Xantrex Technology 809-0912 manual AC Disqualification Priority, AC Disc Priority

Page 35

FSequence IPM Owners Guide.book Page 25 Thursday, October 6, 2011 3:33 PM

Advanced Settings

AC Disqualification Priority

The Freedom Sequence power manager is capable of detecting a compatible inverter/charger, such as the Freedom SW 2012 or the Freedom SW 3012, that is connected on the Xanbus network. Upon detection, it initiates inverter/charger interactive functions. The purpose of the AC Disq Priority is to tell the inverter/charger when a critical load circuit is disconnected due to an overload condition. Another purpose is to request the inverter/charger to stop drawing any current for charging or to stop powering the connected loads through the inverter/charger’s bypass circuit if its battery is at high battery level.

The AC Disq Priority is any number between 1 to 10. This priority number implies that, if an AC load with a circuit Priority number that is the same or less than the AC Disq Priority number is ever disconnected by Freedom Sequence due to an overload condition, then an “AC disqualify request” is sent to the inverter/charger and that request is sustained until the same AC load circuit gets reconnected somehow. The inverter/charger can either accept this request and disqualify its incoming AC or reject the request and keep drawing AC current.

For more information, see “Freedom Sequence Interaction with Other Xanbus Devices” on page 39.

By default, the factory setting is set to 2.

NOTE: This setting can only be modified when Mode is set to Standby.

To change the AC disqualification priority from the Advanced Settings screen:

FSPM 00: StatusFSPM 00: Status

L2 Amps

0.0A

Batt Voltage

 

12.8V

Batt Voltage

12.8V

Circuit Status

 

Circuit Status

 

Config

 

 

Config

 

Advanced Settings

 

1 Press all three buttons to

3 Press button.

2 Scroll down to select

enable Advanced Settings.

 

 

Advanced Settings.

FSPM 00: Advanced Settings

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[2sec]

GEN Warmup Delay

[2sec]

Connect Seq Delay

[5sec]

Connect Seq Delay

[5sec]

AC Disc Priority

[2]

AC Disc Priority

[*2]

5 Press to change

4 Scroll down

7 Press to

6 Scroll up or down

the setting.

 

confirm the

to choose a value.

FSPM 00: Advanced Settings

selected

 

 

value.

 

 

GEN BKR Rating

[30.0A]

 

 

 

GEN Warmup Delay

[2sec]

 

 

 

Connect Seq Delay

[5sec]

 

 

 

AC Disc Priority

[1]

 

 

 

 

 

975-0593-01-01

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 35
Contents Freedom Sequence Page Contact Information Purpose Conventions Used About This GuideRelated Information Reference Important Safety InstructionsExplosion Hazard Precautions When Placing the Power ManagerFCC Information to the User Risk of Damage to the Power ManagerContents Page Introduction Standard FeaturesMaterial List Product/Accessory Product Number Compatible Products and Accessories1Xanbus System Typical Xanbus System DiagramPorts and Terminals Mechanical FeaturesTypical RV Wiring Diagram With Freedom Sequence Typical RV WiringEnterFunc Power Manager ConfigurationPower Manager Configuration Cont Circuit StatusCircuit Status Circuit Status Config Basic Configuration SettingsList of configurable settings includes Priority List of circuit configurable settings includesCircuit Config Operating To change the Mode from the Device Status screenMode ModeManual Shore Breaker ModeSHR BKR Mode Auto25.0A Breaker RatingsShore Breaker Rating 30.0ARestore Defaults Restore DefaultsTo Restore Defaults from the Device Status screen Circuit Priority Circuit ConfigurationConfig Circuit Config Circuit Config To change the priority setting from the Device Status screenLoad Shed EnabledLoad Shed To change the Load Shed from the Device Status screenImproper Configuration DUE to Lack of Experience Advanced SettingsBKR Derating List of advanced settings includeAdvanced Settings Breaker Derating Config Advanced SettingsScreen Generator Warmup DelayGEN Warmup Delay Generator Breaker Rating10sec Connect Sequence DelayConnect Seq Delay AC Disc Priority AC Disqualification Priority12.0V DC Voltage SettingNom DC Voltage Circuit Name Circuit Level Advanced SettingsCircuit2 DC Relay Settings AC Relay SettingsCircuit3 Circuit NameAC Line Circuit TypeGenerator Soft Start PriorityReconnect Margin Battery Voltage TriggersLoading of Shore/Generator Breaker Ratings Freedom Sequence Operational ConceptsAuto-Detection of AC Input Source Shore/Gen Auto-Detection of AC Input Source Type 1-Ph/2-PhAC Load Shedding LINE1 L1 LINE2 L2 DC Load Shedding Using DC Relay to control AC load circuitsPriority Swapping Between Circuits Override the AC Circuit Load Shedding Freedom SW Interactive Charger De-rating ICD Battery Voltage MeasurementGenerator Run Detection B+ Signal Freedom Sequence Interaction with Other Xanbus DevicesFreedom Sequence SCP Menu Map Specifications Warranty Warranty and Return InformationWarranty and Return Information Product DisclaimerReturn Procedure Return Material Authorization PolicyOut of Warranty Service Information About Your System Page Xantrex Technology USA Inc