5.5.2. Double setting is selected (CC-Link Ver.2) (c122=1)

This option occupies one station area of the buffer memory of the PLC.

In the case of c122 = 1, there are remote I/O (RX, RY both 32 bits(same as CC-LINK Ver.1)) and the remote register (RWw, RWr both 8 word) in the communication data for one station area.

* Default value of RY and RX is 0.

Remote register (Default value = 0)

RWr

Inverter → PLC

RWw

PLC → Inverter

Address

Signal

Address

Signal

RWr n

Monitor value 1

RWw n

Monitor code (1 and 2)

RWr n+1

Monitor value 2

RWw n+1

Set frequency

(output frequency)

 

 

 

 

 

RWr n+2

Reply code

RWw n+2

Instruction code

RWr n+3

Read data

RWw n+3

Write data

RWr n+4

Monitor value 3

RWw n+4

Monitor code 3

RWr n+5

Monitor value 4

RWw n+5

Monitor code 4

RWr n+6

Monitor value 5

RWw n+6

Monitor code 5

RWr n+7

Monitor value 6

RWw n+7

Monitor code 6

"n" is depend on the station number.

5.5.3. Quadruple setting is selected (CC-Link Ver.2) (c122=2)

This option occupies one station area of the buffer memory of the PLC.

In the case of c122 = 2, there are remote I/O (RX, RY both 32 bits(same as CC-LINK Ver.1)) and the remote register (RWw, RWr both 16 word) in the communication data for one station area.

* Default value of RY and RX is 0.

Remote register (Default value = 0)

RWr

Inverter → PLC

RWw

PLC → Inverter

Address

 

Signal

Address

 

Signal

RWr n

Monitor value 1

RWw n

Monitor code (1 and 2)

RWr n+1

Monitor value 2

RWw n+1

Set frequency

 

(output frequency)

 

 

 

 

 

 

 

 

 

RWr n+2

Reply code

 

RWw n+2

Instruction code

RWr n+3

Read data

 

RWw n+3

Write data

 

RWr n+4

Monitor value 3

RWw n+4

Monitor code 3

 

RWr n+

Monitor value 4

RWw n+5

Monitor code 4

 

RWr n+

Monitor value 5

RWw n+6

Monitor code 5

 

RWr n+

Monitor value 6

RWw n+7

Monitor code 6

 

 

Upper 8

Trip history No.

 

Upper 8

 

Trip history No.

 

Bits

 

Bits

 

RWr n+8

 

RWw n+8

 

 

Lower 8

Trip code

Lower 8

 

Reserved**

 

 

 

 

Bits

 

Bits

 

 

 

 

 

 

RWr n+9

Trip information (output frequency)

RWw n+9

Reserved**

 

RWr n+A

Trip information (output current)

RWw n+A

Reserved**

 

RWr n+B

Trip information (output voltage)

RWw n+B

Reserved**

 

RWr n+C

Trip information (energization time)

RWw n+C

Reserved**

 

RWr n+D

Reserved*

 

RWw n+D

Reserved**

 

RWr n+E

Reserved*

 

RWw n+E

Reserved**

 

RWr n+F

Reserved*

 

RWw n+F

Reserved**

 

"n" is depend on the station number.

*The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.

**Do not use it.

-18 -

Image 19
Contents CCL003Z Introduction Handling in general Table of Contents Overview Basic specificationsCC-Link Ver CC-Link VersionOutline Names and functionsSLD Connection cable Installation on inverterTerminating resistor DA,DB Connection of CC-Link master unit and inverterMaximum connection number of units Page RUN ERR LED indicatorRUN Functions Initial settingC101 Communication parameters for CCL003ZBaud rate setting CC-Link function setting Station number settingCC-Link extended setting Writing and reading the parameter Run and frequency operation commandBasic functions MonitorRAM I/O signal list One station is occupied CC-Link Ver.1 c122=0Quadruple setting is selected CC-Link Ver.2 c122=2 Double setting is selected CC-Link Ver.2 c122=1Octuple setting is selected CC-Link Ver.2 c122=3 Trip history RYnF Instruction code execution request Detail of input and output signals120 On ST = OFF OFF ST = onRemote Register Assignment Instruction code 3 It is the same as instruction code 1 Monitor code RWwn is set Signal Description 00FDH Instruction Codes00EDH 00FCHEx A900 A900H, C123 C123H Details of an error code Fault record display example Reply code Description of reply codeDescription of monitor code Description of output terminal information Description of input terminal informationProgramming examples SW0 SB0RWr0 X0F Program example for reading the inverter statusEND Program example for setting the operation mode SET Program example for setting the operation commandsProgram example for setting the running frequency PLSProgram example for monitoring the output frequency Program example for parameter writing Program example for parameter reading MOV Program example for trip information readingProgram example for resetting the inverter at inverter error Instructions Disconnection error of network cable Option errorUnusual diagnosis CPU How to check the error using the LEDsLine RUN CCL003ZTime Line ERR RUN TimeTime ERR Time RUNERR Line RUN ERR Time RUN