Carrier TJF004, TJF005-007, 48TJD, 48TJE specifications LOSS-OF-CHARGE LOW Pressure

Page 7

Table 1 — Physical data (cont)

UNIT SIZE 48TJ

 

E/F004

D/E/F005

D/E/F006

D/E/F007

FURNACE SECTION

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

Temp (F)††

 

195

195

195

195

Burner Orifice Diameter

 

 

 

 

 

(in. ...drill size)

 

 

 

 

 

Natural Gas

Std

.113...33

.113...33/.113...33/.129...30

.113...33/.113...33/.129...30

.113...33/.113...33/.129...30

Liquid Propane

Alt

.089...43

.089...43/.089...43/.102...38

.089...43/.089...43/.102...38

.089...43/.089...43/.102...38

Thermostat Heat Anticipator

 

 

 

 

 

Setting (amps)

 

 

 

 

 

208/230 v and 575 Stage 1

 

.14

.14

.14

.14

Stage 2

 

.14

.14

.14

.14

460 v Stage 1

 

.14

.14

.14

.14

Stage 2

 

.14

.14

.14

.14

Gas Input (Btuh) Stage 1

 

74,000/82,000

74,000/115,000/120,000

74,000/115,000/120,000

74,000/115,000/120,000

Stage 2

 

—/115,000

—/—/150,000

—/—/150,000

—/—/150,000

Efficiency (Steady State) (%)

 

80

80

80

80

Temperature Rise Range

 

25-55/55-85

25-55/35-65/50-80

25-55/35-65/50-80

25-55/35-65/50-80

Manifold Pressure (in. wg)

 

 

 

 

 

Natural Gas

Std

3.5

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

3.5

Gas Valve Quantity

 

1

1

1

1

Gas Valve Pressure Range

 

 

 

 

 

Psig

 

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

 

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Field Gas Connection

 

 

 

 

 

Size (in.)

 

1/2

1/2

1/2

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

Standard Compressor

 

 

450 ± 50

 

500 ± 50

Internal Relief (Differential)

 

 

 

 

 

Cutout

 

 

428

 

428

Reset (Auto.)

 

 

320

 

320

LOSS-OF-CHARGE (LOW PRESSURE)

 

 

 

 

 

SWITCH (psig)

 

 

 

 

 

Cutout

 

 

 

7 ± 3

 

Reset (Auto.)

 

 

 

22 ± 7

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

Opens

 

 

 

30 ± 5

 

Closes

 

 

 

45 ± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

Quantity...Size (in.)

 

 

 

1...20 x 24 x 1

 

RETURN-AIR FILTERS

 

 

 

Throwaway

 

Quantity...Size (in.)

 

 

 

2...16 x 25 x 2

 

 

 

LEGEND

Al

Aluminum

Bhp

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local representative for details about coated fins.

†Weight of 14-in. roof curb.

**Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.

NOTES:

1.The 48TJ004-007 units have a loss-of-charge (low-pressure) switch located in the liquid line.

2.High-static motor not available on single-phase units.

7

Image 7
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Accessory/FIOP Static Pressure* in. wg 48TJ004-007 Fan Rpm at Motor Pulley SettingsMotor Data 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Elevation Altitude CompensationGas Propane Orifice Size† 000 Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flash† LED Error Code DescriptionFlashes Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist