service provider, or APC |
|
|
| Technical Support. (See inside front |
|
|
| cover.) |
|
|
|
|
| System level fan failed | A cooling fan in the SymmetraTM | Call your contract service provider, or |
|
| frame has failed. | APC Technical Support. (See inside front |
|
|
| cover.) |
|
|
|
|
| The Redundant Intelligence | The main intelligence module has | Replace the intelligence module. Refer to |
| Module is in control | failed, and the RIM is functioning as | Appendix C for module replacement |
|
| the primary intelligence module. | procedures. |
|
|
|
|
| IIC | The communications between the | Call your contract service provider, or |
| communications failed. | MIM and at least one other module | APC Technical Support. (See inside front |
|
| has failed. | cover.) |
|
|
|
|
Appendix B - Troubleshooting - Page 5 | |
|