Toshiba E6581830 instruction manual

Page 11

E658130

2.Maximum number of units connected to one master station (CC-Link Ver.2.00) 42 units (when connections are inverter only)

If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied:

{(a + a2 + a4 + a8) + (b + b2 + b4 + b8) × 2 + (c + c2 + c4 + c8) × 3 + (d + d2 + d4 + d8) × 4} 64

{(a × 32 + a2 × 32 + a4 × 64 + a8 × 128) + (b × 64 + b2 × 96 + b4 × 192 + b8 × 384)

+(c × 96 + c2 × 160 + c4 × 320 + c8 × 640) + (d × 128 + d2 × 224 + d4 × 448 + d8 × 896)} 8192

{(a × 4 + a2 × 8 + a4 × 16 + a8 × 32) + (b × 8 + b2 × 16 + b4 × 32 + b8 × 64)

+ (c × 12 + c2 × 24 + c4 × 48 + c8 × 96) + (d × 16 + d2 × 32 + d4 × 64 + d8 × 128)}

2048

a:Number of single setting devices occupying one station

b:Number of single setting devices occupying two stations

c:Number of single setting devices occupying three stations

d:Number of single setting devices occupying four stations a2: Number of double setting devices occupying one station

b2: Number of double setting devices occupying two stations

c2: Number of double setting devices occupying three stations

d2: Number of double setting devices occupying four stations

a4: Number of quadruple setting devices occupying one station

b4: Number of quadruple setting devices occupying two stations

c4: Number of quadruple setting devices occupying three stations

d4: Number of quadruple setting devices occupying four stations

a8: Number of octuple setting devices occupying one station

b8: Number of octuple setting devices occupying two stations

c8: Number of octuple setting devices occupying three stations

d8: Number of octuple setting devices occupying four stations 16 × A + 54 × B + 88 × C 2304

A:Numbers of remote I/O 64

B:Number of remote device stations 42

C:Number of local and intelligent device stations 26

- 10 -

Image 11
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionSLD Names and functionsOutline Terminating resistor Installation on inverterConnection cable DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page RUN LED indicatorRUN ERR Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Writing and reading the parameter Run and frequency operation commandBasic functions MonitorRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FDH Instruction Codes00EDH 00FCHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 END Program example for reading the inverter statusX0F Program example for setting the operation mode SET Program example for setting the operation commandsProgram example for setting the running frequency PLSProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Unusual diagnosis Option errorDisconnection error of network cable CPU How to check the error using the LEDsLine RUN CCL003ZTime Line ERR RUN TimeTime ERR Time RUNERR Line RUN ERR Time RUN