REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. .

. 36

(914)

Compressor access

. .

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

. . . . . . 14 (356)

Bottom of unit

. .

. .

. . . . . 0

Flue panel

. .

. .

. . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

Between units, control box side

. . . . . 42 (1067)

Unit and ungrounded surfaces, control box side . . .

. .

. .

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

surfaces, control box side

. .

. .

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT

 

(lb/kg)

 

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

48SX024040

208/230-1-60

333

151

104/47

50/23

130/59

49/22

48SX024060

208/230-1-60

345

157

107/49

53/24

133/60

52/24

48SX030040

208/230-1-60

336

153

97/44

66/30

118/54

55/25

48SX030060/080

208/230-1-60

348

158

100/45

69/31

121/55

58/26

48SX036060/080

208/230-1-60, 208/230-3-60, 460-3-60

366

166

94/43

84/38

117/53

71/32

48SX036100/120

208/230-1-60, 208/230-3-60, 460-3-60

378

172

97/44

87/40

120/55

74/34

 

 

 

 

 

 

 

 

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

 

48SX024040

26.71/678

20.06/510

12.65/321

48SX024060

26.64/677

20.12/511

12.65/321

48SX030040

27.06/687

21.05/535

12.65/321

48SX030060/080

26.98/685

21.07/535

12.65/321

48SX036060/080

27.14/689

21.10/536

12.65/321

48SX036100/120

27.06/687

21.12/536

12.65/321

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 6 Ð 48SX024-036 Without Base Rail, Unit Dimensions

6

Image 6
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Provide Unit Support Receiving and InstallationCheck Equipment Rig and Place UnitPart Number CurbWeight Unit MAXUnit Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS RLA LRA Ð Electrical Data Ð Unit 48SXRange Motor FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPPressure Unit 48SS,SX Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number OrificesHeating Temperature Rise F Input Monoport BurnersStart Up Cooling Section and Make Adjustments Error Code LED IndicationLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS030 Ð Superheat Charging Table, 48SS036Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX024 Ð Superheat Charging Table, 48SX030Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX042 Ð Superheat Charging Table, 48SX048Ð Superheat Charging Table, 48SX060 Temp F Required Suction-Tube Temperature FSuperheat Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmMaintenance Wet Coil Pressure DropUnit Size Airflow Pressure Drop Air Filter Unit Top RemovalEvaporator Blower and Motor Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage Remove and Store in Job File Preliminary InformationIII. START-UP