Measure Manifold Pressure (Propane Units) Ð The main burner ori®ces on a propane gas unit are sized for the unit rated input when the manifold pressure reading matches the level speci®ed in Table 5.
Proceed as follows to adjust gas input on a propane gas unit:
1.Turn off gas to unit.
2.Remove pipe plug on manifold (see Fig. 24), then con- nect manometer at this point.
3.Turn on gas to unit.
4.Remove cover screw over regulator adjustment screw on gas valve.
5.Adjust regulator adjustment screw to the correct mani- fold pressure, as speci®ed in Table 5. Turn adjusting screw clockwise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold pressure.
6.Replace cover screw.
7.Turn off gas to unit. Remove manometer from pressure tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks.
CHECK BURNER FLAME Ð With burner access panel re- moved, observe the unit heating operation. Watch the burner ¯ames to see if they are light blue and soft in appearance, and that the ¯ames are approximately the same for each burner. Propane will have blue ¯ame with yellow tips. See Fig. 25. Refer to Maintenance section for information on burner removal.
Fig. 25 Ð Monoport Burners
AIRFLOW AND TEMPERATURE RISE Ð The heating sec- tion for each size unit is designed and approved for heating operation within the
Table 6 shows the approved
Refer to Evaporator Air¯ow and Air¯ow Adjustments sec- tion on page 35 to adjust heating air¯ow when required.
Table 6 Ð Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input
HEATING |
|
|
|
|
|
| TEMPERATURE RISE °F |
|
|
|
|
|
|
|
| ||
INPUT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Btuh) | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 |
| 75 |
| 80 | 85 | 90 |
40,000 | 1389 | 1111 | 926 | 794 | 694 | 617 | 556 | Ð | Ð | Ð | Ð | Ð | Ð |
| Ð | Ð |
|
56,000 | 2083 | 1667 | 1389 | 1190 | 1042 | 926 | 833 | 758 | Ð | Ð | Ð | Ð | Ð | Ð | Ð |
| |
80,000 | 2778 | 2222 | 1852 | 1587 | 1389 | 1235 | 1111 | 1010 | 926 | 855 | 794 |
| Ð |
| Ð | Ð | Ð |
95,000 | 3472 | 2778 | 2315 | 1984 | 1736 | 1543 | 1389 | 1263 | 1157 | 1068 | 992 |
| 926 |
| 868 | Ð | Ð |
120,000 | 4167 | 3333 | 2778 | 2381 | 2083 | 1852 | 1667 | 1515 | 1389 | 1282 | 1190 |
| 1111 |
| 1042 | 980 | 926 |
136,000 | 5037 | 4029 | 3358 | 2878 | 2518 | 2238 | 2014 | 1831 | 1679 | 1549 | 1439 |
| 1343 |
| 1259 | 1185 | 1119 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
25