Carrier 48TJE, TJF004, TJF005-007, 48TJD Changeover Set Points, Default Potentiometer Settings

Page 19

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

Fig. 37 — Supply-Air Sensor Placement

CO2 Control Set Up — If a CO2 sensor is not being used, proceed to the next section. If a CO2 sensor is being used, per- form the following:

1.Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm.

2.Locate the CO2 SP (PPM) potentiometer and adjust to the desired set point. See Fig. 38.

Mechanical Cooling Lockout — Determine the outdoor-air temperature at which you want the mechanical cooling (com- pressors) to be disabled. Locate the mechanical cooling lock- out (MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to the OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the outdoor air tem- perature is below this value. See Fig. 38.

Dry Bulb Changeover Set Up — Determine the dry bulb changeover set point from Table 3. The settings are A, B, C and D. Locate the ECON SP potentiometer and set the dry bulb changeover set point. See Fig. 38. When the OAT is above this set point, the damper is limited to minimum position setting.

Table 3 — Changeover Set Points

SETTINGS

A

B

C

D

Dry Bulb (°F)

73

69

66

63

Single Enthalpy* (Btu/lb)

27

25

24

22

Differential Temperature*

2

2

2

2

(°F, Not Adjustable)

 

 

 

 

Differential Enthalpy*

1

1

1

1

(Btu/lb, Not Adjustable)

 

 

 

 

*Field-installed accessory.

 

 

 

 

If a potentiometer fails, its setting will default to the values in Table 4.

Table 4 — Default Potentiometer Settings

POTENTIOMETER

DEFAULT SETTING

CO2 SP (PPM)

1,000

MECH CLG LOCKOUT

47°

ECON SP

D

MIN POS (%)

20

Ventilation Air (Minimum Position Set up) — If ventilation air is not required, proceed to Step 5. If ventilation air is required, perform the following:

1.The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board.

2.Locate the minimum position (MIN POS) potentiometer. Turn the potentiometer full CCW to fully close the out- door air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 38.

3.Replace the filter access panel. See Fig. 26. Ensure the fil- ter access panel slides along the tracks and is securely engaged.

4.Calculate the minimum airflow across the EconoMi$er.

a.Calculate % of outside air using the following formula.

%Outdoor air through EconoMi$er

%Outdoor air = Mixture Temp – Return Air Temp Outdoor Temp – Return Air Temp

b.Divide total CFM by percentage outdoor air, this gives outdoor air volume in CFM.

5.Turn on base unit power.

NOTE: The EconoMi$er begins operation three min- utes after power up.

Personal Injury Hazard. Avoid possible injury by keep- ing fingers away from damper blades.

6. See Fig. 39 for barometric relief damper characteristics.

Fig. 38 — EconoMi$er Control Adjustment

Potentiometers (Factory Settings)

WG)

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(IN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

400

600

800

1000

1200

1400

1600

 

0

 

 

 

 

 

FLOW (CUBIC FEET/MINUTE)

 

 

 

 

 

Fig. 39 — Barometric Relief Capacity

 

 

19

Image 19
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Accessory/FIOP Static Pressure* in. wg 48TJ004-007 Fan Rpm at Motor Pulley SettingsMotor Data 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Elevation Altitude CompensationGas Propane Orifice Size† 000 Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flash† LED Error Code DescriptionFlashes Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist