Toshiba E6581830 instruction manual Monitor code RWwn is set

Page 27

E658130

2. Remote register (Inverter -> Master)

RWr

Address

Signal

Description

RWr n

Monitor value 1

When (RYnC) is on, the monitored value specified to the lower 8 bits of

the monitor code (RWwn) is set.

 

 

 

 

When "0" is set to the higher 8 bits of the monitor code (RWwn), the

 

Monitor value 2

current output frequency is always set. When other than "0" is set to the

RWrn+1

upper 8 bits of the monitor code (RWwn) and (RYnC) is on, the

(output frequency)

 

monitored value specified to the higher 8 bits of the monitor code

 

 

 

 

(RWwn) is set.

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+2

Response code 1

code of (RWwn+2) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

RWrn+3

Read data 1

For a normal reply, the reply data to the instruction specified by the

instruction code is set.

 

 

RWrn+4

Monitor value 3

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+4) is set.

 

 

RWrn+5

Monitor value 4

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+5) is set.

 

 

RWrn+6

Monitor value 5

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+6) is set.

 

 

RWrn+7

Monitor value 6

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+7) is set.

 

 

 

Trip information

The fault data of the trip history No. specified by (RWw n+8) is stored in

RWrn+8

the lower 8bits.

(Trip code)

 

The trip history No. specified is echo backed to the upper 8bits.

 

 

RWrn+9

Trip information

Output frequency of the trip history No. specified in (RWw n+8) is

(output frequency)

stored.

 

RWrn+A

Trip information

Output current of the trip history No. specified in (RWw n+8) is stored.

(output current)

 

 

 

RWrn+B

Trip information

Output voltage of the trip history No. specified in (RWw n+8) is stored.

(output voltage)

 

 

 

RWrn+C

Trip information

Energization time of the trip history No. specified in (RWw n+8) is

(energization time)

stored.

 

RWrn+D

 

Do not use it.

to

Reserved

 

RWrn+F

 

 

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+10

Reply code 2

code of (RWw n+10) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

RWrn+11

Read data 2

For a normal reply, the reply data to the instruction specified by the

instruction code is set.

 

 

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+12

Reply code 3

code of (RWw n+12) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

- 26 -

Image 27
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionNames and functions OutlineSLD Installation on inverter Connection cableTerminating resistor DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page LED indicator RUN ERRRUN Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Writing and reading the parameter Run and frequency operation commandBasic functions MonitorRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FDH Instruction Codes00EDH 00FCHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 Program example for reading the inverter status X0FEND Program example for setting the operation mode SET Program example for setting the operation commandsProgram example for setting the running frequency PLSProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Option error Disconnection error of network cableUnusual diagnosis CPU How to check the error using the LEDsLine RUN CCL003ZTime Line ERR RUN TimeTime ERR Time RUNERR Line RUN ERR Time RUN