Emerson 3081FG Model 3081 Transmitter 4-20 mA and Signal Connections, Terminal Block Conduit

Page 28

Instruction Manual

IB-106-3081 Rev. 1.5 September 2002

Model 3081FG

pairs are recommended. Ground the trans- mitter housing to an earth ground to prevent unwanted electromagnetic interference (EMI) or radio frequency interference (RFI).

NOTE

For optimum EMI/RFI immunity, shield the 4-20 mA current loop cable and enclose in an earth grounded metal conduit.

NOTE

Never run signal or sensor wiring in the same conduit, or open tray, with power cables. Keep signal or sensor wiring at least 12 in. (0.3 m) away from other electrical equipment and 6.5 ft (2 m) from heavy electrical equipment.

It is necessary to prevent moisture from entering the Model 3081 Transmitter hous- ing. The use of weather-tight cable glands is required. If conduit is used, plug and seal connections on the transmitter housing to prevent moisture accumulation in the termi- nal side of the housing.

Moisture accumulation in the transmit- ter housing can affect its performance and may void its warranty.

b.Oxygen Probe Signal Connections

1.Two signals represent the O2 value and the cell temperature. The probe pro- vides these values to the Model 3081 Transmitter for processing and signal conditioning.

2.Wiring connections for the probe are shown in Figure 2-9.

c.Model 3081 Transmitter 4-20 mA and Signal Connections

1.A 4-20 mA signal represents the O2 value. Superimposed on the 4-20 mA

signal is HART information that is ac- cessible through a Model 275 Hand- held Communicator or AMS software.

2.Two signals representing the O2 value and the cell temperature are supplied to the Model 3081 Transmitter from the oxygen probe.

3.Wiring connections for the Model 3081 Transmitter are shown in Figure 2-10.

NOTE

The ground arrangement shown in Figure 2-10limits the amount of noise introduced into the electronics.

4.Connect wire shields to terminal 1. Connect earth ground as shown.

TERMINAL

BLOCK

 

 

 

 

 

 

 

CONDUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+(GY)

-(RD)

 

 

 

 

THERMOCOUPLE

THERMOCOUPLE

 

 

 

 

CELL-(WH)

CELL+(BK)

 

 

 

 

 

 

26020004

Figure 2-9. Oxygen Probe Terminal Block

2-10 Installation

Rosemount Analytical Inc. A Division of Emerson Process Management

Image 28
Contents Model 3081FG Essential Instructions Highlights of Changes Page Table of Contents Model 3081FGList of Illustrations Proper Calibration Check Gas Flow RateList of Tables Model 3081 Transmitter Terminal BlockModel 3081FG Preface DefinitionsModel 3081FG Section Description and Specifications Component Checklist of Typical System Package ContentsProduct Matrix Code Mounting Adapter Stack SideSystem Configuration System OverviewScope System DescriptionSystem Features Handling the Analyzer System Considerations Typical System Installation TransmitterSpecifications ProbeLift OFF Maximum Power Supply Voltage OhmsVDC Operating Load RegionSection Installation PRE-INSTALLATIONMechanical Installation InspectFront View Side View Bottom ViewMetal Wall Masonry Wall Stack or Duct Horizontal Probe Installation Adjusting Probe Insertion Depth Model 3081FG Installing Model 3081 Transmitter Cover Lock Circuit Terminal ENDBlock TB Mounting HolesDisplay Positioning Assembly Electrical InstallationTerminal Block Conduit Model 3081 Transmitter 4-20 mA and Signal ConnectionsThermocouple CELL-WH CELL+BK Pneumatic Installation Reference Air PackageInstrument Air Reference Air Calibration Check GasOutlet Connection OutletInlet Connection Flow SET MAX Point Knob Mounting HolesSection Startup and Operation Power UPGeneral Reestablishing Proper Calibration Check GAS Flow Rate Proper Calibration Check Gas Flow RateOperation OverviewDisplay Menu TreeDiagnostics CalcheckMenu ProgramInfrared Remote Control IRC NavigationO2 Concentration Analyzer Access Code Or Security Analyzer Access CodeProgram Menu O2 ConcentrationO2 Concentration Indicator Fault Value O2 Concentration Upper Cell Temperature Fault ValueUpper Range VAL Cell T HIReset MAX Cell T To Reset Maximum Cell TemperatureO2 Concentration Analyzer Access Code SET O2 Filter TimeSET LO Bottle O2 SET HI Bottle O2Concentration Model 3081 Transmitter Parameters Parameter Range DefaultModel 3081 Transmitter Parameters SET Code Show Fault Diagnostics MenuC mV 23. Cell Impedance 24. Previous Slope Previous ConstantSW Build Date SW Build NumberCalcheck Menu 27. in MANUAL? Accept LOW O229. Accept LOW O2 Slope Model 3081FG Hart Communicator Signal Line Section HART/AMSOverview ConnectionsAnalog Output Device Loop Connectors Method 2, For Load Resistance 250 OhmsTWO-WIRE in Situ Oxygen Analyzer Hart Communicator PCOFF-LINE and ON-LINE Operations Menu Tree for Hart CommunicatorDevice Setup From Sheet Basic Setup Detailed From Sheet Signal Condition Detailed Setup Output Hart Communicator Start CAL- Check Method Model 3081FG Section Maintenance and Service Model 3081 Electronics ReplacementDisplay Board Replacement PC Board Stack ReplacementTwo-Wire In Situ Oxygen Analyzer Exploded View Oxygen Probe Replacement Oxygen Probe Terminal Block Probe Life Section TroubleshootingIMPEDANCE, Ω Ofresponse Fault IndicationsSpeed Identifying and Correcting Fault Indications ThermocoupleFault 1, Open Thermocouple Fault 3, Shorted Thermocouple Fault 5, O2 Cell Open Fault 5, O2 Cell Open Fault 6, Cell Impedance Too HighFault 7, Reversed O2 Cell 11. Fault 7, Reversed O2 CellModel 3081FG Section Return of Material Model 3081FG Replacement Parts Replacement Parts ListSection Index No Part Number DescriptionModel 3081FG Section Index Model 3081FG Model 3081FG Page Section Drawings and Schematics Model 3081FG Warranty Two-Wire In Situ Oxygen Analyzer Serial no Order no