5.3.CC-Link function setting

5.3.1. Station number setting

Use parameter c120 to set station number of the inverter.

Set this parameter within the range of 1 to 64.

Title

Function

Description

c120

CC-Link station

1 to 64

 

number selection

 

*Use different station numbers for different devices. (If different devices have the same station number, the communication cannot be performed properly.)

Set consecutive numbers for the station numbers. (Do not skip a number in sequence

like "station number 1 - station number 2 - station number 4".)

The station number does not have to match with the physical connection sequence. (There is no problem with having the physical connection sequence like "station number 1 - station number 3 - station number 4 - station number 2".)

One inverter occupies one station. (One remote device station)

"L.ERR" LED flickers if the setting is changed. When power is switched on again, reset by parameter (f899 = 1) or the RES signal is turned on, the setting value is reflected and the LED turns off.

5.3.2.Baud rate setting

Set the transmission speed. (Refer to the manual for the CC-Link master module for details of transmission speed.)

Title

Function

Description

c121

CC-Link baud rate selection

0: 156kbps

 

 

1: 625kbps

 

 

2: 2.5Mbps

 

 

3: 5Mbps

 

 

4: 10Mbps

"L.ERR" LED flickers if the setting is changed. When power is switched on again, reset by parameter (f899 = 1) or the RES signal is turned on, the setting value is reflected and the LED turns off.

- 14 -

Image 15
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionNames and functions OutlineSLD Installation on inverter Connection cableTerminating resistor DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page LED indicator RUN ERRRUN Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Writing and reading the parameter Run and frequency operation commandBasic functions MonitorRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FDH Instruction Codes00EDH 00FCHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 Program example for reading the inverter status X0FEND Program example for setting the operation mode SET Program example for setting the operation commandsProgram example for setting the running frequency PLSProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Option error Disconnection error of network cableUnusual diagnosis CPU How to check the error using the LEDsLine RUN CCL003ZTime Line ERR RUN TimeTime ERR Time RUNERR Line RUN ERR Time RUN