Toshiba E6581830 instruction manual Remote Register Assignment

Page 25

E658130

5.5.7. Remote Register Assignment

Divide the monitor code (RWw n) into half and select the monitor value 1 (RWr n) from the lower 8 bits and the monitor value 2 (RWr n) from the higher 8 bits.

For example: When output voltage is selected for the monitor value 1 and output torque is selected for the monitor value 2. -> The monitor code is 0703H.

*The hexadecimal value attaches and expresses "H" to the end of a number.

1.Remote register (Master -> inverter)

RWw

Address

Signal

Description

 

 

 

 

 

Set the monitor code to be referenced. By switching on the (RYnC) signal

 

 

after setting, the specified monitored data is set to (RWr n).

RWw n

Monitor code

The monitor value 1 (RWr n): RWw n Setting of the lower 8 bits of monitor

(1 and 2)

code.

 

 

 

The monitor value 2 (RWr n+1): RWw n Setting of the upper 8 bits of

 

 

monitor code.

 

 

Set the set frequency. After setting the register, a frequency is written

RWwn+1

Set frequency

after turning on (RynD). When the writing of the frequency is completed,

(RXnD) turns on, depending on the input command.

 

 

 

 

Unit: 0.01Hz

 

 

Set the command code for actions such as operation mode switching,

RWwn+2

Command code 1

parameter read, write, error reference, error clear, etc. The command will

be executed by turning (RynF) on after the register setting is completed.

 

 

 

 

When the command execution is completed, (RXnF) turns on.

 

 

 

 

 

Set data specified by the above-mentioned command code

 

 

(if necessary).

RWwn+3

Write data 1

If no data needs to be written, the value shall be zero.

 

 

(RynF) is turned on after setting the above-mentioned command code

 

 

and this register.

RWwn+4

Monitor code 3

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+4.

 

 

RWwn+5

Monitor code 4

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+5.

 

 

RWwn+6

Monitor code 5

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+6.

 

 

RWwn+7

Monitor code 6

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+7.

 

 

 

 

Set how many fault records in past to be read.

RWwn+8

Trip history No.

Upper 8 bits: H00 (latest fault) to H07 (eight faults in past)

 

 

Lower 8 bits: H00

 

 

 

RWwn+9

 

Reserved

to

Reserved

 

RWwn+F

 

 

- 24 -

Image 25
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionOutline Names and functionsSLD Connection cable Installation on inverterTerminating resistor DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page RUN ERR LED indicatorRUN Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Basic functions Run and frequency operation commandMonitor Writing and reading the parameterRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00EDH Instruction Codes00FCH 00FDHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 X0F Program example for reading the inverter statusEND Program example for setting the operation mode Program example for setting the running frequency Program example for setting the operation commandsPLS SETProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Disconnection error of network cable Option errorUnusual diagnosis CPU How to check the error using the LEDsTime Line ERR RUN CCL003ZTime Line RUNERR Line RUN Time RUNERR Time RUN Time ERR