Carrier TJF004, TJF005-007, 48TJD, 48TJE specifications 48TJ006 5 Tons Standard Motor Direct Drive

Page 25

Table 14 — Fan Performance 48TJ006 — Vertical Discharge Units, Standard Motor

48TJ006 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

Low Speed

 

 

 

 

Medium Speed

 

 

 

 

High Speed

 

 

 

208 V

 

230,460,575 V

 

208 V

 

230,460,575 V

 

208 V

 

230,460,575 V

(Cfm)

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1500

0.69

0.67

750

1.01

0.71

791

1.00

0.70

782

1.20

0.76

845

1.22

0.79

875

1.28

0.85

949

1600

0.49

0.70

780

0.85

0.74

824

0.85

0.74

821

1.06

0.79

883

1.09

0.82

913

1.17

0.89

988

1700

0.29

0.73

810

0.70

0.77

857

0.70

0.77

861

0.93

0.83

921

0.97

0.85

950

1.06

0.92

1027

1800

0.09

0.75

839

0.54

0.80

891

0.55

0.81

900

0.80

0.86

959

0.84

0.89

988

0.95

0.96

1066

1900

0.39

0.83

924

0.40

0.84

940

0.67

0.90

997

0.72

0.92

1025

0.84

0.99

1105

2000

0.23

0.86

957

0.25

0.88

979

0.54

0.93

1035

0.59

0.95

1063

0.73

1.03

1144

2100

0.08

0.89

990

0.10

0.91

1018

0.41

0.96

1073

0.46

0.99

1101

0.62

1.06

1183

2200

0.28

1.00

1111

0.34

1.02

1138

0.51

1.10

1222

2300

0.15

1.03

1149

0.21

1.06

1176

0.40

1.13

1261

2400

0.02

1.07

1187

0.09

1.09

1213

0.29

1.17

1300

2500

0.18

1.20

1340

LEGEND

Bhp — Brake Horsepower Input to Fan

Esp — External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for Additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

Table 15 — Fan Performance 48TJ006 — Vertical Discharge Units, Alternate Motor

48TJ006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.1

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

729

0.36

368

788

0.42

429

896

 

0.56

572

981

0.69

705

1070

0.85

869

1144

1.01

1032

1600

770

0.42

429

826

0.49

501

930

 

0.64

654

1015

0.78

797

1098

0.94

961

1173

1.11

1134

1700

811

0.50

511

864

0.57

582

964

 

0.72

736

1051

0.88

899

1124

1.03

1053

1203

1.21

1237

1800

852

0.58

593

903

0.66

674

999

 

0.82

838

1085

0.98

1001

1155

1.13

1155

1231

1.32

1349

1900

893

0.68

695

942

0.76

777

1035

 

0.92

940

1119

1.10

1124

1191

1.26

1288

1288

1.43

1461

2000

935

0.78

797

982

0.87

889

1070

 

1.04

1063

1153

1.22

1247

1227

1.40

1431

1287

1.57

1604

2100

977

0.89

910

1022

0.99

1012

1107

 

1.17

1196

1187

1.35

1380

1260

1.54

1574

1323

1.72

1758

2200

1019

1.02

1042

1063

1.12

1145

1144

 

1.30

1328

1222

1.49

1523

1294

1.70

1737

1359

1.89

1931

2300

1061

1.16

1185

1104

1.26

1288

1182

 

1.47

1502

1258

1.65

1686

1328

1.80

1901

1393

2.07

2115

2400

1103

1.30

1328

1145

1.41

1441

1220

 

1.61

1645

1293

1.80

1860

1362

2.03

2074

1426

2.26

2310

2500

1145

1.46

1492

1186

1.57

1604

1259

 

1.78

1819

1329

2.00

2044

1397

2.22

2269

1460

2.45

2504

48TJ006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

External Static Pressure (in. wg)

Airflow

 

 

1.2

 

 

1.4

 

 

1.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

 

1226

1.19

1216

1301

1.46

1492

1380

1.69

1757

1600

 

1242

1.28

1308

1318

1.49

1523

1392

1.78

1800

1700

 

1270

1.39

1420

1335

1.58

1615

1408

1.80

1850

1800

 

1300

1.52

1553

1361

1.71

1747

1423

1.91

1952

1900

 

1329

1.64

1676

1391

1.80

1891

1448

2.05

2095

2000

 

1355

1.77

1809

1420

1.99

2034

1477

2.21

2258

2100

 

1381

1.91

1952

1449

2.14

2167

2200

 

1413

2.08

2126

1474

2.30

2350

2300

 

1449

2.26

2310

2400

 

1485

2.47

2524

2500

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 900 to 1300 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2. indicates field-supplied motor and drive are required.

3.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 1.30 for single-phase units and 2.40 for 3-phase units and the maximum continuous watts are 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

6.Interpolation is permissible. Do not extrapolate.

25

Image 25
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections Supply Size Electrical DataType FLA RLA LRAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Accessory/FIOP Static Pressure* in. wg 48TJ004-007 Fan Rpm at Motor Pulley SettingsMotor Data 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 149 109189 2291064 10281005 938817 48TJ005 4 Tons Alternate Motor Belt Drive1700 750 473 806 536 1900 826 63048TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1700 811 494 865 567 1600 770 420 826 4831800 852 578 1900 894 5671600 826 483 931 641 1020 788 1101 956 1178 12211252 1700 865 567 966 725 1051 883 1133 1061 1205928 700 982 779 885 623 942 700971 787 1022 867 1015 891 1063 9982000 1022 867 1121 1014 1188 1097 1254 1216 1900 982 779 1084 932 1160 1006 1223 11142100 1063 998 1140 1064 1196 1272 1292 2200 1104 1081 1159 1106 1229 1258Elevation Altitude CompensationGas Propane Orifice Size† 000 Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flash† LED Error Code DescriptionFlashes Burner Tray Details Heating Service Analysis LED Error Code Service AnalysisSymptom Cause Remedy Problem Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist