Samsung AP50M1ANXSG, AP50M0ANXSG manual Air purge, Be sure that all valve cocks are closed

Page 44

Air purge

❋❋Be sure that all valve cocks are closed.

ffThe air in the indoor unit and in the pipe must be purged. Make sure to vacuum inside of the connection pipe using vacuum pump after connecting pipes.(Use vacuum pump as shown at the figure.) If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity and could lead to a malfunction.

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

3.Open the valve of the low pressure side of manifold gauge counter-clockwise.

4.Purge the air from the system using vacuum pump for about 10 minutes. -- Close the valve of the low pressure side of manifold gauge clockwise. -- Turn off the vacuum pump.

-- Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes. -- This procedure is very important in order to avoid gas leak.

-- Remove the hose of the low pressure side of manifold gauge.

5.Set valve cork of both liquid side and gas side of packed valve to the open position.

6.Mount the cap and the needle valve cap to the valve (see the below illustration), and tighten them at the torque of 183kgf•cm with a torque wrench.

7.Check for gas leakage.

-- At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.

Gas pipe side

Liquid pipe side

OUTDOOR UNIT

Indoor unit

A

B

 

Liquid pipe side

Gas pipe side

 

 

 

Flare nut

 

 

 

Valve cock

Vacuum Pump

 

 

3-way valve

3-way valve

 

Cap

 

 

 

 

Needle valve

 

Outdoor unit

 

 

 

 

cap

 

 

44

Mirage_AP50M0@_IBIM_EN_05323A-02.indd 44

2016-05-19 오후 1:27:26

Image 44
Contents Air Conditioner Thank you for purchasing this Samsung productLook for Everywhere Features of your new air conditionerStrong Turbo/Long Function Contents Do not yank the power cable with hands Safety precautionsImportant safety symbols and precautions Ensure no water gets into the air conditioner Use a rated circuit breaker only FfPotential risk of injury or electric shockFfPotential risk of personal injury Do not open the front panel during operationFfPotential risk of personal injury or property loss Do not allow children to climb on the air conditionerFfInsufficient ventilation may result in poor performance FfWearing thick gloves can protect your hands Viewing your air conditioner Checking the indoor unit and displayMain parts To open the panelControl panel Heater and Purity function is not supported by this modelChecking the remote controller Remote controller buttonsAre in the same space Remote controller displayUsing the remote controller Battery changing time Storing the remote controllerInserting the batteries Indoor unitBasic operation Turning on the power Selecting the operation modeAdjusting the desired temperature Selecting the fan speedSelecting air flow direction Setting the On/Off timer When the air conditioner is offYou cannot set the fan speed when setting the On timer Controller displayWhen the air conditioner is on ButtonUsing the Turbo function When the air conditioner is operating in Cool or Heat modeUsing the Long function Locking the control panelUsing the air conditioner with the control panel Cleaning the filter Air filter Cleaning and maintaining the air conditionerCleaning the exterior Periodical checks Installation partMaintaining your air conditioner Have deposited at low temperatures Internal protections via the unit control systemTroubleshooting AppendixOperation ranges HumidityInstalling the unit Or accessing its internal componentsGeneral information PersonnelPower supply line, fuse or circuit breaker Do not install the air conditioner in following placesMake sure that you earth the cables Complete, electric shock or fire may occurAccessory parts list Selection of installation place Indoor unitTop view Side viewOutdoor unit Ventilate Preparing the installationSelecting appropriate location for installation Space requirements Wear protective goggles and mask before sprayingWiring standard Electrical workCord. Code designation IEC60245 IEC 66 / CENELECH07RN-F Ssc *2AP50M0 Series Indoor and outdoor connection wiringUsing 4poles ELCBEarth Leakage Circuit Breaker Using 3poles Elcb and 2poles Elcb AP50M1 SeriesElectrical wiring Connecting the power terminalInstallation method Outdoor unit When using the anchor boltWhen using the rubber leg Installation proceduresTrap Check the following list and install an oil trap Refrigerant pipe work Insulating the pipesOil trap FfRadius of curvature R on the oil trap are as followsCut the pipe using the pipe cutter Connection of refrigerant piping Flare processingRemove burr on the edge of pipe It may cause explosion and injuryDrilling a hole in the wall Pipe bendingTightening of connection parts Wall installation Corner Installation Drain hoseFixing the indoor unit ExampleAir purge Be sure that all valve cocks are closedCheck the stability of the pressure for 10 minutes How to add refrigerantRefrigerant charging Is grounding properly made? Check and test operationCheck Test operation Pump down procedure When removing the productWhen the outdoor temperature is below zero, do not Packing and unpacking guide Outdoor unit How to connect your extended power cables Mm of the wire shields of the tubePrepare the following tools TubeFfMethod Apply heat to the contraction tube to contract itMirageAP50M0@IBIMEN05323A-02.indd 2016-05-19 오후 English Questions or COMMENTS?