Toshiba E6581830 instruction manual Instructions

Page 47

E658130

6.10. Instructions

1.Programming instructions

1.1 Since the buffer memory data of the master station is kept transferred (refreshed) to/from the inverters, the TO instruction need not be executed every scan in

response

to data write or read requests.

The execution of the TO instruction every scan does not pose any problem.

1.2If the FROM/TO instruction is executed frequently, data may not be written reliably. When transferring data between the inverter and sequence program via the buffer memory, perform the handshake to confirm that data has been written without error.

2.Operating and handling instructions

2.1Command only from the programmable controller can be accepted during operation from CC-Link communication.

The run command from external and parameter unit is ignored.

2.2If the station number of two or more inverters is the same, wrong data will be transferred and normal communication cannot be made.

2.3If a network error (controller fault , an open CC-LINK dedicated cable, etc) continues past the time set in c100 during CC-Link operation, it is recognized as a communication error and the operation of the inverter follows the setting of c101.

2.4When the programable controller (master) is reset or the power supply of the programable controller (master) is turned off during CC-Link operation, data communication stops and an inverter follows the setting of c101.

- 46 -

Image 47
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionSLD Names and functionsOutline Terminating resistor Installation on inverterConnection cable DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page RUN LED indicatorRUN ERR Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Writing and reading the parameter Run and frequency operation commandBasic functions MonitorRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FDH Instruction Codes00EDH 00FCHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 END Program example for reading the inverter statusX0F Program example for setting the operation mode SET Program example for setting the operation commandsProgram example for setting the running frequency PLSProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Unusual diagnosis Option errorDisconnection error of network cable CPU How to check the error using the LEDsLine RUN CCL003ZTime Line ERR RUN TimeTime ERR Time RUNERR Line RUN ERR Time RUN