CONDENSER INTAKE
COILLOUVERS
TOP COVER
CORNER POST
FLUE HOOD | END PANEL |
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code *Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE | X | |
NOMINAL | ||
DIMENSIONS | ||
DIAMETER | ||
(in.) | (feet) | |
| ||
1/2 | 6 | |
3/4 or 1 | 8 | |
11/4 or larger | 10 |
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Table 2). On
FIELD CONTROL WIRING — Install a
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low- voltage connections (shown in Fig. 12).
Fig. 9 — Conduit Installation
LEGEND
IGC — Integrated Gas Unit Controller
LED —
Fig. 10 — Component Location
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Feed control wires through the raceway located between the condenser coil top cover and burner side panel. See Fig. 10. Connect control wires to corresponding screw terminals, the
HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for second- stage heating, when available.
9