Carrier 48SS018-060, 48SX024-060 Ð Electrical Data Ð Unit 48SX, Range Motor, Rla Lra, Fla Mca

Page 20

Table 4B Ð Electrical Data Ð Unit 48SX

UNIT

 

VOLTAGE

COMPRESSOR

OUTDOOR-FAN

INDOOR-FAN

POWER SUPPLY

AWG 60 C

MAX WIRE

SIZE

V-PH-Hz

RANGE

MOTOR

MOTOR

MIN WIRE

 

 

 

 

LENGTH (ft)

48SX

 

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

SIZE

 

 

024

208/230-1-60

187

253

12.9

62.5

1.4

2.0

19.5

30

12

75

030

208/230-1-60

187

253

15.0

76.0

1.4

2.6

22.8

30

10

100

 

208/230-1-60

187

253

16.7

95.0

1.4

2.8

25.1

30

10

95

036

208/230-3-60

187

253

10.9

75.0

1.4

2.8

17.8

25

12

70

 

460-3-60

414

506

5.4

40.0

0.8

1.4

9.0

10

14

100

 

208/230-1-60

187

253

20.0

104.0

1.4

3.1

29.5

45

10

80

042

208/230-3-60

187

253

13.9

88.0

1.4

3.1

21.9

30

10

60

 

460-3-60

414

506

6.8

44.0

0.8

1.6

10.9

15

14

100

 

208/230-1-60

187

253

26.4

129.0

1.4

7.2

41.6

60

6

100

048

208/230-3-60

187

253

15.0

99.0

1.4

7.2

27.4

40

10

70

 

460-3-60

414

506

8.2

49.5

0.8

2.3

13.4

20

14

100

060

208/230-1-60

187

253

32.1

169.0

2.1

7.2

49.4

60

6

100

208/230-3-60

187

253

19.3

123.0

2.1

7.2

33.4

50

8

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

AWG

Ð American Wire Gage

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and

 

Refrigeration

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

RLA

Ð Rated Load Amps

*Fuse or HACR Breaker.

²Carrier Scroll Compressor. **Copeland Scroll Compressor.

NOTES:

1.In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas As- sociation) units may be fuse or circuit breaker.

2.Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, de- termine size from NEC.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 1 464 1 455 3

= 1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 − 45 2 = 5 v

(BC) 464 − 45 7 = 7 v

(AC) 457 − 45 5 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

 

7

457

 

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

20

Image 20
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Receiving and Installation Check EquipmentProvide Unit Support Rig and Place UnitPart Number CurbUnit WeightUnit MAX Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS Ð Electrical Data Ð Unit 48SX Range MotorRLA LRA FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure Unit 48SS,SX OrificesHeating Temperature Rise F Input Monoport BurnersLED Indications Start Up Cooling Section and Make AdjustmentsError Code LED Indication 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX060 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX048 Required Suction-Tube Temperature F SuperheatTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Evaporator Blower and Motor Air FilterUnit Top Removal Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage III. START-UP Remove and Store in Job FilePreliminary Information