Step 9 — Adjust Evaporator-Fan Speed — Ad- just evaporator-fan rpm to meet jobsite conditions. Table 5 shows fan rpm at motor pulley settings. Table 6 shows motor performance. See Table 7 for Accessory/FIOP Static Pressure. Refer to Tables 8-29 to determine fan speed settings.

DIRECT-DRIVE MOTORS — The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit. If other than factory setting is desired, refer to label dia- gram for motor reconnection. See Fig. 40 for direct drive motor location.

BELT-DRIVE MOTORS — Fan motor pulleys are factory set for speed shown in Table 1. See Fig. 41 for belt drive location.

NOTE: Before adjusting fan speed, make sure the new fan speed will provide an air temperature rise range as shown in Table 1.

To change fan speed:

1.Shut off unit power supply and tag disconnect.

2.Loosen belt by loosening fan motor mounting nuts. See Fig. 41.

3.Loosen movable pulley flange setscrew (see Fig. 42).

4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not ex- ceed maximum speed specified in Table 1.

5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)

To align fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley along fan shaft.

3.Make angular alignment by loosening motor from mounting.

To adjust belt tension:

1.Loosen fan motor mounting nuts.

2.Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection with 8 to 10 lbs of force).

3.Tighten motor mounting nuts.

4.Adjust bolt and tighten nut to secure motor in fixed position.

MOTOR MOUNTING

PLATE NUTS

Fig. 41 — Belt Drive Motor Mounting

DIRECT DRIVE MOTOR

DIMPLED HEAT EXCHANGER

 

Fig. 40 — Direct-Drive Motor Mounting

Fig. 42 — Evaporator-Fan Pulley Adjustment

20

Image 20
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Physical Data Unit Size 48TJLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Conduit Installation Flue Hood DetailsPower Wiring Connections Electrical Data Supply SizeType FLA RLA LRAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Enthalpy Control Installation Horizontal Discharge Block-Off PlateWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Default Potentiometer Settings Changeover Set PointsBelt Drive Motor Mounting Motor Data Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg 48TJ004-007 48TJ004 3 Tons Standard Motor Direct Drive 48TJ004 3 Tons Alternate Motor Belt Drive48TJ004 3 Tons HIGH-STATIC Motor Belt Drive 48TJ005 4 Tons Standard Motor Direct Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive 48TJ006 5 Tons Alternate Motor Belt Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 109 149189 2291028 10641005 93848TJ005 4 Tons Alternate Motor Belt Drive 8171700 750 473 806 536 1900 826 63048TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1600 770 420 826 483 1700 811 494 865 5671800 852 578 1900 894 5671221 1600 826 483 931 641 1020 788 1101 956 11781252 1700 865 567 966 725 1051 883 1133 1061 1205885 623 942 700 928 700 982 779971 787 1022 867 1015 891 1063 9981900 982 779 1084 932 1160 1006 1223 1114 2000 1022 867 1121 1014 1188 1097 1254 12162100 1063 998 1140 1064 1196 1272 1292 2200 1104 1081 1159 1106 1229 1258Gas Propane Orifice Size† 000 Altitude CompensationElevation Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flashes LED Error Code DescriptionFlash† Burner Tray Details LED Error Code Service Analysis Heating Service AnalysisSymptom Cause Remedy Problem Cause RemedyCooling Service Analysis Compressor operates continuouslyDurablade Economizer Troubleshooting Damper does notEconoMi$er Troubleshooting Problem Potential Cause RemedyTypical Wiring Diagram and Component Arrangement Switch Max. Vent Position SW4Page START-UP Checklist