Lennox International Inc ML193DF Gas Pressure Adjustment, Proper Combustion, Dial

Page 38

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 11

GAS METER CLOCKING CHART

 

Seconds for One Revolution

 

 

 

 

 

 

 

ML193

Natural

 

LP

 

Unit

1 cu ft

2 cu ft

 

1 cu ft

 

2 cu ft

 

Dial

Dial

 

Dial

 

DIAL

 

 

 

 

 

 

 

−045

80

160

 

200

 

400

 

 

 

 

 

 

 

−070

55

110

 

136

 

272

 

 

 

 

 

 

 

−090

41

82

 

102

 

204

 

 

 

 

 

 

 

−110

33

66

 

82

 

164

 

 

 

 

 

 

 

Natural−1000 btu/cu ft

LP−2500 btu/cu ft

 

NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.

Furnace should operate at least 5 minutes before check- ing gas flow. Determine time in seconds for two revolu- tions of gas through the meter. (Two revolutions assures a more accurate time). Divide by two and compare to time in table 11. If manifold pressure matches table 12 and rate is incorrect, check gas orifices for proper size and restric- tion. Remove temporary gas meter if installed.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. See table 12 for proper supply line pressure. Replace the threaded plug af- ter measurements have been taken.

TABLE 12

Manifold and Supply Pressure (Outlet) inches w.c.

 

Model

 

Supply

 

Manifold

Pressure in.wg.

Fuel

Input Sizes

Pressure in.wg.

 

 

 

 

Min.

Max.

 

 

 

 

 

 

 

 

Nat. Gas

All sizes

3.5

4.5

10.0

 

 

 

 

 

 

 

L.P. Gas

All sizes

10.0

11.0

13.0

 

 

 

 

 

 

 

NOTE − A natural to L.P. propane gas changeover kit is nec- essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Manifold Pressure Measurement

1 − Remove the threaded plug from the outlet side of the gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pres- sure.

2 − Start unit and allow 5 minutes for unit to reach steady state.

3 − While waiting for the unit to stabilize, notice the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4 − After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 12.

NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com- bustion. Take combustion sample beyond the flue outlet and compare to the tables below. The maximum carbon monoxide reading should not exceed 50 ppm.

TABLE 13

ML193

CO2% For Nat

CO2% For L.P.

Unit

 

 

 

 

 

−045

 

 

 

 

 

−070

7.2 − 7.9

8.6 − 9.3

 

−090

 

 

 

 

 

−110

 

 

 

 

High Altitude Information

 

 

 

 

NOTE − In Canada, certification for installations at eleva- tions over 4500 feet (1372 m) is the jurisdiction of local au- thorities.

ML193DF units require no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048 m) above sea level. Units installed at altitude of 4501 − 10,000 feet (1373 to 3048m) require a pressure switch change which can be ordered separately. Table 14 lists conversion kit and pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory−set and re- quires no adjustment.

NOTE − A natural to LP/propane gas changeover kit is nec- essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Page 38

Image 38
Contents Installation Instructions ML193DF Table of ContentsML193DF Unit Dimensions − inches mm ML193DFControl BOX BAG AssemblyML193DF Parts Arrangement Blower MotorML193DF Gas Furnace Safety InformationDirect Vent Installation NON−DIRECT Vent Shipping and Packing ListUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirEquipment in Confined Space − ALL AIR from Inside Shipping Bolt Removal Equipment in Confined Space − ALL AIR from OutsideFront Horizontal Back Installation − Setting EquipmentSetting Equipment NON−COMBUSTIBLE Floor Opening Size NC‡− Seal the cabinet and check for air leaks Combustible Flooring Base Opening SizeSide View Filters Pipe & Fittings SpecificationsPiping and Fittings Specifications Duct SystemOutdoor Termination Kits Usage Piping Suspension Guidelines Joint Cementing ProcedureVenting Practices ScheduleML193DF MIN. Vent Length Model Vent Piping GuidelinesMinimum Vent Pipe Lengths Maximum Allowable Intake or Exhaust Vent Length in Feet Intake Exhaust Typical Exhaust Pipe ConnectionsTypical Intake Pipe Connections Typical AIR Intake Pipe Connections Inside Corner Detail Inches 305mm or 12 in mmUS Installations1 Canadian Installations2 FLUSH−MOUNT Side Wall Termination KIT 51W11 − On field supplied terminations, a minimum distanceDirect Vent Roof Termination KIT 51mm 76mm Vent Pipe Unconditioned Space Reducer MAY beRequired to Adapt SupportFront View Top ViewExhaust 203mm − 305mm NON−DIRECT Vent Roof Termination KITML193DF NON−DIRECT Vent Application Using Existing Chimney ML193DF with Evaporator Coil To drainTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC Gas Piping Furnace Isolate GAS ValveGAS Pipe Capacity − FT3/HR kL/HR Electrostatic Discharge ESD Precautions and ProceduresElectrical Exterior MAKE−UP BOX FACTORY− Installed Left Side MAKE−UPInterior MAKE−UP BOX BOX InsideTypical ML193DF Field Wiring Diagram Thermostat DesignationsTypical ML193DF Wiring Diagram Integrated Control For Your Safety Read Before OperatingUnit Start−Up Automatic Hot Surface Ignition SystemPage Proper Combustion Gas Pressure AdjustmentGAS Meter Clocking Chart High Altitude Information73W37 73W81 68W68 74W90 74W91 69W73 2286 − 3038m2286m 3048m No Jumper Other Unit AdjustmentsHeat FAN-OFF Time in Seconds Blower Data High Low In. w.g Cfm Watts Cfm Watts cfm WattsService Electrical SHOCK, Fire Or Explosion HazardPage Diagnostic Codes Planned ServiceIgnition Control Board Diagnostic Codes LED #1 Red LED #2 GreenHeating Sequence of Operation Troubleshooting Heating Sequence of OperationNormal Heating Mode Abnormal Heating Mode Heating Sequence Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationNormal Cooling Mode Abnormal Cooling Mode Troubleshooting Continuous Fan Sequence of Operation Continuous Heat Speed FAN Sequence of OperationRepair Parts List Return AIR Duct System Supply AIR Duct Start−Up & Performance Check ListGAS Supply Intake / Exhaust PipeCondensate Line Thermostat Temperature RiseTotal External Static Drain Line Vent PipeRequirements for Commonwealth of Massachusetts LY BELOW. Keep Clear of ALL OBSTRUC- Tions