Advanced Settings

Generator Breaker Rating

To change the generator warmup delay from the Advanced Settings

 

screen:

The generator breaker rating can be set between 5 to 50 amps. By default, the setting is set to 30 amps.

Generator Warmup Delay

The Freedom Sequence power manager applies a generator warmup delay timer (GEN Warmup Delay) to allow any Xanbus-controlled generator a chance to warmup after starting. This delay is similar to warming up a car engine before driving.

The generator warmup delay timer, which can be modified by changing the GEN Warmup Delay setting, is set by default to zero second. The generator warmup delay timer value can be set between 1 to 240 seconds.

NOTE: It is recommended to set the GEN Warmup Delay value to match either the transfer switch delay timer or the generator’s warmup delay timer specified by the manufacturer of the device. Consult the device’s user guide under its specifications or contact the manufacturer for information on the timer rating. Choose a delay that is highest between these two devices.

FSPM 00: Status

L2 Amps

0.0A

Batt Voltage

12.8V

Circuit Status

 

 

 

 

Config

 

1 Press all three buttons to enable Advanced Settings.

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[0sec]

Connect Seq Delay

[10sec]

AC Disc Priority

[2]

5 Press to change

4 Scroll down

the setting.

 

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[2sec]

Connect Seq Delay

[10sec]

AC Disc Priority

[2]

FSPM 00: Status

Batt Voltage

12.8V

Circuit Status

Config

Advanced Settings

3 Press button. 2 Scroll down to select Advanced Settings.

FSPM 00: Advanced Settings

GEN BKR

Rating

[30.0A]

GEN Warmup Delay

[*0sec]

Connect

Seq Delay

[10sec]

AC Disc

Priority

[2]

7 Press to 6 Scroll up or down confirm the to choose a value. selected

value.

 

 

975-0593-01-01

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 33
Contents Freedom Sequence Page Contact Information Purpose Conventions Used About This GuideRelated Information Reference Important Safety InstructionsExplosion Hazard Precautions When Placing the Power ManagerFCC Information to the User Risk of Damage to the Power ManagerContents Page Introduction Standard FeaturesMaterial List Product/Accessory Product Number Compatible Products and Accessories1Xanbus System Typical Xanbus System DiagramPorts and Terminals Mechanical FeaturesTypical RV Wiring Diagram With Freedom Sequence Typical RV WiringEnterFunc Power Manager ConfigurationPower Manager Configuration Circuit Status Circuit StatusCont Circuit Status Basic Configuration Settings List of configurable settings includesConfig List of circuit configurable settings includes Circuit ConfigPriority Mode To change the Mode from the Device Status screenMode OperatingSHR BKR Mode Shore Breaker ModeAuto ManualShore Breaker Rating Breaker Ratings30.0A 25.0ARestore Defaults To Restore Defaults from the Device Status screenRestore Defaults Circuit Configuration Config CircuitCircuit Priority Config Circuit Config To change the priority setting from the Device Status screenLoad Shed EnabledTo change the Load Shed from the Device Status screen Load ShedImproper Configuration DUE to Lack of Experience Advanced SettingsList of advanced settings include Advanced SettingsBKR Derating Breaker Derating Config Advanced SettingsGEN Warmup Delay Generator Warmup DelayGenerator Breaker Rating ScreenConnect Sequence Delay Connect Seq Delay10sec AC Disc Priority AC Disqualification PriorityDC Voltage Setting Nom DC Voltage12.0V Circuit Level Advanced Settings Circuit2Circuit Name DC Relay Settings AC Relay SettingsCircuit3 Circuit NameAC Line Circuit TypeGenerator Soft Start PriorityReconnect Margin Battery Voltage TriggersAuto-Detection of AC Input Source Shore/Gen Freedom Sequence Operational ConceptsAuto-Detection of AC Input Source Type 1-Ph/2-Ph Loading of Shore/Generator Breaker RatingsAC Load Shedding LINE1 L1 LINE2 L2 DC Load Shedding Using DC Relay to control AC load circuitsPriority Swapping Between Circuits Override the AC Circuit Load Shedding Generator Run Detection B+ Signal Battery Voltage MeasurementFreedom Sequence Interaction with Other Xanbus Devices Freedom SW Interactive Charger De-rating ICDFreedom Sequence SCP Menu Map Specifications Warranty Warranty and Return InformationWarranty and Return Information Product DisclaimerReturn Material Authorization Policy Out of Warranty ServiceReturn Procedure Information About Your System Page Xantrex Technology USA Inc