Carrier TJF005-007 48TJ005 4 Tons Alternate Motor Belt Drive, 817, 1700 750 473 806 536, 1600

Page 31

Table 22 — Fan Performance 48TJ005 — Horizontal Discharge Units, Standard Motor

48TJ005 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

(Cfm)

 

 

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

1200

0.75

0.41

458

0.81

 

0.45

 

506

0.87

0.51

572

0.92

 

0.56

 

632

1300

0.68

0.42

471

0.74

 

0.46

 

521

0.79

0.52

589

0.85

 

0.58

 

651

1400

0.60

0.45

503

0.66

 

0.49

 

556

0.71

0.54

616

0.77

 

0.60

 

681

1500

0.51

0.47

536

0.58

 

0.52

 

593

0.64

0.56

631

0.70

 

0.62

 

698

1600

0.42

0.49

557

0.49

 

0.54

 

616

0.56

0.58

654

0.63

 

0.64

 

723

1700

0.32

0.52

584

0.39

 

0.57

 

646

0.48

0.60

678

0.55

 

0.66

 

750

1800

0.21

0.54

610

0.29

 

0.60

 

674

0.41

0.62

698

0.48

 

0.68

 

772

1900

0.09

0.56

629

0.18

 

0.62

 

696

0.33

0.64

720

0.41

 

0.70

 

796

2000

0.06

 

0.65

 

731

0.26

0.66

744

0.33

 

0.73

 

823

LEGEND

Bhp — Brake Horsepower Input to Fan

Esp — External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for Additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

Table 23 — Fan Performance 48TJ005 — Horizontal Discharge Units, Alternate Motor

48TJ005 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.1

 

 

0.2

 

 

0.3

 

 

0.4

 

 

 

0.6

 

 

0.7

 

 

0.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

569

0.18

189

641

0.23

242

701

0.29

299

761

0.34

357

859

 

0.46

483

901

0.52

546

943

0.58

609

1300

604

0.22

231

673

0.28

294

731

0.34

352

788

0.39

410

887

 

0.52

546

928

0.59

615

968

0.65

683

1400

640

0.27

284

705

0.33

347

761

0.39

410

817

0.45

473

914

 

0.59

620

955

0.66

688

996

0.72

757

1500

676

0.32

336

738

0.38

399

793

0.45

468

847

0.51

536

940

 

0.65

683

982

0.73

767

1024

0.81

851

1600

713

0.38

399

772

0.44

462

825

0.51

536

877

0.58

609

967

 

0.73

767

1009

0.81

851

1051

0.89

935

1700

750

0.45

473

806

0.51

536

857

0.59

615

908

0.66

693

997

 

0.81

851

1037

0.90

940

1077

1.01

1030

1800

788

0.52

546

841

0.59

620

890

0.67

704

939

0.75

788

1026

 

0.91

956

 

 

 

1104

1.07

1124

 

1065

1.01

1040

1900

826

0.60

630

876

0.68

714

924

0.76

799

971

0.84

883

1056

 

1.01

1061

1094

1.10

1151

1132

1.18

1240

2000

864

0.70

735

912

0.77

809

958

0.86

898

1004

0.94

988

1087

 

1.12

1177

1125

1.21

1271

1162

1.30

1366

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48TJ005 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.9

 

 

1.0

 

 

1.1

 

 

1.2

 

 

 

1.4

 

 

1.6

 

 

1.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

987

0.64

652

1030

0.70

695

1068

0.79

792

1106

0.87

889

1134

 

0.98

998

1189

1.12

1138

1245

1.21

1358

1300

1006

0.71

709

1044

0.77

736

1086

0.84

833

1128

0.91

930

1183

 

1.10

1052

1226

1.23

1215

1297

1.35

1406

1400

1033

0.79

797

1069

0.86

838

1104

0.93

925

 

 

 

1218

 

1.14

1090

1286

1.34

1282

1320

1.48

1463

1139

1.01

1012

 

1500

1060

0.88

891

1095

0.95

930

1129

1.02

1022

1162

1.09

1114

1228

 

1.24

1186

1303

1.40

1339

1343

1.60

1530

1600

1087

1.01

1001

1123

1.05

1073

1156

1.13

1150

1185

1.20

1226

1250

 

1.35

1291

1319

1.51

1444

1382

1.68

1607

1700

1114

1.07

1108

1151

1.15

1185

1183

1.23

1262

1215

1.31

1339

1276

 

1.48

1415

1334

1.64

1569

1398

1.80

1722

1800

1141

1.17

1221

1178

1.26

1318

1211

1.35

1390

1243

1.43

1461

1303

 

1.61

1540

1359

1.78

1702

1418

1.95

1865

1900

1168

1.28

1371

1204

1.37

1502

1238

1.47

1548

1271

1.56

1594

1330

 

1.74

1664

1386

1.93

1846

1439

2.11

2018

2000

1197

1.39

1485

1231

1.48

1604

1265

1.59

1666

1298

1.69

1727

1358

 

1.89

1808

1413

2.08

1989

1466

2.27

2171

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 835 to 1185 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2. indicates field-supplied motor and drive are required.

3.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 1.00 and the maximum continuous watts are 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for addi- tional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

6.Interpolation is permissible. Do not extrapolate.

31

Image 31
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Accessory/FIOP Static Pressure* in. wg 48TJ004-007 Fan Rpm at Motor Pulley SettingsMotor Data 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Elevation Altitude CompensationGas Propane Orifice Size† 000 Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flash† LED Error Code DescriptionFlashes Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist