Carrier 48SX024-060, 48SS018-060 user manual Ð Electrical Data Ð Unit 48SS

Page 19

Table 4A Ð Electrical Data Ð Unit 48SS

UNIT

 

VOLTAGE

COMPRESSOR

OUTDOOR-FAN

INDOOR-FAN

POWER SUPPLY

AWG 60 C

MAX WIRE

SIZE

V-PH-Hz

RANGE

MOTOR

MOTOR

MIN WIRE

 

 

 

 

LENGTH (ft)

48SS

 

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

SIZE

 

 

018

208/230-1-60

187

253

8.3

45.0

0.7

1.8

12.9

15

14

75

024

208/230-1-60

187

253

12.4

61.0

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82.0

1.4

2.3

21.4

30

10

100

208/230-3-60

187

253

9.4

66.0

1.4

2.0

15.1

25

12

80

 

 

208/230-1-60

187

253

18.0

96.0

1.4

2.8

26.7

40

10

90

036

208/230-3-60

187

253

11.7

75.0

1.4

2.8

18.8

30

12

65

 

460-3-60

414

506

5.6

40.0

0.8

1.4

9.2

10

14

100

 

208/230-1-60

187

253

20.4

104.0

1.4

4.0

30.9

50

8

100

042

208/230-3-60

187

253

14.0

91.0

1.4

4.0

22.9

35

10

85

 

460-3-60

414

506

6.4

42.0

0.8

2.0

10.8

15

14

100

 

208/230-1-60²

187

253

21.8

124.0

2.1

5.0

40.1

60

8

100

 

208/230-1-60**

187

253

26.4

129.0

2.1

5.0

40.1

60

6

100

048

208/230-3-60²

187

253

12.8

93.0

2.1

5.0

25.9

40

10

75

208/230-3-60**

187

253

15.0

99.0

2.1

5.0

25.9

40

10

75

 

 

460-3-60²

414

506

6.4

46.5

1.1

2.3

13.7

20

14

100

 

460-3-60**

414

506

8.2

50.0

1.1

2.3

13.7

20

14

100

 

208/230-1-60

187

253

32.1

169.0

2.1

6.8

49.0

60

6

100

060

208/230-3-60

187

253

19.3

123.0

2.1

6.8

33.0

50

8

90

 

460-3-60

414

506

10.0

62.0

1.1

3.2

16.8

25

12

100

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

AWG

Ð American Wire Gage

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and

 

Refrigeration

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

RLA

Ð Rated Load Amps

*Fuse or HACR Breaker.

²Carrier Scroll Compressor. **Copeland Scroll Compressor.

NOTES:

1.In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas As- sociation) units may be fuse or circuit breaker.

2.Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, de- termine size from NEC.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 1 464 1 455 3

= 1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 − 45 2 = 5 v

(BC) 464 − 45 7 = 7 v

(AC) 457 − 45 5 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

 

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

19

Image 19
Contents Safety Considerations Contents48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Rig and Place Unit Receiving and InstallationCheck Equipment Provide Unit SupportCurb Part NumberUnit MAX WeightUnit Condensate Trap Connect Condensate DrainUnit Size 48SS Physical Data Ð Unit 48SSUnit Size 48SX Physical Data Ð Unit 48SXSediment Trap Supply and Return Duct Openings Maximum Gas Flow CapacityVertical Discharge Cover Removed Install Electrical ConnectionsÐ Electrical Data Ð Unit 48SS FLA MCA Ð Electrical Data Ð Unit 48SXRange Motor RLA LRAHigh- and Control-Voltage Connections Easy Select Interface Board PRE-START-UPSTART-UP Start Up Heating Section and Make AdjustmentsOrifices Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number Pressure Unit 48SS,SXMonoport Burners Heating Temperature Rise F InputError Code LED Indication Start Up Cooling Section and Make AdjustmentsLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS024 Ð Superheat Charging Table, 48SS018Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX048 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX060 Unit Motor AIR Required Suction-Tube Temperature FSuperheat Temp FExternal Static Pressure in. wg 48SX FAN only Cfm Cooling Cfm Unit 48SXWet Coil Pressure Drop MaintenanceUnit Size Airflow Pressure Drop Unit Top Removal Air FilterEvaporator Blower and Motor Burner Access Panel Condenser Fan Condenser Coil, Evaporator Coil, and CondenCooling TroubleshootingBurners will not ignite HeatingLED Troubleshooting Ð Error Code Service TrainingPage Preliminary Information Remove and Store in Job FileIII. START-UP