Table 12 Ð
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT | MOTOR | AIR |
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| |||||
48SS | SPEED | DELIVERY | 0.0 | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | |
| Low | Watts | ² | 295 | 251 | 223 | 201 | 176 | 149 | 124 | ² | ² | ² | |
018 | Cfm | ² | 821 | 817 | 753 | 665 | 536 | 343 | 164 | ² | ² | ² | ||
| ||||||||||||||
High | Watts | 401 | 376 | 346 | 322 | 294 | 272 | 250 | 229 | 219 | ² | ² | ||
| ||||||||||||||
| Cfm | 1334 | 1253 | 1128 | 996 | 816 | 658 | 461 | 246 | 167 | ² | ² | ||
|
| |||||||||||||
| Low | Watts | ² | 285 | 284 | 282 | 278 | 274 | 270 | 261 | 251 | 244 | 230 | |
| Cfm | ² | 798 | 761 | 727 | 682 | 634 | 581 | 525 | 450 | 371 | 304 | ||
|
| |||||||||||||
024, | Med | Watts | ² | 378 | 371 | 368 | 362 | 357 | 343 | 332 | 315 | 301 | 283 | |
030 | Cfm | ² | 1011 | 982 | 948 | 906 | 858 | 771 | 703 | 597 | 492 | 387 | ||
| ||||||||||||||
| High | Watts | ² | 520 | 511 | 487 | 472 | 451 | 431 | 411 | 385 | 362 | 341 | |
| Cfm | ² | 1342 | 1309 | 1237 | 1181 | 1106 | 1007 | 892 | 745 | 610 | 471 | ||
|
| |||||||||||||
| Low | Watts | ² | 460 | 439 | 423 | 398 | 379 | 349 | 322 | 297 | 270 | 246 | |
| Cfm | ² | 1191 | 1136 | 1081 | 1005 | 907 | 795 | 687 | 579 | 471 | 349 | ||
|
| |||||||||||||
036 | Med | Watt | ² | 511 | 492 | 470 | 450 | 420 | 392 | 364 | 332 | 308 | 275 | |
Cfm | ² | 1316 | 1244 | 1178 | 1104 | 1005 | 891 | 784 | 657 | 535 | 389 | |||
|
| |||||||||||||
| High | Watts | ² | 655 | 631 | 603 | 584 | 552 | 522 | 492 | 459 | 433 | 398 | |
| Cfm | ² | 1541 | 1458 | 1367 | 1292 | 1178 | 1053 | 920 | 806 | 662 | 509 | ||
|
| |||||||||||||
| Low | Watts | ² | 637 | 612 | 587 | 560 | 526 | 493 | 455 | ² | ² | ² | |
042 | Cfm | ² | 1500 | 1450 | 1405 | 1350 | 1290 | 1200 | 1105 | ² | ² | ² | ||
| ||||||||||||||
High | Watts | ² | 790 | 750 | 700 | 679 | 639 | 608 | 574 | 547 | ² | ² | ||
| ||||||||||||||
| Cfm | ² | 1750 | 1675 | 1604 | 1509 | 1421 | 1323 | 1221 | 1094 | ² | ² | ||
|
| |||||||||||||
| Low | Watts | ² | 847 | 784 | 746 | 708 | 646 | 609 | 563 | 516 | ² | ² | |
048 | Cfm | ² | 1995 | 1901 | 1822 | 1730 | 1580 | 1477 | 1319 | 1178 | ² | ² | ||
| ||||||||||||||
High | Watts | ² | ² | 909 | 852 | 820 | 801 | 751 | 687 | 639 | ² | ² | ||
| ||||||||||||||
| Cfm | ² | ² | 2018 | 1896 | 1814 | 1729 | 1582 | 1380 | 1270 | ² | ² | ||
|
| |||||||||||||
| Low | Watts | ² | 983 | 950 | 923 | 885 | 845 | 804 | 751 | 697 | 665 | 633 | |
| Cfm | ² | 1838 | 1808 | 1755 | 1702 | 1628 | 1553 | 1446 | 1339 | 1257 | 1175 | ||
|
| |||||||||||||
060 | Med | Watts | ² | 1115 | 1083 | 1045 | 1006 | 964 | 921 | 872 | 823 | 783 | 742 | |
Cfm | ² | 2067 | 2023 | 1957 | 1891 | 1807 | 1723 | 1612 | 1501 | 1392 | 1282 | |||
|
| |||||||||||||
| High | Watts | ² | 1284 | 1201 | 1166 | 1131 | 1092 | 1053 | 1001 | 950 | 907 | 864 | |
| Cfm | ² | 2167 | 2108 | 2038 | 1968 | 1882 | 1796 | 1676 | 1555 | 1437 | 1318 | ||
|
|
*Air delivery values are without air ®lter and are for dry coil. See Table 17 for wet coil pressure drop. Deduct
²Unit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling air¯ow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity.
Table 13 Ð
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT | MOTOR | AIR |
|
|
| EXTERNAL STATIC PRESSURE (in. wg) |
|
|
| |||||
48SX | SPEED | DELIVERY | 0.0 | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | |
| Low | Watts | 280 | 275 | 265 | 255 | 250 | 245 | 240 | ² | ² | ² | ² | |
| Cfm | 820 | 810 | 755 | 700 | 660 | 600 | 560 | ² | ² | ² | ² | ||
|
| |||||||||||||
024, | Med | Watts | 365 | 360 | 350 | 345 | 340 | 330 | 320 | 310 | 300 | ² | ² | |
030 | Cfm | 1025 | 1010 | 975 | 940 | 900 | 850 | 800 | 720 | 630 | ² | ² | ||
| ||||||||||||||
| High | Watts | ² | ² | 490 | 480 | 470 | 460 | 445 | 430 | 410 | 390 | 380 | |
| Cfm | ² | ² | 1300 | 1255 | 1200 | 1150 | 1080 | 1005 | 915 | 790 | 620 | ||
|
| |||||||||||||
| Low | Watts | 520 | 495 | 474 | 458 | 445 | 425 | ² | ² | ² | ² | ² | |
| Cfm | 1375 | 1335 | 1290 | 1240 | 1200 | 1140 | ² | ² | ² | ² | ² | ||
|
| |||||||||||||
036 | Med | Watts | 575 | 560 | 535 | 510 | 480 | 460 | 440 | 425 | ² | ² | ² | |
Cfm | 1520 | 1490 | 1450 | 1400 | 1380 | 1300 | 1200 | 1080 | ² | ² | ² | |||
|
| |||||||||||||
| High | Watts | ² | ² | ² | ² | 650 | 614 | 575 | 540 | 510 | 480 | ² | |
| Cfm | ² | ² | ² | ² | 1560 | 1500 | 1380 | 1280 | 1170 | 1060 | ² | ||
|
| |||||||||||||
| Low | Watts | 490 | 480 | 470 | 460 | 450 | 430 | 410 | 390 | ² | ² | ² | |
| Cfm | 1400 | 1380 | 1340 | 1300 | 1250 | 1200 | 1140 | 1070 | ² | ² | ² | ||
|
| |||||||||||||
042 | Med | Watts | 590 | 580 | 560 | 545 | 525 | 505 | 480 | 450 | 420 | ² | ² | |
Cfm | 1600 | 1560 | 1540 | 1470 | 1430 | 1360 | 1300 | 1220 | 1120 | ² | ² | |||
|
| |||||||||||||
| High | Watts | ² | ² | ² | ² | ² | 700 | 670 | 640 | 600 | 560 | 500 | |
| Cfm | ² | ² | ² | ² | ² | 1780 | 1670 | 1600 | 1480 | 1340 | 1100 | ||
|
| |||||||||||||
| Low | Watts | 1050 | 1000 | 970 | 930 | 870 | 810 | 750 | 680 | 600 | ² | ² | |
048** | Cfm | 1850 | 1830 | 1800 | 1785 | 1750 | 1700 | 1640 | 1500 | 1330 | ² | ² | ||
| ||||||||||||||
High | Watts | ² | ² | ² | 1050 | 1000 | 930 | 870 | 810 | 740 | 665 | ² | ||
| ||||||||||||||
| Cfm | ² | ² | ² | 2000 | 1940 | 1850 | 1750 | 1635 | 1500 | 1300 | ² | ||
|
|
*Air delivery values are without air ®lter and are for dry coil. See Table 17 for wet coil pressure drop. Deduct
²Unit air delivery is outside of operating range.
**For 460 v units only.
NOTE: Do not operate the unit at a cooling air¯ow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity.