Carrier 48SS018-060, 48SX024-060 user manual Ð Superheat Charging Table, 48SS060

Page 38

Table 8F Ð Superheat Charging Table, 48SS048 (Carrier Scroll Compressor)

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

15.5

15.5

15.6

15.6

17.6

 

19.6

 

21.6

 

22.8

24.0

25.2

25.2

25.3

70

 

SPH

11.7

11.8

11.8

11.8

13.9

 

16.0

 

18.0

 

20.1

22.2

24.3

24.3

24.3

75

 

SPH

8.0

8.0

8.0

8.0

10.2

 

12.3

 

14.5

 

17.4

20.4

23.3

23.3

23.3

80

 

SPH

6.0

6.0

6.0

6.0

8.7

 

11.3

 

13.9

 

16.3

18.6

20.9

21.5

22.0

85

 

SPH

*

*

*

*

7.2

 

10.3

 

13.4

 

15.1

16.8

18.5

19.7

20.8

90

 

SPH

*

*

*

*

5.6

 

7.7

 

9.9

 

12.4

15.0

17.6

18.7

19.8

95

 

SPH

*

*

*

*

*

 

5.2

 

6.3

 

9.8

13.2

16.7

17.7

18.8

100

 

SPH

*

*

*

*

*

 

*

 

5.8

 

9.1

12.5

15.8

17.1

18.4

105

 

SPH

*

*

*

*

*

 

*

 

5.2

 

8.4

11.7

14.9

16.5

18.1

110

 

SPH

*

*

*

*

*

 

*

 

6.2

 

8.8

11.4

14.0

15.9

17.8

115

 

SPH

*

*

*

*

*

 

*

 

7.1

 

9.1

11.1

13.1

15.3

17.5

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Table 8G Ð Superheat Charging Table, 48SS048 (Copeland Scroll Compressor)

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

19.0

19.0

19.0

19.0

21.7

 

24.3

 

26.0

 

27.7

27.9

28.2

28.4

28.6

70

 

SPH

15.4

15.4

15.4

15.4

18.1

 

20.8

 

22.5

 

24.1

25.1

26.1

27.1

28.1

75

 

SPH

11.9

11.9

11.9

11.9

14.6

 

17.2

 

18.9

 

20.6

22.3

24.0

25.8

27.5

80

 

SPH

8.4

8.4

8.4

8.4

11.0

 

13.7

 

15.4

 

17.0

19.5

22.0

24.5

27.0

85

 

SPH

5.0

5.0

5.0

5.0

7.5

 

10.1

 

11.8

 

13.5

16.7

20.0

23.2

26.4

90

 

SPH

*

*

*

*

*

 

6.6

 

9.0

 

11.4

14.7

17.9

21.1

24.4

95

 

SPH

*

*

*

*

*

 

*

 

6.2

 

9.4

12.6

15.9

19.1

22.3

100

 

SPH

*

*

*

*

*

 

*

 

*

 

7.3

10.6

13.8

17.0

20.3

105

 

SPH

*

*

*

*

*

 

*

 

*

 

5.3

8.5

11.8

15.0

18.2

110

 

SPH

*

*

*

*

*

 

*

 

*

 

*

6.9

11.2

15.5

19.8

115

 

SPH

*

*

*

*

*

 

*

 

*

 

*

5.3

10.6

16.0

21.3

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

Table 8H Ð Superheat Charging Table, 48SS060

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1995

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

20.1

20.1

20.1

20.1

20.1

 

20.1

 

22.6

 

25.2

25.6

26.1

26.6

27.0

70

 

SPH

16.5

16.5

16.5

16.5

17.3

 

18.0

 

20.6

 

23.1

24.0

24.8

25.6

26.5

75

 

SPH

13.0

13.0

13.0

13.0

14.5

 

16.0

 

18.5

 

21.1

22.3

23.5

24.7

25.9

80

 

SPH

10.9

10.9

10.9

10.9

12.4

 

13.9

 

16.5

 

19.0

20.6

22.2

23.8

25.4

85

 

SPH

8.9

8.9

8.9

8.9

10.4

 

11.9

 

14.4

 

17.0

18.9

20.9

22.9

24.9

90

 

SPH

6.9

6.9

6.9

6.9

8.4

 

9.9

 

12.4

 

14.9

17.3

19.6

22.0

24.3

95

 

SPH

5.0

5.0

5.0

5.0

6.3

 

7.8

 

10.3

 

12.9

15.6

18.3

21.1

23.8

100

 

SPH

*

*

*

*

*

 

5.8

 

8.3

 

10.8

13.9

17.0

20.1

23.2

105

 

SPH

*

*

*

*

*

 

*

 

6.2

 

8.8

12.3

15.7

19.2

22.7

110

 

SPH

*

*

*

*

*

 

*

 

*

 

6.7

10.6

14.4

18.3

22.2

115

 

SPH

*

*

*

*

*

 

*

 

*

 

*

8.9

13.1

17.4

21.6

LEGEND

*Do not attempt to charge system under these conditions Ð refrig-

Ewb Ð Entering Wet Bulb

erant slugging may occur.

SPH Ð Superheat at Compressor (F)

 

38

Image 38
Contents Contents Safety Considerations48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Provide Unit Support Receiving and InstallationCheck Equipment Rig and Place UnitPart Number CurbUnit WeightUnit MAX Connect Condensate Drain Condensate TrapPhysical Data Ð Unit 48SS Unit Size 48SSPhysical Data Ð Unit 48SX Unit Size 48SXSediment Trap Maximum Gas Flow Capacity Supply and Return Duct OpeningsInstall Electrical Connections Vertical Discharge Cover RemovedÐ Electrical Data Ð Unit 48SS RLA LRA Ð Electrical Data Ð Unit 48SXRange Motor FLA MCAHigh- and Control-Voltage Connections PRE-START-UP Easy Select Interface BoardStart Up Heating Section and Make Adjustments START-UPPressure Unit 48SS,SX Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number OrificesHeating Temperature Rise F Input Monoport BurnersLED Indications Start Up Cooling Section and Make AdjustmentsError Code LED Indication 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS018 Ð Superheat Charging Table, 48SS024Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX060 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX048 Temp F Required Suction-Tube Temperature FSuperheat Unit Motor AIRExternal Static Pressure in. wg 48SX Unit 48SX FAN only Cfm Cooling CfmUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Evaporator Blower and Motor Air FilterUnit Top Removal Burner Access Panel Condenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting CoolingHeating Burners will not igniteService Training LED Troubleshooting Ð Error CodePage III. START-UP Remove and Store in Job FilePreliminary Information