Electrical work
The electrical work should be performed by a specialist qualified for the work.
ffUse the three phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit (separately purchased by the user).
❋❋Avoid multiple connecting wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.
ffBe sure to install circuit breaker (separately purchased by the user). ffBe sure to connect the grounding wire.
|
|
| Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible | |
|
|
| cord. (Code designation IEC:60245 IEC 66 / | |
NOTE | ||||
|
1.Remove the screw on the electrical component box and remove the cover plate.
2.Route the connection cord through the side of the indoor unit and connect the cable to terminals.
3.Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4.Reassemble the electrical component box cover, carefully tightening the screw.
Wiring standard
| Model | AP50M0✴ Series / AP50M1✴ Series | |
Power |
|
| 3N~, |
Circuit breaker |
|
| Earth leakage circuit breaker(ELCB) 30A |
Electric wire |
| Below 20m | 2.5mm2 |
| Below 50m | 4mm2 | |
|
| ||
Allowable voltage | 342~457V | ||
Min. size of electric wires from/to the | Below 20m : 0.75mm2 | ||
indoor/outdoor units | Over 20m : 1mm2 |
•You must compress the solderless ring to the cable and then connect it to the main power terminal. CAUTION • Solderless ring selection
Silver solder
Thickness of cable (mm2) | B (mm) | d2 (mm) |
|
|
|
2.5 | Less than 9.5 | More than 4.5 |
|
|
|
4 | Less than 9.5 | More than 4.5 |
|
|
|
NOTE
34
This equipment complies with IEC
[Ssc (*2)]
MODEL | Ssc[MVA] |
|
|
AP50M0AXXSG | 0.528 |
|
|
AP50M1AXXSG | 0.528 |
|
|