Carrier 48SS018-060, 48SX024-060 user manual 48SS018-042 Without Base Rail, Unit Dimensions

Page 2

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

. .

. 36

(914)

Compressor access

. .

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

.

. 14 (356)

Bottom of unit

. . . . . 0

Flue panel

.

. 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

Between units, control box side

 

. 42 (1067)

Unit and ungrounded surfaces, control box side

.

. 36 (914)

Unit and block or concrete walls and other grounded

 

 

surfaces, control box side

 

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT HEIGHT

UNIT

 

(lb/kg)

 

(in./mm)

CHARACTERISTICS

 

 

 

 

 

 

lb

kg

A

B

C

D

E

48SS180040

208/230-1-60

272

123

81/37

62/28

76/35

53/24

24.1/613

48SS024040

208/230-1-60

303

138

97/44

43/20

123/56

40/18

24.1/613

48SS024060

208/230-1-60

315

143

100/45

46/21

126/57

43/20

24.1/613

48SS030040

208/230-1-60, 208/230-3-60

320

145

100/45

47/21

126/57

47/21

24.1/613

48SS030060/080

208/230-1-60, 208/230-3-60

332

149

103/46

50/22

129/58

50/23

24.1/613

48SS036060/080

208/230-1-60, 208/230-3-60, 460-3-60

336

153

86/39

76/35

111/50

63/29

24.1/613

48SS036100/120

208/230-1-60, 208/230-3-60, 460-3-60

348

158

89/40

79/36

114/52

66/30

24.1/613

48SS042060/080

208/230-1-60, 208/230-3-60, 460-3-60

375

170

95/43

86/39

119/54

75/34

28.1/714

48SS042100/120

208/230-1-60, 208/230-3-60, 460-3-60

387

176

98/45

89/40

122/55

78/35

28.1/714

 

 

 

 

 

 

 

 

 

UNIT

F

G

CENTER OF GRAVITY in./mm

 

in./mm

in./mm

X

Y

Z

48SS018040

 

 

25.07/637

20.59/523

 

48SS024040

 

 

27.07/688

23.35/593

 

48SS024060

 

 

26.98/685

23.27/591

 

48SS030040

169¤16/420.7

1815¤16/481.0

26.71/678

23.46/596

10.85/276

48SS030060/080

 

 

27.15/689

22.36/568

 

48SS036060/080

 

 

27.50/698

22.48/571

 

48SS036100/120

 

 

27.40/696

22.44/570

 

48SS042060/080

209¤16/522.3

2215¤16/582.6

27.01/686

22.44/570

12.7/321

48SS042100/120

26.94/684

22.44/570

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 2 Ð 48SS018-042 Without Base Rail, Unit Dimensions

2

Image 2
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Provide Unit Support Receiving and InstallationCheck Equipment Rig and Place UnitPart Number CurbUnit WeightUnit MAX Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS RLA LRA Ð Electrical Data Ð Unit 48SXRange Motor FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPPressure Unit 48SS,SX Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number OrificesHeating Temperature Rise F Input Monoport BurnersLED Indications Start Up Cooling Section and Make AdjustmentsError Code LED Indication 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX060 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX048 Temp F Required Suction-Tube Temperature FSuperheat Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Evaporator Blower and Motor Air FilterUnit Top Removal Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage III. START-UP Remove and Store in Job FilePreliminary Information