Table 36 — EconoMi$er Troubleshooting
PROBLEM | POTENTIAL CAUSE | REMEDY |
Damper Does Not | Indoor (Evaporator) Fan is Off | Check to ensure that 24 vac is present at Terminal C1 (Common Power) |
Open |
| on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at |
|
| the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is |
|
| present at |
|
| not present, check wiring (see unit label diagram). |
|
| Check proper thermostat connection to G on the connection board. |
| No Power to EconoMi$er Controller | Check to ensure that 24 vac is present across Terminals 24 VAC and |
|
| 24V COM on the EconoMi$er control. If 24 vac is not present, check wiring |
|
| (see unit label diagram). If 24 vac is present, STATUS light should be on |
|
| constantly. |
| No Power to G Terminal | If IFM is on, check to ensure 24 vac is present on G Terminal of the |
|
| EconoMi$er controller. If 24 vac is not present, check wiring (see unit |
|
| label diagram). |
| Controller Fault | If STATUS light is flashing one flash, the EconoMi$er controller is |
|
| experiencing a fault condition. Cycle power to the controller. If condition |
|
| continues, replace the EconoMi$er controller. |
| Thermostat Fault | If STATUS light is flashing two flashes, the EconoMi$er controller senses |
|
| the thermostat is wired incorrectly. Check wiring between the thermostat |
|
| and the connection board in the electrical panel. The fault condition is |
|
| caused by Y2 being energized before Y1. |
| Actuator Fault | Check the wiring between the EconoMi$er controller and the actuator. |
|
| Hold CONFIG button between 3 and 10 seconds to verify the |
|
| actuator’s operation. (This process takes 3 minutes to complete.) |
EconoMi$er | Minimum Position Set Incorrectly | Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) |
Operation Limited to |
| to 100% to verify operation, and then set to correct setting. |
Minimum Position | EconoMi$er Changeover Set Point Set Too | Set at correct value. See Table 3. |
| High or Too Low |
|
| Supply Air Temperature Sensor Faulty | If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is |
|
| faulty. Check wiring or replace sensor. |
| Outdoor Air Temperature Sensor Faulty | If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is |
|
| faulty. Check wiring or replace sensor. |
Damper Position | Supply Air Low Limit Strategy Controlling | The |
Less than Minimum |
| position to decrease. Refer to the |
Position Set Point |
| setting of MIN POS (%). If correct, EconoMi$er is operating correctly. |
Damper Does Not | CO2 Ventilation Strategy Controlling | If a CO2 sensor is being used, and the damper position is greater than |
Return to Minimum |
| minimum position, the ventilation control strategy is controlling. Refer to |
Position |
| the |
Damper Does Not | Damper Travel is Restricted | Check to ensure the damper is not blocked. |
Close on Power Loss |
|
|
LEGEND
PL — Plug
48