Carrier 48TJD, TJF004, TJF005-007, 48TJE 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive

Page 23

Table 10 — Fan Performance 48TJ004 — Vertical Discharge Units, High-Static Motor

48TJ004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

673

0.18

179

805

0.25

249

911

0.34

338

988

0.43

428

1061

0.47

487

1000

709

0.22

219

835

0.30

298

937

0.38

378

1039

0.49

487

1086

0.55

547

1100

746

0.26

259

867

0.35

348

964

0.40

398

1068

0.55

547

1109

0.61

607

1200

785

0.32

318

903

0.41

408

994

0.50

497

1090

0.64

637

1156

0.68

676

1300

826

0.38

378

942

0.48

477

1047

0.60

597

1122

0.70

696

1190

0.76

756

1400

868

0.45

448

984

0.57

567

1067

0.67

666

1160

0.84

766

1237

0.85

845

1500

911

0.53

527

1029

0.66

656

1109

0.77

766

1190

1.00

855

1271

0.95

945

 

 

 

 

 

 

 

 

 

 

48TJ004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

1105

0.57

567

1140

0.63

622

1170

0.68

674

1198

0.73

723

1224

0.77

771

1000

1136

0.63

627

1172

0.69

688

1203

0.75

745

1232

0.80

799

1258

0.86

852

1100

1145

0.67

666

1181

0.73

731

1213

0.80

792

1242

0.85

850

1268

0.91

906

1200

1210

0.74

736

1248

0.81

808

1282

0.88

875

1312

0.94

939

1340

1.01

1000

1300

1266

0.84

836

1306

0.92

917

1341

1.00

993

1373

1.07

1066

1402

1.14

1136

1400

1349

0.93

925

1391

1.02

1015

1492

1.11

1100

1463

1.19

1180

1494

1.26

1257

1500

1383

1.05

1044

1426

1.15

1146

1465

1.25

1242

1500

1.34

1332

1532

1.43

1419

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 1075 to 1455 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

3.Maximum continuous bhp is 2.4 and the maximum continuous watts are 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for addi- tional information.

4.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

5.Interpolation is permissible. Do not extrapolate.

Table 11 — Fan Performance 48TJ005 — Vertical Discharge Units, Standard Motor

48TJ005 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

(Cfm)

 

 

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

1200

0.68

0.41

458

0.74

 

0.45

 

506

0.74

0.51

572

0.85

 

0.56

 

632

1300

0.61

0.42

471

0.67

 

0.46

 

521

0.66

0.52

589

0.78

 

0.58

 

651

1400

0.53

0.45

503

0.59

 

0.49

 

556

0.59

0.54

616

0.70

 

0.60

 

681

1500

0.45

0.47

536

0.51

 

0.52

 

593

0.52

0.56

631

0.63

 

0.62

 

698

1600

0.36

0.49

557

0.42

 

0.54

 

616

0.45

0.58

654

0.56

 

0.64

 

723

1700

0.26

0.52

584

0.32

 

0.57

 

646

0.37

0.60

678

0.48

 

0.66

 

750

1800

0.15

0.54

610

0.22

 

0.60

 

674

0.30

0.62

698

0.41

 

0.68

 

772

1900

0.04

0.56

629

0.11

 

0.62

 

696

0.23

0.64

720

0.34

 

0.70

 

796

2000

 

 

0.16

0.66

744

0.26

 

0.73

 

823

LEGEND

Bhp — Brake Horsepower Input to Fan

Esp — External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

23

Image 23
Contents Installation, Start-Up Service Instructions Horizontal Conversion Panels Viewed from Duct End Roof Curb Dimensions Unit Leveling Tolerances Make Electrical Connections Unit Size 48TJ Physical DataLOSS-OF-CHARGE LOW Pressure Base Unit Dimensions Flue Hood Details Conduit InstallationPower Wiring Connections RLA LRA Electrical DataSupply Size Type FLAMake Outdoor-Air Adjustments and Install Outdoor-Air Hood Typical Access Panel Locations Horizontal Discharge Block-Off Plate Enthalpy Control InstallationWiring Connections for Outdoor-Air Thermostat Outdoor-Air Hood Assembly EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsBelt Drive Motor Mounting Motor Data Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg 48TJ004-007 48TJ004 3 Tons Alternate Motor Belt Drive 48TJ004 3 Tons Standard Motor Direct Drive48TJ005 4 Tons Standard Motor Direct Drive 48TJ004 3 Tons HIGH-STATIC Motor Belt Drive48TJ005 4 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Alternate Motor Belt Drive 48TJ006 5 Tons Standard Motor Direct Drive48TJ006 5 Tons HIGH-STATIC Motor Belt Drive 48TJ007 6 Tons Standard Motor Belt Drive 48TJ007 6 Tons HIGH-STATIC Motor Belt Drive 229 109149 189938 10281064 10051900 826 630 48TJ005 4 Tons Alternate Motor Belt Drive817 1700 750 473 806 53648TJ005 4 Tons HIGH-STATIC Motor Belt Drive 1900 894 567 1600 770 420 826 4831700 811 494 865 567 1800 852 5781700 865 567 966 725 1051 883 1133 1061 1205 12211600 826 483 931 641 1020 788 1101 956 1178 12521015 891 1063 998 885 623 942 700928 700 982 779 971 787 1022 8672200 1104 1081 1159 1106 1229 1258 1900 982 779 1084 932 1160 1006 1223 11142000 1022 867 1121 1014 1188 1097 1254 1216 2100 1063 998 1140 1064 1196 1272 1292Gas Propane Orifice Size† 000 Altitude CompensationElevation Heating Page Service Lubrication Cooling Charging Chart, 48TJ004 Flashes LED Error Code DescriptionFlash† Burner Tray Details Problem Cause Remedy LED Error Code Service AnalysisHeating Service Analysis Symptom Cause RemedyCompressor operates continuously Cooling Service AnalysisDamper does not Durablade Economizer TroubleshootingProblem Potential Cause Remedy EconoMi$er TroubleshootingTypical Wiring Diagram and Component Arrangement SW4 Switch Max. Vent PositionPage START-UP Checklist