Carrier 48SS018-060, 48SX024-060 user manual Troubleshooting, Cooling

Page 48

TROUBLESHOOTING

Cooling

SYMPTOM

CAUSE

REMEDY

 

 

 

Compressor and

Power failure

Call power company.

condenser fan will

 

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

not start.

Defective thermostat, contactor, transformer,

Replace component.

 

 

or control relay

 

 

 

 

 

Insufficient line voltage

Determine cause and correct.

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

 

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not

Faulty wiring or loose connections in

Check wiring and repair or replace.

start but condenser

compressor circuit

 

fan runs.

 

 

Compressor motor burned out, seized, or

Determine cause. Replace compressor.

 

internal overload open

 

 

Defective run/start capacitor, overload,

Determine cause and replace.

 

start relay

 

 

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Three-phase scroll

Scroll compressor is rotating in the

Correct the direction of rotation by reversing the

compressor (Units

wrong direction

3-phase power leads to the unit. Shut down unit to

48SS048,060 and

 

allow pressures to equalize.

48SX036-060 only)

 

 

makes excessive

 

 

noise, and there

 

 

may be a low pres-

 

 

sure differential.

 

 

Compressor cycles

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and

(other than normally

 

recharge to capacities shown on nameplate.

satisfying

 

 

Defective compressor

Replace and determine cause.

thermostat).

Insufficient line voltage

Determine cause and correct.

 

 

Blocked condenser

Determine cause and correct.

 

Defective run/start capacitor, overload

Determine cause and replace.

 

or start relay

 

 

Defective thermostat

Replace thermostat.

 

Faulty condenser-fan motor or capacitor

Replace.

 

Restriction in refrigerant system

Locate restriction and remove.

Compressor

Dirty air ®lter

Replace ®lter.

operates

 

 

Unit undersized for load

Decrease load or increase unit size.

continuously.

Thermostat set too low

Reset thermostat.

 

 

Low refrigerant charge

Locate leak, repair, and recharge.

 

Leaking valves in compressor

Replace compressor.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head

Dirty air ®lter

Replace ®lter.

pressure.

 

 

Dirty condenser coil

Clean coil.

 

 

Refrigerant overcharged

Recover excess refrigerant.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too

Low refrigerant charge

Check for leaks, repair and recharge.

low.

 

 

Compressor valves leaking

Replace compressor.

 

 

Restriction in liquid tube

Remove restriction.

Excessive suction

High heat load

Check for source and eliminate.

pressure.

 

 

Compressor valves leaking

Replace compressor.

 

 

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure

Dirty air ®lter

Replace ®lter.

too low.

 

 

Low refrigerant charge

Check for leaks, repair and recharge.

 

 

Metering device or low side restricted

Remove source of restriction.

 

Insufficient evaporator air¯ow

Increase air quantity. Check ®lter Ð replace if

 

 

necessary.

 

Temperature too low in conditioned area

Reset thermostat.

 

Outdoor ambient below 40 F

Install low-ambient kit.

 

Field-installed ®lter-drier restricted

Replace.

48

Image 48
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Receiving and Installation Check EquipmentProvide Unit Support Rig and Place UnitPart Number CurbWeight Unit MAXUnit Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS Ð Electrical Data Ð Unit 48SX Range MotorRLA LRA FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure Unit 48SS,SX OrificesHeating Temperature Rise F Input Monoport BurnersStart Up Cooling Section and Make Adjustments Error Code LED IndicationLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS030 Ð Superheat Charging Table, 48SS036Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX024 Ð Superheat Charging Table, 48SX030Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX042 Ð Superheat Charging Table, 48SX048Ð Superheat Charging Table, 48SX060 Required Suction-Tube Temperature F SuperheatTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmMaintenance Wet Coil Pressure DropUnit Size Airflow Pressure Drop Air Filter Unit Top RemovalEvaporator Blower and Motor Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage Remove and Store in Job File Preliminary InformationIII. START-UP