Page 14

E658130

5.2.Communication parameters for CCL003Z

Title

Function

Description

c100

Communication error detection

0.0 - 100.0 sec.

delay time

 

 

c101

 

0: Stop and controlled by cmod, fmod

 

 

1: Operation continue

 

Inverter operation at the

2: Deceleration stop

 

communication loss action

3: Coast stop

 

 

4: Network error stop (err8 trip)

 

 

5: Preset speed operation (by c102 setting)

c102

Preset speed

0: None

 

operation selection

1 to 15: Preset speed

c103

Communication time-out

0: Disconnection detection

 

1: When communication mode enable (Both cmod and

 

condition selection

fmod are set CANopen or communication option) only

 

 

2: 1 + Driving operation

c120*

CC-Link station number

1 to 64

 

selection

Set the number of stations of inverters (Remote device

 

 

 

 

station).

c121*

CC-Link baud rate selection

0: 156kbps

 

 

1: 625kbps

 

 

2: 2.5Mbps

 

 

3: 5Mbps

 

 

4: 10Mbps

 

 

Set the baud rate for CC-LINK network

c122*

CC-Link extended selection

0: Occupies one station (V1.10)

 

 

1: Occupies one station double (V2.0)

 

 

2: Occupies one station quadruple (V2.0)

 

 

3: Occupies one station octuple (V2.0)

 

 

The function of remote registers can be enhanced.

* Set parameters according to the CC-Link network system.

- 13 -

Image 14
Contents CCL003Z Introduction Handling in general Table of Contents Basic specifications OverviewCC-Link Version CC-Link VerSLD Names and functionsOutline Terminating resistor Installation on inverterConnection cable Connection of CC-Link master unit and inverter DA,DBMaximum connection number of units Page RUN LED indicatorRUN ERR Initial setting FunctionsCommunication parameters for CCL003Z C101CC-Link function setting Station number setting Baud rate settingCC-Link extended setting Monitor Run and frequency operation commandBasic functions Writing and reading the parameterI/O signal list One station is occupied CC-Link Ver.1 c122=0 RAMDouble setting is selected CC-Link Ver.2 c122=1 Quadruple setting is selected CC-Link Ver.2 c122=2Octuple setting is selected CC-Link Ver.2 c122=3 Trip history Detail of input and output signals RYnF Instruction code execution request120 OFF ST = on On ST = OFFRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FCH Instruction Codes00EDH 00FDHEx A900 A900H, C123 C123H Details of an error code Fault record display example Description of reply code Reply codeDescription of monitor code Description of input terminal information Description of output terminal informationProgramming examples SB0 SW0RWr0 END Program example for reading the inverter statusX0F Program example for setting the operation mode PLS Program example for setting the operation commandsProgram example for setting the running frequency SETProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading Program example for trip information reading MOVProgram example for resetting the inverter at inverter error Instructions Unusual diagnosis Option errorDisconnection error of network cable How to check the error using the LEDs CPUTime CCL003ZTime Line ERR RUN Line RUNERR Time RUN Time RUNERR Line RUN Time ERR