Lennox International Inc ML193DF Requirements for Commonwealth of Massachusetts

Page 52

Requirements for Commonwealth of Massachusetts

Modifications to NFPA−54, Chapter 10

Revise NFPA−54 section 10.8.3 to add the following re- quirements:

For all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfied:

1 − INSTALLATION OF CARBON MONOXIDE DETEC- TORS. At the time of installation of the side wall, hori- zontally vented, gas−fueled equipment, the installing plumber or gasfitter shall observe that a hard−wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery−oper- ated or hard−wired carbon monoxide detector with an alarm is installed on each additional level of the dwell- ing, building or structure served by the side wall, hori- zontally vented, gas−fueled equipment. It shall be the responsibility of the property owner to secure the ser- vices of qualified licensed professionals for the instal- lation of hard−wired carbon monoxide detectors.

a − In the event that the side wall, horizontally vented, gas−fueled equipment is installed in a crawl space or an attic, the hard−wired carbon monoxide detec- tor with alarm and battery back−up may be installed on the next adjacent floor level.

b − In the event that the requirements of this subdivi- sion cannot be met at the time of completion of installation, the owner shall have a period of thirty

(30)days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery−operated carbon monoxide detec- tor with an alarm shall be installed.

2 − APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi- fied.

3 − SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade di- rectly in line with the exhaust vent terminal for the hori- zontally vented, gas−fueled heating appliance or equipment. The sign shall read, in print size no less than one−half (1/2) inch in size,

LY BELOW. KEEP CLEAR OF ALL OBSTRUC- TIONS."

4 − INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas−fueled equipment shall not approve the installation unless, upon inspec- tion, the inspector observes carbon monoxide detec- tors and signage installed in accordance with the pro- visions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:

1 − The equipment listed in Chapter 10 entitled

ment Not Required to Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2 − Product Approved side wall, horizontally vented, gas− fueled equipment installed in a room or structure sepa- rate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS −

GAS EQUIPMENT VENTING SYSTEM PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment provides a vent- ing system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1 − Detailed instructions for the installation of the venting system design or the venting system components: and

2 − A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS −

GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment does not pro- vide the parts for venting the flue gases, but identifies cial venting systems," the following requirements shall be satisfied by the manufacturer:

1 − The referenced instructions

shall be included with the appliance or equipment installation instructions; and

2The

proved by the Board, and the instructions for that sys- tem shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall, horizontally vented, gas−fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc- tions shall remain with the appliance or equipment at the completion of the installation.

Page 52

Image 52
Contents Installation Instructions ML193DF Table of ContentsML193DF Unit Dimensions − inches mm ML193DFBAG Assembly ML193DF Parts ArrangementControl BOX Blower MotorSafety Information Direct Vent Installation NON−DIRECT VentML193DF Gas Furnace Shipping and Packing ListUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirEquipment in Confined Space − ALL AIR from Inside Shipping Bolt Removal Equipment in Confined Space − ALL AIR from OutsideSetting Equipment Installation − Setting EquipmentFront Horizontal Back NON−COMBUSTIBLE Floor Opening Size NC‡Side View Combustible Flooring Base Opening Size− Seal the cabinet and check for air leaks Pipe & Fittings Specifications Piping and Fittings SpecificationsFilters Duct SystemOutdoor Termination Kits Usage Joint Cementing Procedure Venting PracticesPiping Suspension Guidelines ScheduleMinimum Vent Pipe Lengths Vent Piping GuidelinesML193DF MIN. Vent Length Model Maximum Allowable Intake or Exhaust Vent Length in Feet Typical Intake Pipe Connections Typical Exhaust Pipe ConnectionsIntake Exhaust Typical AIR Intake Pipe Connections Inside Corner Detail Inches 305mm or 12 in mmUS Installations1 Canadian Installations2 Direct Vent Roof Termination KIT − On field supplied terminations, a minimum distanceFLUSH−MOUNT Side Wall Termination KIT 51W11 51mm 76mm Vent Pipe Reducer MAY be Required to AdaptUnconditioned Space SupportFront View Top ViewExhaust 203mm − 305mm NON−DIRECT Vent Roof Termination KITML193DF NON−DIRECT Vent Application Using Existing Chimney ML193DF with Evaporator Coil To drainTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC Gas Piping Furnace Isolate GAS ValveGAS Pipe Capacity − FT3/HR kL/HR Electrical Precautions and ProceduresElectrostatic Discharge ESD FACTORY− Installed Left Side MAKE−UP Interior MAKE−UP BOXExterior MAKE−UP BOX BOX InsideTypical ML193DF Field Wiring Diagram Thermostat DesignationsTypical ML193DF Wiring Diagram For Your Safety Read Before Operating Unit Start−UpIntegrated Control Automatic Hot Surface Ignition SystemPage Gas Pressure Adjustment GAS Meter Clocking ChartProper Combustion High Altitude Information2286m 3048m 2286 − 3038m73W37 73W81 68W68 74W90 74W91 69W73 Heat FAN-OFF Time in Seconds Other Unit AdjustmentsNo Jumper Blower Data High Low In. w.g Cfm Watts Cfm Watts cfm WattsService Electrical SHOCK, Fire Or Explosion HazardPage Planned Service Ignition Control Board Diagnostic CodesDiagnostic Codes LED #1 Red LED #2 GreenNormal Heating Mode Abnormal Heating Mode Troubleshooting Heating Sequence of OperationHeating Sequence of Operation Heating Sequence Normal Cooling Mode Abnormal Cooling Mode Troubleshooting Cooling Sequence of OperationCooling Sequence of Operation Troubleshooting Continuous Fan Sequence of Operation Continuous Heat Speed FAN Sequence of OperationRepair Parts List Start−Up & Performance Check List GAS SupplyReturn AIR Duct System Supply AIR Duct Intake / Exhaust PipeTemperature Rise Total External Static Drain LineCondensate Line Thermostat Vent PipeRequirements for Commonwealth of Massachusetts LY BELOW. Keep Clear of ALL OBSTRUC- Tions