Toshiba E6581830 I/O signal list One station is occupied CC-Link Ver.1 c122=0, Ram

Page 18

E658130

5.5.I/O signal list

5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)

This option occupies one station area of the buffer memory of the PLC.

In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register (RWw, RWr both 4 word) in the communication data for one station area.

Remote I/O (Default value = 0)

Inverter (Slave) → PLC (Master)

PLC (Master) → Inverter (Slave)

Device No.

Signal

Device No.

Signal

RXn0

Forward running

RYn0

Forward rotation command

RXn1

Reverse running

RYn1

Reverse rotation command

RXn2

Output terminal 1 (RY-RC)

RYn2

Input terminal 3 (S1)

RXn3

Output terminal 2 (OUT)

RYn3

Input terminal 4 (S2)

RXn4

Output terminal 3 (FL)

RYn4

Input terminal 5 (S3)

RXn5

Failure FL

RYn5

Input terminal 6 (S4)

RXn6

PI control OFF

RYn6

Input terminal 7 (PIOFF)

RXn7

Acceleration/deceleration

RYn7

Input terminal 8 (AD1)

pattern selection (1 or 2)

 

 

 

RXn8

Emergency stop

RYn8

Input terminal 9 (ESTP)

RXn9

Coast stop (ST = OFF)

RYn9

Intercept output to inverter

(Coast stop)

 

 

 

RXnA

Alarm

RYnA

Frequency priority CC-Link

RXnB

Reserved*

RYnB

Command priority CC-Link

RXnC

Monitoring

RYnC

Monitor command

RXnD

Frequency setting completion

RYnD

Frequency setting command

(RAM)

(RAM)

 

 

RXnE

Reserved*

RYnE

Reserved**

RXnF

Instruction code execution

RYnF

Instruction code execution request

completion

 

 

 

RX(n+1)0

 

RY(n+1)0

 

to

Reserved*

to

Reserved**

RX(n+1)9

 

RY(n+1)9

 

 

 

 

Error reset request flag

RX(n+1)A

Error status flag

RY(n+1)A

(A reset request is during switched

 

 

 

ON)

RX(n+1)B

Remote station ready

RY(n+1)B

Reserved**

RX(n+1)C

 

RY(n+1)C

 

to

Reserved*

to

Reserved**

RX(n+1)F

 

RY(n+1)F

 

"n" is depend on the station number.

*The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.

**Set OFF (“0”) to reserved bit.

Remote register (Default value = 0)

RWr

Inverter → PLC

RWw

PLC → Inverter

Address

Signal

Address

Signal

RWr n

Monitor value 1

RWw n

Monitor code (1 and 2)

RWr n+1

Monitor value 2

RWw n+1

Set frequency

(output frequency)

 

 

 

 

 

RWr n+2

Reply code

RWw n+2

Instruction code

RWr n+3

Read data

RWw n+3

Write data

"n" is depend on the station number.

- 17 -

Image 18
Contents CCL003Z Introduction Handling in general Table of Contents Basic specifications OverviewCC-Link Version CC-Link VerNames and functions OutlineSLD Installation on inverter Connection cableTerminating resistor Connection of CC-Link master unit and inverter DA,DBMaximum connection number of units Page LED indicator RUN ERRRUN Initial setting FunctionsCommunication parameters for CCL003Z C101CC-Link function setting Station number setting Baud rate settingCC-Link extended setting Monitor Run and frequency operation commandBasic functions Writing and reading the parameterI/O signal list One station is occupied CC-Link Ver.1 c122=0 RAMDouble setting is selected CC-Link Ver.2 c122=1 Quadruple setting is selected CC-Link Ver.2 c122=2Octuple setting is selected CC-Link Ver.2 c122=3 Trip history Detail of input and output signals RYnF Instruction code execution request120 OFF ST = on On ST = OFFRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FCH Instruction Codes00EDH 00FDHEx A900 A900H, C123 C123H Details of an error code Fault record display example Description of reply code Reply codeDescription of monitor code Description of input terminal information Description of output terminal informationProgramming examples SB0 SW0RWr0 Program example for reading the inverter status X0FEND Program example for setting the operation mode PLS Program example for setting the operation commandsProgram example for setting the running frequency SETProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading Program example for trip information reading MOVProgram example for resetting the inverter at inverter error Instructions Option error Disconnection error of network cableUnusual diagnosis How to check the error using the LEDs CPUTime CCL003ZTime Line ERR RUN Line RUNERR Time RUN Time RUNERR Line RUN Time ERR