Carrier 48SX024-060, 48SS018-060 user manual Heating, Burners will not ignite

Page 49

Cooling (cont)

SYMPTOM

CAUSE

REMEDY

 

 

 

Integrated control

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft.

motor

 

 

Insufficient voltage at motor

Determine cause and correct.

(units 48SX048,060

 

 

208/230 v)

Power connectors not properly

Connectors should snap easily; do not

IFM does not run.

seated

force.

Integrated control

Motor programmed with a delay

Allow a few minutes for motor to shut off.

motor (units

pro®le

 

48SX048,060

 

 

With thermostat in OFF the voltage

If measured voltage is more than 1¤2, the

208/230 v)

on G,Y1,Y/Y2,W with respect to

thermostat is incompatible with motor. If

IFM runs when it

common, should be 1¤2 of actual

voltage is less than 1¤2, the motor has failed.

should be off.

low voltage supply

 

 

 

 

 

 

Integrated control

Water dripping into motor

Verify proper drip loops in connector wires.

motor (units

 

 

48SX048,060

 

 

Connectors not ®rmly seated

Gently pull wires individually to be sure they

208/230 v) IFM

 

are crimped into the housing.

operation is

 

intermittent.

 

 

IFM Ð Evaporator (Indoor) Fan Motor

 

Heating

SYMPTOM

CAUSE

 

REMEDY

 

 

 

Burners will not ignite.

Water in gas line

Drain. Install drip leg.

 

No power to furnace

Check power supply fuses, wiring, or circuit breaker.

 

No 24-v power supply to control

Check transformer.

 

circuit

NOTE: Some transformers have internal overcurrent

 

 

protection that requires a cool-down period to reset.

 

Miswired or loose connections

Check all wiring and wirenut connections.

 

Burned-out heat anticipator in

Replace thermostat.

 

thermostat

 

 

 

Broken thermostat wire

Run continuity check. Replace wire if necessary.

 

Misaligned spark electrodes

Check ¯ame ignition and sense electrode positioning.

 

 

Adjust as necessary.

 

No gas at main burners

1.

Check gas line for air. Purge as necessary.

 

 

 

NOTE: After purging gas line of air, wait at least

 

 

 

5 minutes for any gas to dissipate before attempt-

 

 

 

ing to light unit.

 

 

2.

Check gas valve.

Inadequate heating.

Dirty air ®lter

Clean or replace ®lter as necessary.

 

Gas input to furnace too low

Check gas pressure at manifold. Match with that on

 

 

unit nameplate.

 

Unit undersized for application

Replace with proper unit or add additional unit.

 

Restricted air¯ow

Clean or replace ®lter. Remove any restriction.

 

Blower speed too low

Use faster speed tap if available, or install alternate

 

 

motor.

 

Limit switch cycles main burners

Check rotation of blower, thermostat heat antic-

 

 

ipator settings, temperature rise of unit. Adjust as

 

 

necessary.

Poor ¯ame characteristics.

Incomplete combustion results in:

1.

Tighten all screws around burner compartment.

 

Aldehyde odors, carbon monox-

2.

Cracked heat exchanger. Replace.

 

ide, sooting ¯ame, ¯oating ¯ame

3. Unit over®red. Reduce input (change ori®ces or

 

 

 

adjust gas line or manifold pressure).

 

 

4.

Check burner alignment.

49

Image 49
Contents Safety Considerations Contents48SS018-042 Without Base Rail, Unit Dimensions 48SS018-042 With Optional Base Rail, Unit Dimensions 48SS048,060 Without Base Rail, Unit Dimensions 48SS048,060 With Optional Base Rail, Unit Dimensions 48SX024-036 Without Base Rail, Unit Dimensions 48SX024-036 With Optional Base Rail, Unit Dimensions 48SX042-060 Without Base Rail, Unit Dimensions 48SX042-060 With Optional Base Rail, Unit Dimensions Check Equipment Receiving and InstallationProvide Unit Support Rig and Place UnitCurb Part NumberUnit MAX WeightUnit Condensate Trap Connect Condensate DrainUnit Size 48SS Physical Data Ð Unit 48SSUnit Size 48SX Physical Data Ð Unit 48SXSediment Trap Supply and Return Duct Openings Maximum Gas Flow CapacityVertical Discharge Cover Removed Install Electrical ConnectionsÐ Electrical Data Ð Unit 48SS Range Motor Ð Electrical Data Ð Unit 48SXRLA LRA FLA MCAHigh- and Control-Voltage Connections Easy Select Interface Board PRE-START-UPSTART-UP Start Up Heating Section and Make AdjustmentsGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure Unit 48SS,SX OrificesMonoport Burners Heating Temperature Rise F InputError Code LED Indication Start Up Cooling Section and Make AdjustmentsLED Indications 208/230-1-60 Wiring Diagram, Units 48SS018-060 208/230-3-60 Wiring Diagram, Units 48SS030-060 460-3-60 Wiring Diagram, Units 48SS036-060 208/230-1-60 Wiring Diagram, Units 48SX024-042 208/230-1-60 Wiring Diagram, Units 48SX048,060 208/230-3-60 Wiring Diagram, Units 48SX036-042 208/230-3-60 Wiring Diagram, Units 48SX048,060 460-3-60 Wiring Diagram, Units 48SX036-048 Checking and Adjusting Refrigerant Charge Ð Superheat Charging Table, 48SS024 Ð Superheat Charging Table, 48SS018Ð Superheat Charging Table, 48SS036 Ð Superheat Charging Table, 48SS030Ð Superheat Charging Table, 48SS042 Ð Superheat Charging Table, 48SS060 Ð Superheat Charging Table, 48SX030 Ð Superheat Charging Table, 48SX024Ð Superheat Charging Table, 48SX036 Ð Superheat Charging Table, 48SX048 Ð Superheat Charging Table, 48SX042Ð Superheat Charging Table, 48SX060 Superheat Required Suction-Tube Temperature FTemp F Unit Motor AIRExternal Static Pressure in. wg 48SX FAN only Cfm Cooling Cfm Unit 48SXWet Coil Pressure Drop MaintenanceUnit Size Airflow Pressure Drop Unit Top Removal Air FilterEvaporator Blower and Motor Burner Access Panel Condenser Fan Condenser Coil, Evaporator Coil, and CondenCooling TroubleshootingBurners will not ignite HeatingLED Troubleshooting Ð Error Code Service TrainingPage Preliminary Information Remove and Store in Job FileIII. START-UP