Sterling 6017 series installation manual Shutting Down the Unit, Returning Fluid to the Tank

Page 32

4-2 Shutting Down the Unit

UNIT SHUT DOWN (WITH AUTOVENT SOLENOID OR MANUAL VENT VALVE)

Cool the unit down by switching the Mode switch to the "Manual Cool" position. This will disable the heaters ( i.e. prevent the controller from turning them on) and open the cool solenoid. Fluid temperature can be monitored on the controller display during cool down. When fluid temperature is below 120ºF, depress the PUMP STOP button to turn the unit off.

4-3 Returning Fluid to the Tank

RETURNING FLUID TO TANK

If the unit is to be moved from one process to another (i.e. mold changes, etc.), the following steps must be taken to drain the mold and process lines. Note that this is just the opposite of unit start up/air purge:

1.Cool fluid to 150°F (66°C) maximum.

2.Depress the PUMP STOP push button.

3.Close the Return Valve.

4.Open the Blow Off Valve. (with autovent, the valve will open on its own)

5.Depress and hold the PUMP REVERSE push-button. The pump will then run in reverse, drawing fluid from the mold and lines, and into the reservoir tank.

6.Watch the sight glass to prevent overflow of the reservoir tank.

!CAUTION

The reservoir tank may not have adequate volume

to contain the total system capacity of fluid.

An overflowing reservoir allows hot fluid to escape

and become a potential fire and slip hazard.

The total capacity of the tank can be found on page 14.

If it appears that the tank may overfill, connect a line from the FILL port of the reservoir tank to a clean auxiliary container.

Page 32

6017 Series Hot Oil Large Temperature Control Units

Image 32
Contents Series Large Hot Oil Temperature Control Units $30.00Series Hot Oil Large Temperature Control Units Safety Considerations Table of Contents Startup Preparations Charts and Figures Introduction Necessary DocumentsStandard Features Models CoveredImmersion Heaters Feature DescriptionsAvailable Options Ful-Flo Valve Heater TankPump Optional CoolingConnection Lines Electrical System Controls Electrical Panel and System Components Air PurgeReservoir Tank Pressure SwitchSafety Thermostat Series Hot Oil Large Temperature Control Units 50 kW 100 kW 150 kW 200 kW 90 gpm 150 gpm 200 gpm Lbs Unpacking and Inspection Event of Shipping DamagesReturns If the Shipment is Not CompleteIf the Shipment is Not Correct Work Rules Installation RequirementsInstallation Location Considerations Connecting Piping Piping Considerations for Mobile Installations Customer is responsible for conversions to metric standardsConnecting Vent Piping Connecting Process PipingConnecting Cooling Water Piping Series Hot Oil Large Temperature Control Units Typical Flow Schematic Custom Process Piping Making Electrical Connections Series Hot Oil Large Temperature Control Units Series Hot Oil Large Temperature Control Units Startup Preparations Starting the UnitUnit START-UP with Autovent Solenoid Series Hot Oil Large Temperature Control Units Shutting Down the Unit Returning Fluid to the TankSeries Hot Oil Large Temperature Control Units Using Controls and Indicators Microprocessor ControllerStatus Indicators Display IndicatorsIdentifying M2B Controller Panel Components Screen DisplaysAlarm Indicators Using M2B Controller Keys Motor Fail IndicatorSET Point Key UP Arrow KeyIndex Key Alarm HI Alarm Key Alarm LO Alarm Key Enter KeyDigital Flow Screen Identifying Control Panel SwitchesDisplay Key Mode Select Pump StartPump Stop Vent Cycle Start optionalIdentifying System Status Board Indicators Alarm SilenceStatus Indicator Lights Mode Indicator LightsFault Indicator Lights Auto Mode Indicator LightPump Overload Indicator Light Low Pressure Indicator LightHigh Level Indicator Light Low Level Indicator LightSeries Hot Oil Large Temperature Control Units Making Monthly Checks Periodic ChecksMaking Daily Checks Making Six-Month Checks Routine ServicingMaking Quarterly Checks Servicing the Unit Monthly or Every 500 Hours Servicing the Unit Every Three MonthsMotor Lubrication Procedure Corrective Maintenance Pumps and SealsSeries Hot Oil Large Temperature Control Units Troubleshooting Check the heater output with an Service Notes Service Notes Service Notes Technical Assistance Parts Department