Sigma S2Ba, S2Ca warranty Technical data, external contact, Controller type 0 see identity code

Page 38

Features of the S2Ca metering pumps

Dulcodes UV-Desinfektionsanlage

 

 

Technical data, external contact

Semi-conductor switch elements (e.g. transistors in open-collector circuits) or contactors (relays) with a residual voltage of -0.7 V can be used as input switch elements.

Controller type 0 (see identity code)

Pin 1 = Pause input (activating function)

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V)

Pin 2 = Contact input

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V) Min. contact duration: 20 ms

Max. pulse frequency: 25 pulses/s

Pin 3 = unused

Pin 4 = GND

Pin 5 = Auxiliary input

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V)

Controller type 1 (see identity code)

Pin 1 = Pause input (activating function)

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V)

Pin 2 = Contact input (not active during analogue operation)

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V) Min. contact duration: 20 ms

Max. pulse frequency: 25 pulses/s

Pin 3 = Identical to input*

Input load:

approx. 120

Pin 4 = GND

Pin 5 = Auxiliary input

Voltage at open contacts: approx. 5 V

Input resistance: 10 k

Controller: – zero volts contact (approx. 0.5 mA)

semi-conductor (residual voltage: < 0.7 V)

* The metering pump makes its first metering stroke at approx. 0.4 mA (4.4 mA) and starts continuous operation at approx. 19.2 mA.

Page 38

ProMinent®

Image 38
Contents Operating Instructions Control elements and key functions Control elements overviewOperating-/Settings Diagram Continuous DisplayPrevious Analog ActivatedfunctionImprint Dulcodes UV-Desinfektionsanlage ImprintDulcodes UV-Desinfektionsanlage Table of contents Table of contents Dulcodes UV-Desinfektionsanlage Identcode ordering system B a G m a B a s i c Ty p e S 2 B aIdentcode ordering system Dulcodes UV-Desinfektionsanlage ProMinent Dulcodes UV-Desinfektionsanlage Safety devices General notesDulcodes UV-Desinfektionsanlage Design/Functional description Functional description, drive Product description S2Ba/S2CaIdentification of pump type Stroke movement 75 % 30 %Metering capacity diagram HM50Hz MeteringcapacitydiagramS2BaS2CaHM Functional description, delivery unit Design and functional description refer to Fig. No Integrated overflow valve with bleeder functionTask Product description S2Ba/S2Ca Function Diaphragm rupture sensorUse for intended purpose/Use unintended purpose Design and function description see Fig3162-4 Pvdf Ptfe Technical data Technical data Sigma Capacity dataAccuracy Technical data S2CaTemperature specifications Model Connector Dimensions Sigma/ 2 mmDimension sheet Sigma/ 2 with stroke adjustment motor Stroke actuator drive mechanism Stroke adjuster drive mechanismMotor data Electrical data, stroke sensor ÒSigmaÓSound intensity level Input voltage Mains frequency Power consumptionElectrical data, pacing relay ÒSigmaÓ Relay inputStart-up Start-up/MaintenanceMaintenance Replacement of wearing parts Maintenance intervalsGuideline on Valve Installation Function description, controller Features of the S2Ca metering pumpsFunction description, motors ÒFault indicating and pacing relayÓ option ÒFloat switchÓ functionOptional Òfault-indicating relayÓ or Òpower relayÓ LED indicator Operating indicator greenSockets, symbols and wiring diagram Hierarchy of operating modes, functions and fault statusesRelay type Power relay Wiring diagram Controller type 1 see identity code Technical data, external contactController type 0 see identity code Pump, Inside Block circuit diagram S2CaInputs OutputsCircuit examples universal signal cable By customer CableRetrofitting relays Not in Profibus version Delivery rangeControl elements Settings SetSelect operating mode Mode menu Check adjustable valuesChange to settings mode Settings for ÒanalogueÓ operating mode Analg menu Settings for operating mode SET menuSettings for ÒmanualÓ operating mode Set Straight lineLower band Upper band Alkali pump Acid pump Settings for ÒcontactÓ operating mode Contct menuLower/upper band Lower bandSet Settings for ÒbatchÓ operating mode Batch menu ÒMemoryÓ extension functionSettings for programmable functions SET menu Settings for ÒcalibrationÓ function Calib menuSetting code Code menu Settings for Òauxiliary frequencyÓ function AUX menuSettings for the ÒflowÓ function Flow menu Cancel total stroke number or total litres Clear windowOperating Manual operationTroubleshooting Remote controlError Messages Decommissioning and disposal Spare parts and accessories ProMinent 1011036For pumps without Ex protection For pumps with Ex protection Valve assy DN 15/PVT* Order No 6105-1040100-03 Order No Retrofit kit double diaphragm S2Ba/S2Ca Stroke actuator wiring diagram Wiring diagram for stroke length adjuster