Toshiba E6581830 instruction manual Functions, Initial setting

Page 13

E658130

5.Functions

This option is a communication interface unit that allows the PLC program to operate, monitor and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate with a maximum speed of 10Mbps not only transmitting bit data but also by word data.

Moreover, more data transmissions are possible by the use of CC-Link V2.0.

5.1. Initial setting

Set the following parameters of the inverter.

Title

Function

Description

Factory

CC-Link

setting

setting

 

 

 

 

 

 

 

0: Terminal board

 

 

cmod

Command mode

1: Panel keypad (including remote keypad)

1

4

2: RS485 communication

 

selection

 

 

 

3: CANopen communication

 

 

 

 

 

 

 

 

 

 

4: Communcation option

 

 

 

 

 

0: Setting dial 1 (save even if power is off)

 

 

 

 

 

1: Terminal board VIA

 

 

 

 

 

2: Terminal board VIB

 

 

 

 

 

3: Setting dial 2 (press in center to save)

 

 

 

 

 

4: RS485 communication

 

 

 

Frequency

setting

5: UP/DOWN from external logic input

0

7

fmod

6: CANopen communication

mode selection 1

 

7: Communication option

 

 

 

 

 

 

 

 

 

 

8: Terminal board VIC

 

 

 

 

 

9, 10: -

 

 

 

 

 

11: Pulse train input

 

 

 

 

 

12, 13: -

 

 

 

 

 

14: sro

 

 

 

 

 

1: 2 poles

 

 

 

 

 

2: 4 poles

 

 

 

Number of motor

3: 6 poles

 

 

 

4: 8 poles

2

*

f856

pole for

 

 

5: 10 poles

 

communication

 

 

 

 

 

6: 12 poles

 

 

 

 

 

 

 

 

 

 

7: 14 poles

 

 

 

 

 

8: 16 poles

 

 

f899

Communication

0: -

0

-

function reset

 

1: Reset (after execution: 0)

 

 

 

 

*Set parameter according to number of motor pole used.

- 12 -

Image 13
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionOutline Names and functionsSLD Connection cable Installation on inverterTerminating resistor DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page RUN ERR LED indicatorRUN Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Basic functions Run and frequency operation commandMonitor Writing and reading the parameterRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00EDH Instruction Codes00FCH 00FDHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 X0F Program example for reading the inverter statusEND Program example for setting the operation mode Program example for setting the running frequency Program example for setting the operation commandsPLS SETProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Disconnection error of network cable Option errorUnusual diagnosis CPU How to check the error using the LEDsTime Line ERR RUN CCL003ZTime Line RUNERR Line RUN Time RUNERR Time RUN Time ERR