REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914) Side opposite ducts . . . . . . . . . . . . . . . . . . . . 36 (914) Compressor access . . . . . . . . . . . . . . . . . . . . 36 (914) (Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm) |
|
|
Between units, control box side | . 42 | (1067) |
Unit and ungrounded surfaces, control box side | . . 36 (914) | |
Unit and block or concrete walls and other grounded |
|
|
surfaces, control box side | . 42 | (1067) |
| ELECTRICAL | UNIT WEIGHT |
| CORNER WEIGHT |
| ||
UNIT |
| (lb/kg) |
| ||||
CHARACTERISTICS |
|
|
|
| |||
|
| lb | kg | A | B | C | D |
48SX024040 | 357 | 163 | 110/50 | 56/25 | 136/62 | 55/25 | |
48SX024060 | 369 | 168 | 113/51 | 59/27 | 139/63 | 58/26 | |
48SX030040 | 360 | 164 | 103/47 | 72/33 | 124/56 | 61/28 | |
48SX030060/080 | 372 | 169 | 106/48 | 75/34 | 127/58 | 64/29 | |
48SX036060/080 | 390 | 177 | 100/45 | 90/41 | 123/56 | 77/35 | |
48SX036100/120 | 402 | 183 | 103/47 | 93/42 | 127/57 | 80/36 | |
|
|
|
|
|
|
|
|
UNIT | CENTER OF GRAVITY (in./mm) | |||
X | Y | Z | ||
| ||||
48SX024040 | 26.57/674.9 | 20.17/512.3 | 14.96/380.0 | |
48SX024060 | 26.51/673.3 | 20.22/513.6 | 14.96/380.0 | |
48SX030040 | 26.90/683.3 | 21.09/535.7 | 14.96/380.0 | |
48SX030060/080 | 26.83/681.5 | 21.11/536.2 | 14.96/380.0 | |
48SX036060/080 | 26.99/685.5 | 21.14/537.0 | 14.96/380.0 | |
48SX036100/120 | 26.92/683.8 | 21.14/537.0 | 14.96/380.0 |
|
| LEGEND |
|
| |
CG | Ð | Center of Gravity | MAT'L | Ð | Material |
COND | Ð Condenser | NEC | Ð National Electrical Code | ||
LV | Ð | Low Voltage | REQ'D | Ð | Required |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.
2.Adequate clearance around air openings into combustion chamber must be provided.
Fig. 7 Ð 48SX024-036 With Optional Base Rail, Unit Dimensions
7