Carrier TJF004, TJF005-007, 48TJD, 48TJE Durablade Economizer Troubleshooting, Damper does not

Page 47

Table 35 — Durablade Economizer Troubleshooting

 

PROBLEM

 

 

CAUSE

 

REMEDY

Damper does not

 

Indoor (evaporator) fan is off.

1.

Check to ensure that 24 vac is present at terminal C1 on the IFC or

open.

 

 

 

 

 

that 24 vac is present at the IFO terminal. Check whether 24 vac is

 

 

 

 

 

 

 

 

present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is

 

 

 

 

 

 

 

 

not present, check wiring (see unit label diagram).

 

 

 

 

 

 

 

2.

Check proper thermostat connection to G on the connection board.

 

 

 

 

No power to economizer motor.

1.

Check that SW3 is properly making contact with the damper

 

 

 

 

 

 

 

 

blade. Check that SW1 is in the NC (normally closed) position.

 

 

 

 

 

 

 

2. Check diode D18. If diode is not functioning properly, replace control

 

 

 

 

 

 

 

 

board.

 

 

 

 

 

 

 

3.

Confirm that the economizer control board is grounded properly at

 

 

 

 

 

 

 

 

PL6-4 (brown wire) and at brown terminal of the economizer control

 

 

 

 

 

 

 

 

board (brown wire). The economizer motor must also be grounded

 

 

 

 

 

 

 

 

properly at the negative motor terminal (brown wire).

 

 

 

 

 

 

 

4.

Verify SW1 and SW3 are working and wired properly (see unit label

 

 

 

 

 

 

 

 

diagram).

 

 

 

 

 

 

 

5.

Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black

 

 

 

 

 

 

 

 

wire). If 24 vac not present, check unit wiring (see unit label

 

 

 

 

 

 

 

 

diagram). If 24 vac is found in both places, check for 24 vac at the

 

 

 

 

 

 

 

 

yellow terminal of the economizer control board (yellow wire). If

 

 

 

 

 

 

 

 

24 vac power is not present, replace the economizer control board.

 

 

 

 

Economizer motor failure.

 

If the indoor (evaporator) fan and economizer motor are energized,

 

 

 

 

 

 

 

verify that there is a minimum of 18 vdc at the positive motor

 

 

 

 

 

 

 

terminal. If the motor is not operating, replace the motor.

Economizer

 

OAT or EC set too high.

 

1.

Set at correct temperature (3 F below indoor space temperature).

operation

 

 

 

 

2.

Check OAT or EC by setting above outdoor temperature or humidity

limited to minimum

 

 

 

 

 

level. If the OAT or EC switches do not close, replace OAT or EC.

position.

 

 

Verify economizer control board is correctly

1.

Perform the following tests when OAT or EC is closed, Y1 is called

 

 

 

 

wired and works properly.

 

 

for and damper is at minimum position. Confirm 24 vac on gray

 

 

 

 

 

 

 

 

terminal of the economizer control board (gray wire). If 24 vac is

 

 

 

 

 

 

 

 

not present, check wiring (see unit label diagram).

 

 

 

 

 

 

 

2.

Verify that SW1 and SW3 are wired correctly and working properly

 

 

 

 

 

 

 

 

(see unit label diagram).

 

 

 

 

 

 

 

3.

Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is

 

 

 

 

 

 

 

 

not present, check wiring (see unit wiring label diagram).

 

 

 

 

 

 

 

4.

Check 24 vac output at PL6-10 (white wire). If 24 vac is not

 

 

 

 

 

 

 

 

present, replace economizer control board.

 

 

 

 

Check SAT.

 

 

1.

After verifying that the OAT and EC settings and the economizer

 

 

 

 

 

 

 

 

control board wiring are correct, check to ensure that the 24 vac

 

 

 

 

 

 

 

 

terminal of the SAT has 24 vac (white wire). If OAT, EC, and control

 

 

 

 

 

 

 

 

board are functioning and wired properly and no 24 vac exists,

 

 

 

 

 

 

 

 

check wiring (see unit label diagram).

 

 

 

 

 

 

 

2.

If supply-air temperature is greater than 57 F, 24 vac should be

 

 

 

 

 

 

 

 

found at terminal T2 on the SAT (pink wire). If 24 vac is not present,

 

 

 

 

 

 

 

 

replace SAT.

Damper does not

 

Incorrect wiring of economizer.

1.

Verify that SW2 and SW4 are wired and working properly (see unit

close.

 

 

 

 

 

label diagram).

 

 

 

 

 

 

 

2. Check diode D19. If diode is not functioning properly, replace control

 

 

 

 

 

 

 

 

board.

 

 

 

 

Verify economizer control board is functioning

1.

After verifying that the wiring is correct, modulate the damper to the

 

 

 

 

properly.

 

 

 

minimum position. Remove the calls for G.

 

 

 

 

 

 

 

2.

If the damper does not move, check for 24 vac at PL6-1 (red wire).

 

 

 

 

 

 

 

 

If 24 vac is not present, check wiring (see unit label diagram).

 

 

 

 

 

 

 

3.

If damper still does not move, check for 24 vac at blue terminal of

 

 

 

 

 

 

 

 

economizer control board (blue wire). If 24 vac is not present, re-

 

 

 

 

 

 

 

 

place the economizer circuit board.

 

 

 

 

Check SAT.

 

 

1.

After verifying that the wiring is correct and the economizer control

 

 

 

 

 

 

 

 

board is functioning properly, place the OAT or EC switch in the

 

 

 

 

 

 

 

 

closed position. Place a call for Y1 and open the damper to the fully

 

 

 

 

 

 

 

 

open position. Confirm that the 24 vac terminal of the SAT has

 

 

 

 

 

 

 

 

24 vac (white wire). If 24 vac is not present, check wiring (see unit

 

 

 

 

 

 

 

 

label diagram).

 

 

 

 

 

 

 

2.

If supply-air temperature is less than 52 F, 24 vac should be found

 

 

 

 

 

 

 

 

at terminal T1 on the SAT (violet wire). If 24 vac not found, replace

 

 

 

 

 

 

 

 

SAT.

 

 

 

 

Economizer motor failure.

 

If economizer control board and SAT are functioning properly, verify

 

 

 

 

 

 

 

that there is a minimum of 18 vdc at the positive motor terminal. If a

 

 

 

 

 

 

 

minimum if 18 vdc is present and the motor is still not operating, re-

 

 

 

 

 

 

 

place the motor.

Economizer damper

 

Verify that close-on-power-loss and economizer

1.

Check voltage potential across batteries. If lower than 14 vdc,

does not close on

 

control board are functioning properly.

 

replace close-on-power-loss power supply (9-v alkaline batteries). It

power loss.

 

 

 

 

 

is recommended that you check this emergency power supply on a

 

 

 

 

 

 

 

 

regular basis or whenever the filters are changed.

 

 

 

 

 

 

 

2.

If the close-on-power-loss and economizer control board are

 

 

 

 

 

 

 

 

functioning properly, check for 14 vdc or higher at the blue terminal

 

 

 

 

 

 

 

 

of the economizer control board (blue wire) when power is discon-

 

 

 

 

 

 

 

 

nected from unit. If 14 vdc is not present, replace the control board.

C1

Common Power

 

OAT

Outdoor-Air Thermostat

EC

Enthalpy Control

PL

Plug

 

 

IFC

Indoor (Evaporator) Fan Contactor

SAT

Supply-Air Thermostat

IFO

Indoor (Evaporator) Fan On

SW

Economizer Position Switch

47

Image 47
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Motor Data Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg 48TJ004-007 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Gas Propane Orifice Size† 000 Altitude CompensationElevation Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flashes LED Error Code DescriptionFlash† Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist