Cooling (cont)
SYMPTOM | CAUSE | REMEDY | |
|
|
| |
Integrated control | Blower wheel not secured to shaft | Properly tighten blower wheel to shaft. | |
motor |
|
| |
Insufficient voltage at motor | Determine cause and correct. | ||
(units 48SX048,060 | |||
|
| ||
208/230 v) | Power connectors not properly | Connectors should snap easily; do not | |
IFM does not run. | seated | force. | |
Integrated control | Motor programmed with a delay | Allow a few minutes for motor to shut off. | |
motor (units | pro®le |
| |
48SX048,060 |
|
| |
With thermostat in OFF the voltage | If measured voltage is more than 1¤2, the | ||
208/230 v) | on G,Y1,Y/Y2,W with respect to | thermostat is incompatible with motor. If | |
IFM runs when it | |||
common, should be 1¤2 of actual | voltage is less than 1¤2, the motor has failed. | ||
should be off. | low voltage supply |
| |
|
| ||
|
|
| |
Integrated control | Water dripping into motor | Verify proper drip loops in connector wires. | |
motor (units |
|
| |
48SX048,060 |
|
| |
Connectors not ®rmly seated | Gently pull wires individually to be sure they | ||
208/230 v) IFM | |||
| are crimped into the housing. | ||
operation is |
| ||
intermittent. |
|
| |
IFM Ð Evaporator (Indoor) Fan Motor |
|
Heating
SYMPTOM | CAUSE |
| REMEDY |
|
|
| |
Burners will not ignite. | Water in gas line | Drain. Install drip leg. | |
| No power to furnace | Check power supply fuses, wiring, or circuit breaker. | |
| No | Check transformer. | |
| circuit | NOTE: Some transformers have internal overcurrent | |
|
| protection that requires a | |
| Miswired or loose connections | Check all wiring and wirenut connections. | |
| Replace thermostat. | ||
| thermostat |
|
|
| Broken thermostat wire | Run continuity check. Replace wire if necessary. | |
| Misaligned spark electrodes | Check ¯ame ignition and sense electrode positioning. | |
|
| Adjust as necessary. | |
| No gas at main burners | 1. | Check gas line for air. Purge as necessary. |
|
|
| NOTE: After purging gas line of air, wait at least |
|
|
| 5 minutes for any gas to dissipate before attempt- |
|
|
| ing to light unit. |
|
| 2. | Check gas valve. |
Inadequate heating. | Dirty air ®lter | Clean or replace ®lter as necessary. | |
| Gas input to furnace too low | Check gas pressure at manifold. Match with that on | |
|
| unit nameplate. | |
| Unit undersized for application | Replace with proper unit or add additional unit. | |
| Restricted air¯ow | Clean or replace ®lter. Remove any restriction. | |
| Blower speed too low | Use faster speed tap if available, or install alternate | |
|
| motor. | |
| Limit switch cycles main burners | Check rotation of blower, thermostat heat antic- | |
|
| ipator settings, temperature rise of unit. Adjust as | |
|
| necessary. | |
Poor ¯ame characteristics. | Incomplete combustion results in: | 1. | Tighten all screws around burner compartment. |
| Aldehyde odors, carbon monox- | 2. | Cracked heat exchanger. Replace. |
| ide, sooting ¯ame, ¯oating ¯ame | 3. Unit over®red. Reduce input (change ori®ces or | |
|
|
| adjust gas line or manifold pressure). |
|
| 4. | Check burner alignment. |
49