Toshiba E6581830 Unusual diagnosis, Option error, Disconnection error of network cable

Page 48

E658130

7.Unusual diagnosis

7.1. Option error

The error message is displayed when there is hardware error, software error or lose of connection of wire.

▼Display of trip information

e-23 (Optional unit fault 2 : 0037H) : Option error

7.2. Disconnection error of network cable

▼Display of trip information

err8 (Optional unit fault 1: 001BH): Network error stop

*If a network error occurs when c101 is set to "4", it is displayed.

▼Related parameter

TitleFunction

Setting range

Description

c100

Communication error

0.0 to100.0 sec

detection delay time

c101

Inverter operation at the

0 to 5

 

communications loss action

 

c102

Preset speed operation

0 to 15

 

selection

 

 

 

 

c103

Communication time-out

0 to 2

 

condition selection

 

The waiting time from when a network error occurs can be adjusted. If a network error continues past the time set in c100, it is recognized as a communication error and the operation of the inverter follows the setting of c101.

When normal communication returns during the setting time, a communication error is not displayed and operation is continued.

* Time-out time = CC-Link network time out

+c100

(communication error detection delay time) [0.1s] The operation of the drive when the communication fault occurs can be specified.

The operation frequency of the drive when the communication fault occurs can be specified. (Only when c101 is set to 5)

Select the communication time-out condition.

- 47 -

Image 48
Contents CCL003Z Introduction Handling in general Table of Contents Basic specifications OverviewCC-Link Version CC-Link VerNames and functions OutlineSLD Installation on inverter Connection cableTerminating resistor Connection of CC-Link master unit and inverter DA,DBMaximum connection number of units Page LED indicator RUN ERRRUN Initial setting FunctionsCommunication parameters for CCL003Z C101CC-Link function setting Station number setting Baud rate settingCC-Link extended setting Run and frequency operation command Basic functionsMonitor Writing and reading the parameterI/O signal list One station is occupied CC-Link Ver.1 c122=0 RAMDouble setting is selected CC-Link Ver.2 c122=1 Quadruple setting is selected CC-Link Ver.2 c122=2Octuple setting is selected CC-Link Ver.2 c122=3 Trip history Detail of input and output signals RYnF Instruction code execution request120 OFF ST = on On ST = OFFRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description Instruction Codes 00EDH00FCH 00FDHEx A900 A900H, C123 C123H Details of an error code Fault record display example Description of reply code Reply codeDescription of monitor code Description of input terminal information Description of output terminal informationProgramming examples SB0 SW0RWr0 Program example for reading the inverter status X0FEND Program example for setting the operation mode Program example for setting the operation commands Program example for setting the running frequencyPLS SETProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading Program example for trip information reading MOVProgram example for resetting the inverter at inverter error Instructions Option error Disconnection error of network cableUnusual diagnosis How to check the error using the LEDs CPUCCL003Z Time Line ERR RUNTime Line RUNTime RUN ERR Line RUNERR Time RUN Time ERR