Carrier Air Conditioner Product Data and Specifications for 48TJD and 48TJE Models

Page 9

CONDENSER INTAKE

COILLOUVERS

TOP COVER

CORNER POST

FLUE HOOD

END PANEL

Fig. 7 — Flue Hood Details

LEGEND

NFGC — National Fuel Gas Code *Field supplied.

NOTE: Follow all local codes.

SPACING OF SUPPORTS

STEEL PIPE

X

NOMINAL

DIMENSIONS

DIAMETER

(in.)

(feet)

 

1/2

6

3/4 or 1

8

11/4 or larger

10

Fig. 8 — Gas Piping Guide (With Accessory

Thru-the-Curb Service Connections)

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 2, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or ex- cessive phase imbalance constitutes abuse and may cause dam- age to electrical components. Such operation would invalidate any applicable Carrier warranty.

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in- structions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense aver- age temperature in accordance with thermostat installation instructions. Connect thermostat wires to terminal board.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low- voltage connections (shown in Fig. 12).

Fig. 9 — Conduit Installation

LEGEND

IGC — Integrated Gas Unit Controller

LED — Light-Emitting Diode

Fig. 10 — Component Location

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Feed control wires through the raceway located between the condenser coil top cover and burner side panel. See Fig. 10. Connect control wires to corresponding screw terminals, the low-voltage connections located inside low-voltage access panel. See Fig. 12 for connections. The low-voltage connec- tions provide the UL required clearance between high- and low-voltage wiring.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for second- stage heating, when available.

9

Image 9
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections Supply Size Electrical DataType FLA RLA LRAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure* in. wg 48TJ004-007Motor Data 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 149 109189 2291064 10281005 938817 48TJ005 4 Tons Alternate Motor Belt Drive1700 750 473 806 536 1900 826 63048TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1700 811 494 865 567 1600 770 420 826 4831800 852 578 1900 894 5671600 826 483 931 641 1020 788 1101 956 1178 12211252 1700 865 567 966 725 1051 883 1133 1061 1205928 700 982 779 885 623 942 700971 787 1022 867 1015 891 1063 9982000 1022 867 1121 1014 1188 1097 1254 1216 1900 982 779 1084 932 1160 1006 1223 11142100 1063 998 1140 1064 1196 1272 1292 2200 1104 1081 1159 1106 1229 1258Altitude Compensation ElevationGas Propane Orifice Size† 000 Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 LED Error Code Description Flash†Flashes Burner Tray Details Heating Service Analysis LED Error Code Service AnalysisSymptom Cause Remedy Problem Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist