Carrier 48SX024-060, 48SS018-060 Air Filter, Unit Top Removal, Evaporator Blower and Motor

Page 45

Air Filter

Never operate the unit without a suitable air ®lter in the return-air duct system. Always replace the ®lter with the same dimensional size and type as originally installed. See Tables 1 and 2 for recommended ®lter sizes.

Inspect air ®lter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice dur- ing each heating and cooling season or whenever the ®lter(s) becomes clogged with dust and lint.

Unit Top Removal

NOTE: When performing maintenance or service proce- dures that require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top removal, including: inspection of the heat exchanger area, coil inspection and cleaning, and condensate drain pan in- spection and cleaning.

Only quali®ed service personnel should perform mainte- nance and service procedures that require unit top removal. Refer to the following top removal procedures:

1.Turn off gas supply, then turn off electric power to unit.

2.Remove all screws that secure unit top, including screws around 4 sides and those on top that screw into internal divider panels. Save all screws.

3.Lift top from unit carefully. Set top on edge.

4.Carefully replace and secure unit top to unit, using screws removed in Step 2, when maintenance and/or service pro- cedures are completed. (Be sure to use original screws that have rubber washers to seal out water when securing top to internal divider panels.)

Evaporator Blower and Motor

NOTE: Motors without oilers are prelubricated. Do not at- tempt to lubricate these motors.

For longer life, operating economy, and continuing effi- ciency, clean accumulated dirt and grease from the blower wheel and motor annually.

Lubricate the motor every 5 years if the motor is used in- termittently (thermostat FAN switch in AUTO. position), or every 2 years if the motor is used continuously (thermostat FAN switch in ON position).

Turn off the gas supply, then disconnect and tag elec- trical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause personal injury or death.

To clean and lubricate the blower motor and wheel:

1.Remove and disassemble blower assembly as follows:

a.Remove blower access door.

b.On standard non-ICM units disconnect motor lead from blower relay (BR). Disconnect yellow lead from ter- minal L2 of the contactor.

c.On all units remove blower assembly from unit. Re- move screws securing blower to gas partition and slide assembly out. Be careful not to tear insulation in blower compartment.

d.Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before dis- assembly.

e.Loosen setscrew(s) that secures wheel to motor shaft, remove screws that secure motor mount brackets to

housing, and slide motor and motor mount out of housing.

2.Lubricate motor as follows:

a.Thoroughly clean all accumulations of dirt or grease from motor housing.

b.Remove dust caps or plugs from oil ports located at each end of motor.

c.Use a good grade of SAE 20 nondetergent motor oil and put one teaspoon (3¤16 oz. or 16 to 25 drops) in each oil port.

d.Allow time for oil to be absorbed by each bearing, then wipe excess oil from motor housing.

e.Replace dust caps or plugs in oil ports.

3.Remove and clean blower wheel as follows:

a.Ensure proper reassembly by marking wheel orientation.

b.Lift wheel from housing. When handling and/or clean- ing blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.

c.Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush at- tachment. Remove grease and oil with mild solvent.

d.Reassemble wheel into housing.

e.Reassemble motor into housing. Be sure setscrews are tightened on motor shaft ¯ats and not on round part of shaft.

f.Reinstall blower access door.

4.Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.

Flue Gas Passageways Ð To inspect the ¯ue col- lector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor assem- bly according to directions in Combustion-Air Blower sec- tion on page 46.

2.Remove the 3 screws holding the blower housing to the ¯ue collector box cover (see Fig. 34).

3.Remove the 12 screws holding the ¯ue collector box cover (Fig. 34) to the heat exchanger assembly. Inspect the heat exchangers.

4.Clean all surfaces as required using the wire brush.

FLUE COLLECTOR

BOX

INDUCED

DRAFT MOTOR

MOUNTING PLATE

BLOWER

HOUSING

BURNER

RACK

MOUNTING

SCREW

Fig. 34 Ð Blower Housing and Flue Collector Box

45

Image 45
Contents Safety Considerations Contents48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Check Equipment Receiving and InstallationProvide Unit Support Rig and Place UnitCurb Part NumberWeight Unit MAXUnit Condensate Trap Connect Condensate DrainUnit Size 48SS Physical Data Ð Unit 48SSUnit Size 48SX Physical Data Ð Unit 48SXSediment Trap Supply and Return Duct Openings Maximum Gas Flow CapacityVertical Discharge Cover Removed Install Electrical ConnectionsÐ Electrical Data Ð Unit 48SS Range Motor Ð Electrical Data Ð Unit 48SXRLA LRA FLA MCAHigh- and Control-Voltage Connections Easy Select Interface Board PRE-START-UPSTART-UP Start Up Heating Section and Make AdjustmentsGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure Unit 48SS,SX OrificesMonoport Burners Heating Temperature Rise F InputStart Up Cooling Section and Make Adjustments Error Code LED IndicationLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS024 Ð Superheat Charging Table, 48SS018Ð Superheat Charging Table, 48SS030 Ð Superheat Charging Table, 48SS036Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX024 Ð Superheat Charging Table, 48SX030Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX042 Ð Superheat Charging Table, 48SX048Ð Superheat Charging Table, 48SX060 Superheat Required Suction-Tube Temperature FTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX FAN only Cfm Cooling Cfm Unit 48SXMaintenance Wet Coil Pressure DropUnit Size Airflow Pressure Drop Air Filter Unit Top RemovalEvaporator Blower and Motor Burner Access Panel Condenser Fan Condenser Coil, Evaporator Coil, and CondenCooling TroubleshootingBurners will not ignite HeatingLED Troubleshooting Ð Error Code Service TrainingPage Remove and Store in Job File Preliminary InformationIII. START-UP