Carrier TJF005-007, TJF004, TJE Electrical Data, Supply Size, Type FLA, Rla Lra, Fla Mca Mocp† Lra

Page 11

Table 2 — Electrical Data

UNIT

NOMINAL

IFM

VOLTAGE

COMPRESSOR

 

OFM

 

IFM

COMBUSTION

POWER

DISCONNECT

RANGE

 

(ea)

 

(ea)

 

FAN MOTOR

SUPPLY

SIZE*

48TF

V-Ph-Hz

TYPE

 

 

 

FLA

Min

Max

RLA

 

LRA

Qty

Hp

FLA

FLA

MCA

MOCP†

FLA

LRA

 

208/230-1-60

Std

187

254

16.2

 

96.0

1

1/4

1.4

3.5

.6

24.5/24.5

30/30

23/23

106/106

 

Alt

 

4.9

26.6/26.6

35/35

26/26

111/111

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

17.7/17.7

25/25

17/17

85/85

 

208/230-3-60

Alt

187

254

10.2

 

75.0

1

1/4

1.4

4.9

.6

19.1/19.1

25/25

19/19

90/90

 

 

High

 

 

 

 

 

 

 

 

5.2

 

19.4/19.4

25/25

19/19

109/109

004

 

Std

 

 

 

 

 

 

 

 

1.3

 

7.6

15

7

48/48

 

460-3-60

Alt

414

508

4.4

 

40.0

1

1/4

0.8

2.1

.3

8.4

15

8

48/48

 

 

High

 

 

 

 

 

 

 

 

2.6

 

8.9

15

9

57/57

 

 

Std

 

 

 

 

 

 

 

 

1.3

 

6.3

15

7

35

 

575-3-60

Alt

518

632

3.7

 

31.0

1

1/4

0.8

2.1

.3

6.9

15

8

37

 

 

High

 

 

 

 

 

 

 

 

2.6

 

7.3

15

7

45

 

208/230-1-60

Std

187

254

23.3

 

118.0

1

1/4

1.4

3.5

.6

34.0/34.0

40/40

32/32

129/129

 

Alt

 

4.9

35.4/35.4

45/45

34/34

133/133

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

24.2/24.2

30/30

23/23

101/101

 

208/230-3-60

Alt

187

254

15.4

 

90.0

1

1/4

1.4

4.9

.6

25.6/25.6

30/30

25/25

105/105

 

 

High

 

 

 

 

 

 

 

 

5.2

 

25.9/25.9

30/30

25/25

124/124

005

 

Std

 

 

 

 

 

 

 

 

1.8

 

13.0

20

13

51

 

460-3-60

Alt

414

508

8.3

 

45.0

1

1/4

0.8

2.1

.3

13.3

20

13

53

 

 

High

 

 

 

 

 

 

 

 

2.6

 

13.8

20

13

62

 

 

Std

 

 

 

 

 

 

 

 

1.8

 

10.1

15

10

41

 

575-3-60

Alt

518

632

6.4

 

36.0

1

1/4

0.8

2.1

.3

10.3

15

11

42

 

 

High

 

 

 

 

 

 

 

 

2.6

 

10.7

15

10

50

 

208/230-1-60

Std

187

254

28.8

 

147.0

1

1/4

1.4

5.9

.6

43.3/43.3

60/60

42/42

161/161

 

Alt

 

6.6

44.0/44.0

60/60

42/42

184/184

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

5.9

 

27.3/27.3

35/35

29/29

128/128

 

208/230-3-60

Alt

187

254

16.3

 

114.0

1

1/4

1.4

5.2

.6

26.6/26.6

35/35

26/26

148/148

 

 

High

 

 

 

 

 

 

 

 

7.5

 

28.9/28.9

35/35

29/29

174/174

006

 

Std

 

 

 

 

 

 

 

 

3.1

 

13.2

20

13

72

 

460-3-60

Alt

414

508

7.4

 

64.0

1

1/4

0.8

2.6

.3

12.7

15

12

81

 

 

High

 

 

 

 

 

 

 

 

3.4

 

13.5

20

13

94

 

 

Std

 

 

 

 

 

 

 

 

3.1

 

10.9

15

11

58

 

575-3-60

Alt

518

632

6.2

 

62.0

1

1/4

0.8

3.0

.3

10.5

15

10

66

 

 

High

 

 

 

 

 

 

 

 

3.4

 

12.6

15

11

76

 

208/230-3-60

Std

187

254

23.6

 

146.0

1

1/4

1.4

5.2

.6

30.2/30.2

35/35

29/29

180/180

 

High

 

7.5

32.5/32.5

40/40

32/32

205/205

 

 

 

 

 

 

 

 

 

 

 

007

460-3-60

Std

414

508

10.6

 

73.0

1

1/4

0.6

2.6

.3

15.4

20

15

90

High

 

3.4

16.1

20

16

103

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

8.5

 

58.4

1

1/4

0.6

2.6

.3

12.3

15

13

72

 

High

 

3.4

12.9

20

14

82

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination

load equipment (refer to NEC Articles 430 and 440), the overcurrent

protective device for the unit shall be fuse or HACR breaker. Canadian

units may be fuse or circuit breaker.

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

=1371

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

2. Unbalanced 3-Phase Supply Voltage

% Voltage Imbalance = 100 x

7

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percent

of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the max- imum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

Image 11
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Motor Data Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg 48TJ004-007 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Gas Propane Orifice Size† 000 Altitude CompensationElevation Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flashes LED Error Code DescriptionFlash† Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist