Carrier 48SX024-060, 48SS018-060 Maximum Gas Flow Capacity, Supply and Return Duct Openings

Page 17

 

 

 

Table 3 Ð Maximum Gas Flow Capacity*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL

INTERNAL

 

 

 

 

 

LENGTH OF PIPE, FT²

 

 

 

 

 

IRON PIPE,

 

 

 

 

 

 

 

 

 

 

DIAMETER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

(in.)

10

20

30

40

50

60

70

80

 

90

100

125

150

175

200

(in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1¤2

.622

175

120

97

82

73

66

61

57

 

53

50

44

40

Ð

Ð

3¤4

.824

360

250

200

170

151

138

125

118

 

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

 

205

195

175

160

145

135

11¤4

1.380

1400

950

770

600

580

530

490

460

 

430

400

360

325

300

280

11¤2

1.610

2100

1460

1180

990

900

810

750

690

 

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 speci®c gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.

²This length includes an ordinary number of ®ttings.

SUPPLY DUCT OPENING

RETURN DUCT OPENING

Fig. 16 Ð Supply and Return Duct Openings

Fig. 18 Ð Vertical Duct Cover Removed

Fig. 17 Ð Lance Location for Vertical Duct

Opening CoverFig. 19 Ð Removal of Vertical Discharge Opening Cover

17

Image 17
Contents Safety Considerations Contents48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Check Equipment Receiving and InstallationProvide Unit Support Rig and Place UnitCurb Part NumberUnit WeightUnit MAX Condensate Trap Connect Condensate DrainUnit Size 48SS Physical Data Ð Unit 48SSUnit Size 48SX Physical Data Ð Unit 48SXSediment Trap Supply and Return Duct Openings Maximum Gas Flow CapacityVertical Discharge Cover Removed Install Electrical ConnectionsÐ Electrical Data Ð Unit 48SS Range Motor Ð Electrical Data Ð Unit 48SXRLA LRA FLA MCAHigh- and Control-Voltage Connections Easy Select Interface Board PRE-START-UPSTART-UP Start Up Heating Section and Make AdjustmentsGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure Unit 48SS,SX OrificesMonoport Burners Heating Temperature Rise F InputLED Indications Start Up Cooling Section and Make AdjustmentsError Code LED Indication 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS024 Ð Superheat Charging Table, 48SS018Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX060 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX048 Superheat Required Suction-Tube Temperature FTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX FAN only Cfm Cooling Cfm Unit 48SXUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Evaporator Blower and Motor Air FilterUnit Top Removal Burner Access Panel Condenser Fan Condenser Coil, Evaporator Coil, and CondenCooling TroubleshootingBurners will not ignite HeatingLED Troubleshooting Ð Error Code Service TrainingPage III. START-UP Remove and Store in Job FilePreliminary Information