Carrier 48SS018-060 Ð Superheat Charging Table, 48SS018, Ð Superheat Charging Table, 48SS024

Page 36

For Integrated Control Motors (ICM) Ð To con®gure the 48SX unit, move the 5 Easy Select board wires to the terminals which control the air¯ow. Refer to the Easy Select interface board (Fig. 22) located next to the terminals and to Fig. 30 and 32.

Perform the following steps for basic system con®guration.

AUX HEAT RANGE (VIO) Ð The air¯ow for unit 48SX is preset at the factory. The air¯ow selection must not be set at a setting lower than the default. Refer to Table 15 for air¯ow and gas heat input for terminals 1-4.

AC/HP SIZE (BLU) Ð The preset factory default selection for AC/HP SIZE (air conditioner/heat pump) is set to 400 cfm/ton. The selection pins are con®gured for 350 cfm/ ton and 400 cfm/ton.

TYPE (ORN) Ð The TYPE is a preset factory default se- lection. The preset factory default setting is AC for the 48SX units. Default setting should not be altered.

AC/HP CFM ADJUST (BLK) Ð The preset factory default selection is MED. Selections HI and LO will adjust the air- ¯ow supplied for all operational modes (see following table).

The selection options allow installer to adjust air¯ow to meet such individual needs as noise and static compensation, etc.

MODE

FAN ONLY

COOLING

HEATING

LO - Adjust

−15%

−10%

−10%

HI - Adjust

15%

10%

10%

AC/HP TIME DELAY (GRY) Ð Four motor operation delay options are provided to customize system operation. See table below:

OPTION

TERMINAL

DESCRIPTION

 

 

Used when it is desirable

30-Sec On/60-Sec

 

to allow system coils time

1

to heat up or cool down

Off Delay Pro®le

 

prior to air¯ow. Enhances

 

 

 

 

system efficiency.

 

 

Preset factory default setting for

 

 

48SX. Used for servicing or

No Delay Option

2

when other components are

used to perform a delay func-

 

 

 

 

tion (e.g., integrated gas

 

 

control).

30-Sec Off Delay

3

Enhances system efficiency.

45-Sec Off Delay

4

Enhances system efficiency.

Table 8A Ð Superheat Charging Table, 48SS018

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

17.3

18.5

19.6

20.8

24.2

 

27.7

 

28.5

 

29.3

29.3

29.3

29.3

29.3

70

 

SPH

13.8

14.9

16.1

17.3

20.7

 

24.1

 

25.7

 

27.3

27.3

27.3

27.3

27.3

75

 

SPH

10.2

11.4

12.5

13.7

17.1

 

20.6

 

22.9

 

25.2

25.2

25.2

25.2

25.2

80

 

SPH

8.2

8.8

9.5

10.2

13.6

 

17.0

 

20.1

 

23.1

23.9

24.1

25.4

26.1

85

 

SPH

6.1

6.2

6.5

6.6

10.0

 

13.5

 

17.3

 

21.1

22.6

24.1

25.6

27.1

90

 

SPH

*

*

*

5.0

8.1

 

11.4

 

15.2

 

19.0

20.5

22.0

23.5

25.0

95

 

SPH

*

*

*

*

6.2

 

9.4

 

13.2

 

17.0

18.5

20.0

21.5

23.0

100

 

SPH

*

*

*

*

*

 

7.3

 

11.1

 

14.9

17.2

19.5

21.7

24.0

105

 

SPH

*

*

*

*

*

 

5.3

 

9.1

 

12.9

15.9

18.9

21.9

24.9

110

 

SPH

*

*

*

*

*

 

*

 

6.7

 

10.8

13.8

16.8

19.8

22.8

115

 

SPH

*

*

*

*

*

 

*

 

*

 

8.8

11.8

14.8

17.8

20.8

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Table 8B Ð Superheat Charging Table, 48SS024

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

800

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

18.2

19.0

19.9

20.7

22.5

 

24.2

 

25.1

 

25.9

26.6

27.2

27.9

28.6

70

 

SPH

17.1

17.6

18.1

18.6

20.4

 

22.1

 

23.0

 

23.9

24.9

26.0

27.1

28.1

75

 

SPH

16.0

16.2

16.4

16.6

18.3

 

20.1

 

21.0

 

21.8

23.3

24.8

26.2

27.7

80

 

SPH

14.8

14.7

14.6

14.5

16.3

 

18.0

 

19.7

 

21.3

22.4

23.5

24.6

25.8

85

 

SPH

13.7

13.3

12.9

12.5

14.3

 

16.0

 

18.4

 

20.7

21.5

22.3

23.1

23.8

90

 

SPH

11.1

10.9

10.7

10.4

12.2

 

13.9

 

16.3

 

18.7

19.9

21.0

22.2

23.4

95

 

SPH

8.5

8.4

8.4

8.4

10.1

 

11.9

 

14.3

 

16.6

18.2

19.8

21.4

23.0

100

 

SPH

7.3

7.5

7.7

7.9

8.9

 

9.9

 

12.2

 

14.6

16.6

18.6

20.6

22.6

105

 

SPH

6.2

6.6

6.9

7.3

7.6

 

7.8

 

10.2

 

12.5

14.9

17.3

19.7

22.1

110

 

SPH

*

*

*

5.3

5.5

 

5.8

 

8.1

 

10.5

13.3

16.1

18.9

21.7

115

 

SPH

*

*

*

*

*

 

*

 

6.1

 

8.4

11.6

14.9

18.1

21.3

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

36

Image 36
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Receiving and Installation Check EquipmentProvide Unit Support Rig and Place UnitPart Number CurbWeight Unit MAXUnit Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS Ð Electrical Data Ð Unit 48SX Range MotorRLA LRA FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure Unit 48SS,SX OrificesHeating Temperature Rise F Input Monoport BurnersStart Up Cooling Section and Make Adjustments Error Code LED IndicationLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS030 Ð Superheat Charging Table, 48SS036Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX024 Ð Superheat Charging Table, 48SX030Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX042 Ð Superheat Charging Table, 48SX048Ð Superheat Charging Table, 48SX060 Required Suction-Tube Temperature F SuperheatTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmMaintenance Wet Coil Pressure DropUnit Size Airflow Pressure Drop Air Filter Unit Top RemovalEvaporator Blower and Motor Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage Remove and Store in Job File Preliminary InformationIII. START-UP