Table 24 — Fan Performance 48TJ005 — Horizontal Discharge Units, High-Static Motor

48TJ005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

641

0.23

242

761

0.34

357

859

0.46

483

943

0.58

609

1030

0.70

695

1300

673

0.28

294

788

0.39

410

887

0.52

546

968

0.65

683

1044

0.77

736

1400

705

0.33

347

817

0.45

473

914

0.59

620

996

0.72

757

1069

0.86

838

1500

738

0.38

399

847

0.51

536

940

0.65

683

1024

0.81

851

1095

0.95

930

1600

772

0.44

462

877

0.58

609

967

0.73

767

1051

0.89

935

1123

1.05

1073

1700

806

0.51

536

908

0.66

693

997

0.81

851

1077

1.01

1030

1151

1.15

1185

1800

841

0.59

620

939

0.75

789

1026

0.91

956

1104

1.07

1124

1178

1.26

1318

1900

876

0.68

714

971

0.84

883

1056

1.01

1061

1132

1.18

1240

1204

1.37

1502

2000

912

0.77

809

1004

0.94

988

1087

1.12

1177

1162

1.30

1366

1231

1.48

1604

 

 

 

 

 

 

 

 

 

 

48TJ005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

1106

0.87

889

1134

0.98

998

1189

1.12

1138

1245

1.21

1358

1292

1.35

1345

1300

1128

0.91

930

1183

1.10

1052

1226

1.23

1215

1297

1.35

1406

1346

1.51

1500

1400

1139

1.01

1012

1218

1.14

1090

1286

1.34

1282

1320

1.48

1463

1370

1.65

1645

1500

1162

1.09

1114

1228

1.24

1186

1303

1.40

1339

1343

1.60

1530

1393

1.79

1778

1600

1185

1.20

1226

1250

1.35

1291

1319

1.51

1444

1382

1.68

1607

1434

1.88

1867

1700

1215

1.31

1339

1276

1.48

1415

1334

1.64

1569

1389

1.80

1722

1451

2.01

2001

1800

1243

1.43

1461

1303

1.61

1540

1359

1.78

1702

1418

1.95

1865

1471

2.18

2167

1900

1271

1.56

1594

1330

1.74

1664

1386

1.93

1846

1439

2.11

2018

1493

2.36

2345

2000

1298

1.69

1727

1358

1.89

1808

1413

2.08

1989

1468

2.27

2171

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 1075 to 1455 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

3.Maximum continuous bhp is 2.4 and maximum continuous watts are 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confi- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. See Table 6 — Motor Data for additional information.

4.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

5.Interpolation is permissible. Do not extrapolate.

Table 25 — Fan Performance 48TJ006 — Horizontal Discharge Units, Standard Motor

48TJ006 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

Low Speed

 

 

 

 

Medium Speed

 

 

 

 

High Speed

 

 

 

208V

 

230, 460, 575 V

 

208 V

 

230, 460, 575 V

 

208 V

 

230, 460, 575 V

(Cfm)

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1500

0.74

0.67

750

1.06

0.71

791

1.07

0.70

782

1.27

0.76

845

1.26

0.79

875

1.33

0.85

949

1600

0.54

0.70

780

0.90

0.74

824

0.92

0.74

821

1.13

0.79

883

1.14

0.82

913

1.22

0.89

988

1700

0.34

0.73

810

0.75

0.77

857

0.77

0.77

861

1.00

0.83

921

1.01

0.85

950

1.11

0.92

1027

1800

0.14

0.75

839

0.59

0.80

891

0.62

0.81

900

0.87

0.86

959

0.89

0.88

988

1.00

0.96

1066

1900

0.44

0.83

924

0.47

0.84

940

0.74

0.90

997

0.77

0.92

1025

0.89

0.99

1105

2000

0.28

0.86

957

0.32

0.88

979

0.61

0.93

1035

0.64

0.95

1063

0.78

1.03

1144

2100

0.13

0.89

990

0.17

0.91

1018

0.48

0.96

1073

0.51

0.99

1101

0.67

1.06

1183

2200

0.02

0.95

1058

0.35

1.00

1111

0.39

1.02

1138

0.56

1.10

1222

2300

0.22

1.03

1149

0.26

1.06

1176

0.45

1.13

1261

2400

0.09

1.07

1187

0.14

1.09

1213

0.34

1.17

1300

2500

0.23

1.20

1340

LEGEND

Bhp — Brake Horsepower Input to Fan

Esp — External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for Additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

32

Image 32
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Physical Data Unit Size 48TJLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Conduit Installation Flue Hood DetailsPower Wiring Connections Electrical Data Supply SizeType FLA RLA LRAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Enthalpy Control Installation Horizontal Discharge Block-Off PlateWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Default Potentiometer Settings Changeover Set PointsBelt Drive Motor Mounting Motor Data Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg 48TJ004-007 48TJ004 3 Tons Standard Motor Direct Drive 48TJ004 3 Tons Alternate Motor Belt Drive48TJ004 3 Tons HIGH-STATIC Motor Belt Drive 48TJ005 4 Tons Standard Motor Direct Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive 48TJ006 5 Tons Alternate Motor Belt Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 109 149189 2291028 10641005 93848TJ005 4 Tons Alternate Motor Belt Drive 8171700 750 473 806 536 1900 826 63048TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1600 770 420 826 483 1700 811 494 865 5671800 852 578 1900 894 5671221 1600 826 483 931 641 1020 788 1101 956 11781252 1700 865 567 966 725 1051 883 1133 1061 1205885 623 942 700 928 700 982 779971 787 1022 867 1015 891 1063 9981900 982 779 1084 932 1160 1006 1223 1114 2000 1022 867 1121 1014 1188 1097 1254 12162100 1063 998 1140 1064 1196 1272 1292 2200 1104 1081 1159 1106 1229 1258Gas Propane Orifice Size† 000 Altitude CompensationElevation Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flashes LED Error Code DescriptionFlash† Burner Tray Details LED Error Code Service Analysis Heating Service AnalysisSymptom Cause Remedy Problem Cause RemedyCooling Service Analysis Compressor operates continuouslyDurablade Economizer Troubleshooting Damper does notEconoMi$er Troubleshooting Problem Potential Cause RemedyTypical Wiring Diagram and Component Arrangement Switch Max. Vent Position SW4Page START-UP Checklist