Carrier 48SX024-060 Ð Superheat Charging Table, 48SS030, Ð Superheat Charging Table, 48SS036

Page 37

Table 8C Ð Superheat Charging Table, 48SS030

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

14.2

15.1

16.1

17.1

19.2

 

21.3

 

23.3

 

24.7

25.9

27.2

27.8

28.5

70

 

SPH

13.6

14.1

14.6

15.0

17.1

 

19.2

 

21.3

 

22.8

24.2

25.7

26.3

26.9

75

 

SPH

13.0

13.0

13.0

13.0

15.1

 

17.2

 

19.2

 

20.9

22.6

24.2

24.8

25.4

80

 

SPH

10.9

11.0

11.0

10.9

13.6

 

16.1

 

18.7

 

20.1

21.4

22.7

23.6

24.4

85

 

SPH

8.9

8.9

8.9

8.9

12.0

 

15.1

 

18.2

 

19.2

20.2

21.2

22.4

23.5

90

 

SPH

8.3

8.4

8.4

8.3

10.9

 

13.6

 

16.2

 

17.7

19.2

20.8

21.6

22.5

95

 

SPH

7.8

7.8

7.8

7.8

9.9

 

12.0

 

14.1

 

16.1

18.2

20.2

20.9

21.7

100

 

SPH

7.3

7.3

7.3

7.3

9.3

 

11.4

 

13.6

 

15.6

17.6

19.7

20.2

20.7

105

 

SPH

6.7

6.7

6.7

6.7

8.8

 

10.9

 

13.0

 

15.0

17.1

19.1

19.4

19.8

110

 

SPH

*

*

*

*

6.7

 

8.9

 

10.9

 

13.0

15.0

17.1

18.0

18.9

115

 

SPH

*

*

*

*

*

 

6.8

 

8.9

 

10.9

13.0

15.0

16.5

18.0

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Table 8D Ð Superheat Charging Table, 48SS036

TEMP (F)

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

1200

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

64

66

 

68

70

72

74

76

65

 

SPH

8.4

8.4

8.4

8.4

12.5

16.7

18.7

 

20.7

22.0

23.4

24.8

26.1

70

 

SPH

5.0

5.0

5.0

5.0

9.0

13.1

15.9

 

18.6

20.0

21.3

22.7

24.0

75

 

SPH

*

*

*

*

5.4

9.6

13.1

 

16.6

17.9

19.3

20.6

22.0

80

 

SPH

*

*

*

*

*

6.0

10.3

 

14.5

15.9

17.3

18.6

20.0

85

 

SPH

*

*

*

*

*

*

7.5

 

12.5

13.9

15.2

16.5

17.9

90

 

SPH

*

*

*

*

*

*

5.4

 

10.4

12.5

14.6

16.8

18.8

95

 

SPH

*

*

*

*

*

*

*

 

8.4

11.3

14.1

17.0

19.8

100

 

SPH

*

*

*

*

*

*

*

 

6.4

10.0

13.5

17.1

20.7

105

 

SPH

*

*

*

*

*

*

*

 

*

8.7

13.0

17.3

21.7

110

 

SPH

*

*

*

*

*

*

*

 

*

9.3

12.4

15.6

18.7

115

 

SPH

*

*

*

*

*

*

*

 

*

10.0

11.9

13.8

15.8

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Table 8E Ð Superheat Charging Table, 48SS042

TEMP (F)

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

1400

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

64

 

66

 

68

70

72

74

76

65

 

SPH

11.0

11.0

11.0

14.0

17.0

20.0

 

22.0

 

24.0

26.0

26.0

27.7

28.6

70

 

SPH

7.5

7.5

7.5

10.4

13.4

16.4

 

18.9

 

21.4

24.0

25.0

26.1

27.1

75

 

SPH

*

*

*

6.9

9.9

12.9

 

15.9

 

18.9

21.9

23.2

24.4

25.7

80

 

SPH

*

*

*

5.9

8.4

10.8

 

13.8

 

16.8

19.8

21.3

22.8

24.9

85

 

SPH

*

*

*

5.0

6.9

8.8

 

11.8

 

14.8

17.8

19.5

21.1

22.8

90

 

SPH

*

*

*

*

6.0

6.8

 

10.2

 

13.7

17.3

18.6

20.0

21.4

95

 

SPH

*

*

*

*

*

5.0

 

8.7

 

12.7

16.7

17.8

18.9

20.0

100

 

SPH

*

*

*

*

*

*

 

6.5

 

10.5

14.6

16.4

18.2

20.0

105

 

SPH

*

*

*

*

*

*

 

*

 

8.4

12.6

15.1

17.6

20.0

110

 

SPH

*

*

*

*

*

*

 

*

 

8.0

12.0

14.2

16.4

18.6

115

 

SPH

*

*

*

*

*

*

 

*

 

7.7

11.5

13.4

15.3

17.2

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

37

Image 37
Contents Safety Considerations Contents48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Check Equipment Receiving and InstallationProvide Unit Support Rig and Place UnitCurb Part NumberUnit MAX WeightUnit Condensate Trap Connect Condensate DrainUnit Size 48SS Physical Data Ð Unit 48SSUnit Size 48SX Physical Data Ð Unit 48SXSediment Trap Supply and Return Duct Openings Maximum Gas Flow CapacityVertical Discharge Cover Removed Install Electrical ConnectionsÐ Electrical Data Ð Unit 48SS Range Motor Ð Electrical Data Ð Unit 48SXRLA LRA FLA MCAHigh- and Control-Voltage Connections Easy Select Interface Board PRE-START-UPSTART-UP Start Up Heating Section and Make AdjustmentsGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure Unit 48SS,SX OrificesMonoport Burners Heating Temperature Rise F InputError Code LED Indication Start Up Cooling Section and Make AdjustmentsLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS024 Ð Superheat Charging Table, 48SS018Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX048 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX060 Superheat Required Suction-Tube Temperature FTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX FAN only Cfm Cooling Cfm Unit 48SXWet Coil Pressure Drop MaintenanceUnit Size Airflow Pressure Drop Unit Top Removal Air FilterEvaporator Blower and Motor Burner Access Panel Condenser Fan Condenser Coil, Evaporator Coil, and CondenCooling TroubleshootingBurners will not ignite HeatingLED Troubleshooting Ð Error Code Service TrainingPage Preliminary Information Remove and Store in Job FileIII. START-UP