Xantrex Technology 809-0912 manual LINE1 L1 LINE2 L2

Page 45

FSequence IPM Owners Guide.book Page 35 Thursday, October 6, 2011 3:33 PM

Freedom Sequence Operational Concepts

PRESENT CONFIGURATION

STATUS AT OVERLOAD

STATUS AFTER LOAD SHEDDING EVENT

Desired Mode

[Operating]

SHR BKR Mode

[Manual]

SHR BKR Rating

[30.0A]

GEN BKR Rating

[20.0A]

AC-Front

[1]

AC-Central

[3]

Space Heat

[6]

Washer

[2]

Dryer

[4]

Elec Range

[5]

Circuit7

[]

Circuit8

[]

Circuit9

[]

Circuit10

[]

Sequence Delay

[10sec]

AC Disc Priority

[2]

2

1

LINE1 (L1)

LINE2 (L2)

AC Src Type

2-Ph

AC Source

Shore1

AMPS L1

35.0A

AMPS L2

15.0A

Batt Level

12.0V

AC-Front

On 10.0A

AC-Central

On 15.0A

Space Heat

On 10.0A

Washer

On 6.0A

Dryer

On 4.0A

Elec Range

On 5.0A

Circuit7

On 0.0A

Circuit8

On 0.0A

Circuit9

On 0.0A

Circuit10

On 0.0A

Config FSPM

 

Advanced Settings

 

 

 

3

AC Src Type

2-Ph

AC Source

Shore1

AMPS L1

25.0A

AMPS L2

15.0A

Batt Level

12.0V

AC-Front

On 10.0A

AC-Central

On 15.0A

Space Heat

Off 0.0A

Washer

On 6.0A

Dryer

On 4.0A

Elec Range

On 5.0A

Circuit7

On 0.0A

Circuit8

On 0.0A

Circuit9

On 0.0A

Circuit10

On 0.0A

Config FSPM

 

Advanced Settings

 

 

 

5

4

Look at the highlighted AC circuits. Notice the priority settings for each circuit (1).

Also, observe that the SHR BKR Rating is set to 30 amps (2).

Line1 is experiencing an overload condition at 35 amps (3) exceeding the SHR BKR Rating of 30 amps by 5 amps. At this point, Freedom Sequence will apply its load shedding logic to all circuits in Line1 and shed the load that has the lowest priority setting. In this case, that load is Space Heat with a priority setting of 6.

After the load shedding event, Freedom Sequence will report Space Heat as Off 0.0A (4).

Line1 is no longer in overload condition at 25 amps (5) not exceeding the SHR BKR Rating of 30 amps.

Figure 12 AC Load Shedding Illustration

 

 

975-0593-01-01

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 45
Contents Freedom Sequence Page Contact Information Purpose Conventions Used About This GuideRelated Information Reference Important Safety InstructionsExplosion Hazard Precautions When Placing the Power ManagerFCC Information to the User Risk of Damage to the Power ManagerContents Page Introduction Standard FeaturesMaterial List Product/Accessory Product Number Compatible Products and Accessories1Xanbus System Typical Xanbus System DiagramPorts and Terminals Mechanical FeaturesTypical RV Wiring Diagram With Freedom Sequence Typical RV WiringEnterFunc Power Manager ConfigurationPower Manager Configuration Circuit Status Circuit StatusCont Circuit Status Basic Configuration Settings List of configurable settings includesConfig List of circuit configurable settings includes Circuit ConfigPriority Mode To change the Mode from the Device Status screenMode OperatingSHR BKR Mode Shore Breaker ModeAuto ManualShore Breaker Rating Breaker Ratings30.0A 25.0ARestore Defaults To Restore Defaults from the Device Status screenRestore Defaults Circuit Configuration Config CircuitCircuit Priority Config Circuit Config To change the priority setting from the Device Status screenLoad Shed EnabledTo change the Load Shed from the Device Status screen Load ShedImproper Configuration DUE to Lack of Experience Advanced SettingsList of advanced settings include Advanced SettingsBKR Derating Breaker Derating Config Advanced SettingsGEN Warmup Delay Generator Warmup DelayGenerator Breaker Rating ScreenConnect Sequence Delay Connect Seq Delay10sec AC Disc Priority AC Disqualification PriorityDC Voltage Setting Nom DC Voltage12.0V Circuit Level Advanced Settings Circuit2Circuit Name DC Relay Settings AC Relay SettingsCircuit3 Circuit NameAC Line Circuit TypeGenerator Soft Start PriorityReconnect Margin Battery Voltage TriggersAuto-Detection of AC Input Source Shore/Gen Freedom Sequence Operational ConceptsAuto-Detection of AC Input Source Type 1-Ph/2-Ph Loading of Shore/Generator Breaker RatingsAC Load Shedding LINE1 L1 LINE2 L2 DC Load Shedding Using DC Relay to control AC load circuitsPriority Swapping Between Circuits Override the AC Circuit Load Shedding Generator Run Detection B+ Signal Battery Voltage MeasurementFreedom Sequence Interaction with Other Xanbus Devices Freedom SW Interactive Charger De-rating ICDFreedom Sequence SCP Menu Map Specifications Warranty Warranty and Return InformationWarranty and Return Information Product DisclaimerReturn Material Authorization Policy Out of Warranty ServiceReturn Procedure Information About Your System Page Xantrex Technology USA Inc